> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/courseware/electric-courseware/electric-machines-courseware/mastering-synchronous-machines-using-real-time-simulation-laboratories/synchronous-generator-connected-to-the-grid.md).

# Synchronous Generator Connected To The Grid

## Objective <a href="#id-6.1-objective" id="id-6.1-objective"></a>

This exercise presents the implementation of the synchronous machine operating in generator mode and connected to the grid (infinite bus) at constant frequency and voltage.\
After completing the procedure to synchronize the generator to the grid, we study the control of active and reactive power flow with the grid and the operating stability limits.

## Initialization of the Setup <a href="#id-6.2-initialization-of-the-setup" id="id-6.2-initialization-of-the-setup"></a>

When the simulator is started up, the initial settings on screen are as follows:

1. Continuous voltage supplies SC1, SC2, SC3 set to 0 V.
2. Continuous voltage supply SC4, in the "Measurement Resistors" tab, set to 0 V.
3. Alternative power SA1, in the "AC Grid" tab, set to 0 V.
4. Switches K<sub>1</sub>, K<sub>2</sub>, K<sub>3</sub>, K<sub>4</sub> opened: synchronous generator armature has no load.
5. Switch K<sub>6</sub> disabled: the synchronous machine rotor is driven by the DC motor.
6. Switch K<sub>5</sub> disabled: voltage source SC3 powers the synchronous machine field winding.
7. Trigger switches K<sub>10</sub>, K<sub>11</sub>, K<sub>12</sub>, K<sub>13</sub>, K<sub>14</sub>, in the "Oscilloscope" tab, disabled.

## 6.3 Connecting the Generator to the Grid <a href="#id-6.3-connecting-the-generator-to-the-grid" id="id-6.3-connecting-the-generator-to-the-grid"></a>

In this exercise, the synchronous machine is operating in generator mode and is driven by the DC motor.\
It will be connected to the AC grid at constant frequency and voltage.\
In the basic tests on the synchronous machine recommended in this manual, we consider the AC grid as an infinite bus, i.e., a balanced, three-phase voltage source with constant frequency and voltage.

In a grid of this type, the balance of active and reactive power exchanged is always maintained by the appropriate automatic command from various power plants and voltage regulating devices (synchronous generator exciters, static compensators and synchronous compensators, to name just a few).

We use voltage source SC1 together with SC2, as in the procedure described in Section 4.3, to control the generator's speed and the frequency of the armature voltage before connecting it to the grid.

The user can then close switch K<sub>1</sub> to connect the synchronous machine to the grid, which supplies autotransformer SA1.\
Once connected, the constant frequency of the infinite bus will force the drive speed.\
By the same token, the constant voltage of the infinite bus will force the RMS voltage at the armature terminals of the synchronous machine.

Therefore, voltage source SC2 will control the torque provided by the DC motor, and, consequently, the active power exchanged between the synchronous machine and the infinite bus (under the assumption that conversion losses are small enough, therefore neglected).

Notice that on this virtual test bench, it is even possible to reverse the sign of the torque provided by the DC machine, and therefore, the power flow between the synchronous machine and the infinite bus (in other words, the DC machine is operating in generator mode and the synchronous machine is in motor mode).

After connecting the synchronous generator to the grid, the user has two inputs to control the active and reactive power exchanged between the synchronous machine and the infinite bus: (i) the torque available at the coupling shaft that can be adjusted using the DC motor control and (ii) the field current of the synchronous machine.

In this exercise, the nature, features and reversibility of these two control inputs are investigated, as well as the operating limits of the synchronous machine.

### 6.3.1 Setup Diagram <a href="#id-6.3.1-setup-diagram" id="id-6.3.1-setup-diagram"></a>

<figure><img src="https://4054096626-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FYbyVjpgEQX9nfCkpYoFP%2Fuploads%2FKUgr4Mw8fyghebzaKx4w%2F2907a95d-ca7b-4a3d-8109-1e5c2ccc987c.png?alt=media&amp;token=4f5e7b8d-3e9f-444d-936c-b97bc84f2e10" alt="" width="480"><figcaption><p><strong>Figure 11</strong>: Synchronous machine connected to infinite grid</p></figcaption></figure>

### 6.3.2 Exercise <a href="#id-6.3.2-exercise" id="id-6.3.2-exercise"></a>

To avoid harmful currents or transient torques when connecting the synchronous generator to the infinite bus, the three instantaneous voltages measured on both sides of the K<sub>1</sub> switch, i.e., at (i) the generator armature and (ii) the infinite bus must be approximately equal before closing the switch.\
Consequently:

* The frequency and the RMS values of the voltages on both sides of the switch must be as close to identical
* The sequence of the phases must be the same

