> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/courseware/electric-courseware/electric-machines-courseware/understanding-transient-stability-using-real-time-simulation-laboratories/power-system-overview.md).

# Power System Overview

## Single-line diagram of the Power System <a href="#id-2.1-single-line-diagram-of-the-power-system" id="id-2.1-single-line-diagram-of-the-power-system"></a>

<figure><img src="https://4054096626-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FYbyVjpgEQX9nfCkpYoFP%2Fuploads%2FVF2HxLZjNfx28u2Pci9l%2Fbb04302f-1946-4b31-91df-eb2604316b02.png?alt=media&amp;token=1c1c33f1-68bc-4445-8068-8438f8459f7e" alt=""><figcaption><p>Figure 1: Single-line diagram of the power system under study</p></figcaption></figure>

The main elements of this grid are:

* An **infinite bus** (or busbar)
* A 60 Hz **synchronous generator**
* A **transforme**r
* **Three lines** $$L\_{12}$$ , $$L\_{13}$$ and $$L\_{23}$$

### Power System parameters <a href="#id-2.2-power-system-parameters" id="id-2.2-power-system-parameters"></a>

* All impedances are in per unit (pu) using a common base of 100 MVA.
* The infinite busbar receives active power of 1.0 pu with a lagging power factor of 0.95.

Circuit parameters are shown in the following table. The per-unit bases of the system are $$S\_{base}$$ = 100 MVA et $$U\_{base}$$ = 13800 V.

<table><thead><tr><th width="120">Parameter</th><th width="120.4000244140625">Value (pu)</th><th>Description</th></tr></thead><tbody><tr><td><strong>X</strong><sub><strong>d</strong></sub></td><td>0.3</td><td>Generator d-axis transient reactance</td></tr><tr><td><strong>X</strong><sub><strong>TR</strong></sub></td><td>0.1</td><td>Transformer reactance</td></tr><tr><td><strong>X</strong><sub><strong>12</strong></sub></td><td>0.2</td><td><p>Line</p><p>reactance</p></td></tr><tr><td><strong>X</strong><sub><strong>13</strong></sub></td><td>0.1</td><td><p>Line</p><p>reactance</p></td></tr><tr><td><strong>X</strong><sub><strong>23</strong></sub></td><td>0.2</td><td><p>Line</p><p>reactance</p></td></tr></tbody></table>

## Preliminary Calculations <a href="#id-2.3-preliminary-calculations" id="id-2.3-preliminary-calculations"></a>

The equation that describes the dynamics of the electromechanical system, in pu, is given as:

$$
\\\[8pt]\frac{2H}{\omega\_{0}},\omega\_{pu}(t),\frac{d\omega(t)}{dt} = P\_{pu}^{m} - P\_{pu}^{e} - D,\frac{\omega(t)-\omega\_{0}}{\omega\_{0}} = P\_{pu}^{a} \\\[6pt]
\frac{d\delta(t)}{dt} = \omega(t) - \omega\_{0}\\\[8pt]
$$

It is a differential, non-linear equation because of $$P\_{pu}^{a}$$ which is a non-linear function of δ and $$(\omega\_{pu})$$. The equation includes the possibility of modeling the generator damping. The damping is proportional to the speed of the machine in relation to synchronous speed and constant D. It is assumed that the machine’s mechanical power and internal voltage remain constant during transients.

Before proceeding to real-time simulations, it is useful to perform preliminary calculations on transient stability by determining the following values:

1. The current, in pu, at the infinite bus (bus 2) in steady state.
2. The amplitude and angle of the voltage at generator terminals in steady state.
3. The amplitude and angle of the internal voltage of the generator in steady state.
4. The amplitude and angle of voltage at all buses in steady state.
5. Active and reactive power at buses 2 and 4 in steady state.
6. Mechanical power supplied to the generator turbine at $$t = 0^{-}$$ and at $$t = 0^{+}$$ (fault occurs at t = 0).
7. The expression of active power flow (sending from generator to the infinite bus) as a function of the generator internal angle.
8. The expression of active power flow (sending from generator to the infinite bus) as a function of the generator internal angle during a fault. Calculate the two cases below:
   * A solid three-phase short-circuit on bus 1
   * A solid three-phase short-circuit on bus 3
9. Apply the Equal Area criterion to determine the transient stability for the following two cases (the fault is clearing after six cycles)
   * A solid three-phase short-circuit on bus 1. Once the fault is cleared, the grid resumes its original topology.
   * A solid three-phase short-circuit on bus 3. Once the fault is cleared, circuit breakers D1 and D2 open.


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/courseware/electric-courseware/electric-machines-courseware/understanding-transient-stability-using-real-time-simulation-laboratories/power-system-overview.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.