The following steps describe the connection process:

1. Select the "Oscilloscopes1" tab.\
   The scope to the left displays two signals: (i) the line-neutral voltage of phase a of the generator's armature, in yellow, and (ii) the line-neutral voltage of phase a of the infinite bus, in red.\
   The scope to the right displays the same entities but for phase b.\
   Enable switch K<sub>10</sub> to activate the trigger for the Oscilloscopes 1 group.\
   Buttons "xscale" and "yscale" can be used to adjust time and voltage scales, respectively.
2. Follow the procedure used to start the DC motor, described in Section 4.3, to set the synchronous generator no-load speed as close as possible to the synchronization speed (1798 rpm for example).\
   In this way, the generator output voltage frequencies are very close to 60 Hz.
3. Gradually increase, starting from 0, current J<sub>f</sub> supplied by the DC voltage source SC3, which is feeding the synchronous machine field winding, in such a way that the line-line RMS voltage of the generator armature is U<sub>s</sub> = 460 V.
4. In the "AC Grid" tab, adjust the line-line RMS voltage of the autotransformer SA1 to U = 460 V.
5. Check that the sequence of voltage phases on both sides of switch K<sub>1</sub> are identical by observing instantaneous line-neutral voltages on both scopes.\
   Notice, the slight difference in the frequency between the machine and the grid voltages, on both scopes.\
   That is due to the difference between the rotating speed (almost 1798 rpm) and the synchronization speed (1800 rpm).\
   If both instantaneous voltages, displayed on both scopes, are in phase at the same time, the sequence of phases is OK.\
   If not, enable switch K<sub>7</sub>, which inverse autotransformer SA1 phase sequences.\
   To better understand the functioning of switch K<sub>7</sub>, the user can observe the behavior of the phases for the two possible positions of that switch.
6. To achieve the generator to grid connection, close switch K<sub>1</sub> once the two instantaneous voltages are identical.\
   If a fuse is blown after closing K<sub>1</sub>, then the connection procedure has failed.\
   In this case, it is necessary to wait until the speed decreases to 0 and then return to the initial setting described in Section 6.2.\
   Then, and only then, the user can simulate the fuse replacement by resetting the protection system (Reset) using button K<sub>8</sub>.\
   After that, the entire connection procedure must be repeated from the previous step.
7. The synchronous generator is now connected to the grid and, the drive speed dictated by the infinite bus frequency must be constant and equal to 1800 rpm.\
   Additionally, the line-line RMS voltage at the generator armature is also constant and equal to 460 V.

{% hint style="info" %}
If, after closing switch K<sub>1,</sub> (i) the drive speed is not exactly at 1800 rpm, (ii) the internal angle θ is not constant and (ii) the RMS current in the armature is significant, then the connection procedure has failed, even though the protection system was not triggered.\
It means that the generator is operating in asynchronous state, which produces oscillating torques, currents in the armature (stator), the field (rotor) and the damper windings cages that can lead to dangerous damages.\
In this case, the user must open the switch K<sub>1</sub> and restart the connection procedure.
{% endhint %}

## 6.4 Study of the Regulation of the Active Power Flow Between the Synchronous Machine and the Grid, With Constant Field Current J<sub>f</sub> - Operating Limits <a href="#id-6.4-study-of-the-regulation-of-the-active-power-flow-between-the-synchronous-machine-and-the-grid-wi" id="id-6.4-study-of-the-regulation-of-the-active-power-flow-between-the-synchronous-machine-and-the-grid-wi"></a>

### 6.4.1 Sign Convention for Measuring Devices <a href="#id-6.4.1-sign-convention-for-measuring-devices" id="id-6.4.1-sign-convention-for-measuring-devices"></a>

* The active sign convention is adopted for the armature (stator) current of the synchronous machine.\
  Therefore, the algebraic value of the active power P is positive if the power is supplied to the grid and negative if it is absorbed by the synchronous machine.\
  Consequently, if P is positive then the synchronous machine is operating in generator mode, if not, it is in motor mode.
* The passive sign convention is adopted for the armature (rotor) current of the brushed-DC machine.\
  Therefore, the product V<sub>a</sub>\*I<sub>a</sub> is positive when the machine is operating in motor mode and negative when it is in generator mode.
* The torque T<sub>u</sub> at the DC-machine shaft is positive if the DC-machine is operating in motor mode and the direction of the rotation N is positive.
* The internal angle θ between (i) the electromotive force E phasors and (ii) the armature line-neutral voltage V<sub>s</sub> of the synchronous machine is positive in generator mode and negative in motor mode.

For more details refer to [Table 5](https://www.opal-rt.com/docs/courseware/electric-courseware/electric-machines-courseware/mastering-synchronous-machines-using-real-time-simulation-laboratories/panels-overview.md#table-5-display-modules-for-measurement-devices-and-sign-convention-for-parameters-displayed).

### 6.4.2 Exercise <a href="#id-6.4.2-exercise" id="id-6.4.2-exercise"></a>

1. After synchronizing the synchronous generator to the grid do not modify its field current J<sub>f</sub>.\
   Observe the values and the signs of (i) active power P exchanged with the grid, (ii) torque T<sub>u</sub> at the shaft, (iii) internal angle θ and the (iv) armature RMS current value I<sub>s</sub>.
2. Using SC2, gradually decrease the DC machine field current I<sub>f</sub>.\
   By observing the values and signs of the four entities above, check that when I<sub>f</sub> decreases, P and T<sub>u</sub> increase.\
   Therefore, the DC machine operates in motor mode and provides mechanical power to the shaft of the synchronous machine, which is operating in generator mode.\
   The latter converts the mechanical power to electric power and supplies it to the grid, under the assumption that conversion losses are small enough, therefore neglected.
3. Continue gradually decreasing the DC machine field current I<sub>f</sub> : P, I<sub>s</sub> and θ increase.\
   We are now close to the operating limits for this type of regulator.\
   Two scenarios may occur: (i) the current I<sub>s</sub> exceeds its value I<sub>sn</sub> and the protection system triggers or (ii) the internal angle θ reaches its limit of static stability, starts oscillating, leading to the loss of synchronization.\
   Save the value of θ corresponding to the limit of static stability.\
   If the generator disconnects or the protection system triggers, open switch K<sub>1</sub> and repeat the complete synchronization procedure described in Section 6.3.2.
4. Return to the initial state after synchronization by decreasing I<sub>f</sub> until it reaches the value obtained in step 1.
5. Using SC2, gradually increase I<sub>f</sub>.\
   Observe the values and the signs of the four entities enumerated in step 1.\
   Check that when I<sub>f</sub> increases, P and T<sub>u</sub> decrease.\
   Consequently, the mechanical power provided by the DC machine decreases progressively.\
   Notice that there is a value of I<sub>f</sub> for which the torque T<sub>u</sub> vanishes.\
   Save the values at this specific operating point, called the "floating point", where the power flow between the two machines vanishes.\
   Also, notice that for this point, power P and the product V<sub>a</sub>\*I<sub>a</sub> are not zero.
6. Continue to gradually increase I<sub>f</sub> starting from the floating point.\
   The sign reverses for (i) the torque T<sub>u</sub> at the shaft, (ii) the armature current I<sub>a</sub>, (iii) the active power P and (iv) the internal angle θ.\
   The DC machine is then operating in generator mode and the synchronous machine is in motor mode.\
   The latter absorbs electric active power from the grid and converts it to mechanical power at the DC machine shaft.
7. Continue increasing I<sub>f</sub> **with caution**: the absolute values of P, θ and I<sub>s</sub> increase.\
   We are now close to the operating limits for this type of regulator.\
   Two scenarios may occur: (i) the current I<sub>s</sub> exceeds its value I<sub>sn</sub> and the protection system triggers or (ii) the internal angle θ reaches its limit of static stability, starts oscillating, leading to the loss of synchronization.\
   Save the value of θ corresponding to the limit of static stability.\
   If the generator disconnects or the protection system triggers, open switch K<sub>1</sub> and repeat the complete synchronization procedure described in Section 6.3.2
8. Return to the initial state after synchronization by decreasing I<sub>f</sub> until it reaches the value obtained in step 1.

## 6.5 Study of the Regulation of the Reactive Power Flow Between the Synchronous Machine and the Grid, With Zero Active Power - Operating Limits <a href="#id-6.5-study-of-the-regulation-of-the-reactive-power-flow-between-the-synchronous-machine-and-the-grid" id="id-6.5-study-of-the-regulation-of-the-reactive-power-flow-between-the-synchronous-machine-and-the-grid"></a>

1. If the virtual test bench is in its initial state after synchronization, as in the last step 8 of the previous exercise, go to step 2.\
   If the machines are stopped, return to the initial setup of Section 6.2 and repeat the complete synchronization procedure described in Section 6.3.2
2. Adjust I<sub>f</sub> to retrieve the floating point, as described in step 5, where the active power flow vanishes between the two machines.
3. Using SC3, increase field current J<sub>f</sub> of the synchronous machine, while maintaining the torque T<sub>u</sub> at zero using the DC motor's current field I<sub>f</sub>.\
   The RMS armature current I<sub>s</sub> increases.\
   Keep increasing J<sub>f</sub> until I<sub>s</sub> is close to its nominal value I<sub>sn</sub>. For this operating point: (i) save the values of active power P, reactive power Q, and I<sub>s</sub> and (ii) compute the power factor of the synchronous machine.\
   Does the machine produce or absorb reactive power?
4. Starting from the operating point of step 3 (I<sub>s</sub> as close as possible to I<sub>sn</sub>), decrease J<sub>f</sub> using SC3, while maintaining T<sub>u</sub> at zero using I<sub>f</sub>.\
   Notice that I<sub>s</sub> and Q decrease.\
   Keep decreasing J<sub>f</sub>, while maintaining T<sub>u</sub> at zero, until Q vanishes.\
   At this operating point, there is no reactive power between the grid and the synchronous generator.\
   What is the power factor of the synchronous machine?
5. Keep decreasing J<sub>f</sub> using SC3 while maintaining T<sub>u</sub> at zero using I<sub>f</sub>.\
   Notice that (i) I<sub>s</sub>, which went through a minimum when Q = 0, increases again and (ii) that the sign of Q is reversed.\
   Does the machine produce or absorb reactive power for this new operating point?
6. Keep decreasing J<sub>f</sub> using SC3 while maintaining T<sub>u</sub> at zero using I<sub>f</sub> until I<sub>s</sub> is close to its nominal value I<sub>sn</sub>.\
   If there is a loss of synchronization during this maneuver, i.e., while I<sub>s</sub> is getting close to I<sub>sn</sub>, return to the initial setup of Section 6.2 and repeat the complete synchronization procedure described in Section 6.3.2.\
   Then repeat step 6 until I<sub>s</sub> is as close as possible to I<sub>sn</sub> without loss of synchronization.\
   At this operating point: (i) save the values of P, Q, and I<sub>s</sub> and (ii) compute the power factor of the synchronous machine.\
   Does the machine produce or absorb reactive power?

## 6.6 Procedure to Stop the Drive <a href="#id-6.6-procedure-to-stop-the-drive" id="id-6.6-procedure-to-stop-the-drive"></a>

1. Bring the torque T<sub>u</sub> as close as possible to zero using I<sub>f</sub>.
2. Open switch K<sub>1</sub> to disconnect the synchronous machine from the grid.
3. Bring voltage source SA1 back to 0 V.
4. Bring voltage sources SC1, SC2 and SC3 back to 0 V.

## 6.7 Lab Report <a href="#id-6.7-lab-report" id="id-6.7-lab-report"></a>

1. Plot the phasor diagram for synchronous machine voltages E and V<sub>s</sub> at the instant where the synchronization occurs.
2. Due to synchronization, the 60 Hz constant frequency of the grid forces the rotation speed to 1800 rpm.\
   Using the steady-state model of the DC motor with independent excitation, show that for constant V<sub>a</sub> = 460 V, I<sub>f</sub> controls T<sub>u</sub> and, therefore, the power flow between the synchronous machine and the grid.
3. Provide the two values of the internal angle θ, corresponding to the limit of static stability, recorded in steps 3 and 7 of Section 6.4.2, and corresponding to the synchronous machine operating in generator and motor mode, respectively.\
   Compare them to the theoretical values of static stability of the synchronous machine connected to the grid.
4. What is the power factor of the synchronous machine obtained in steps 3 and 6 of Section 6.5?\
   In which case does the machine supply reactive power to the grid?\
   In which case does the machine absorb reactive power from the grid?\
   Justify your answer.
5. In a hydraulic power plant connected to the grid and not equipped with a turbine speed governor, which control device is used instead of the DC motor field current I<sub>f</sub> of this virtual test bench to control the torque at the shaft, and consequently, the active power exchanged between the synchronous machine and the grid?
6. When a private hydraulic plant connects to the grid to sell electrical energy, it is contractually obligated to maintain a minimum value of the power factor of its plant, seen from the infinite bus.\
   If it cannot maintain a power factor greater than or equal to this minimum value, the sale price of its energy is penalized and reduced.\
   Explain why?\
   Which control device should they use to respect their contract?\
   Should this device be adapted for the active power it supplies?
7. Is it possible to vary the active power produced by a synchronous generator connected to an infinite bus by controlling its field current J<sub>f</sub>?\
   Discuss.
8. When the mechanical power on a synchronous generator shaft connected to a grid varies and its field current J<sub>f</sub> remains constant, does the reactive power exchanged with the grid vary?\
   Discuss.


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/courseware/electric-courseware/electric-machines-courseware/mastering-synchronous-machines-using-real-time-simulation-laboratories/synchronous-generator-connected-to-the-grid.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.