> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/courseware/electric-courseware/power-electronics-ii/synchronous-generator-static-excitation-systems.md).

# Synchronous Generator Static Excitation Systems

This power electronics laboratory is designed to help students understand how controlled rectifiers are applied to static excitation systems for synchronous generators. Students will gain experience in modeling, simulating, and analyzing both the steady-state and transient behavior of controlled rectifiers.

In addition, students will be introduced to HYPERSIM and Dashboards for real-time simulation, offering a thorough grasp of the simulation environment and its practical applications.

## Introduction

Diode and thyristor-based AC-DC converters are used in a number of applications. Diode AC-DC converters are also known as uncontrolled rectifiers because they present unidirectional power flow characteristics, only being able to operate as rectifiers, and do not allow the variation of the DC bus voltage for a constant AC side voltage. In electric utility applications that require either bidirectional power flow control, such as in HVDC transmission systems, or control of the output voltage, such as in static exciters for synchronous generators, thyristor AC-DC converters are used.

A three-phase full-wave diode and thyristor rectifier are illustrated in Fig. 1(a) and (b) respectively. The power supply is represented by a pure three-phase voltage supply (resistance and inductance of supply are neglected), the diodes/thyristors are considered ideals, and the load is represented by a pure DC current source (highly inductive load).

<figure><img src="https://4054096626-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FYbyVjpgEQX9nfCkpYoFP%2Fuploads%2FfDQGPlJOZxIe5ziCOAki%2Fimage.png?alt=media&amp;token=32577d77-6e68-4d1a-81af-e0edb322a7ef" alt=""><figcaption><p>Figure 1: (a) Three-phase full-wave rectifier: Diode (b) Three-phase full-wave rectifier: Thyristor.</p></figcaption></figure>

Figure 2 (a) shows the two operational quadrants of a thyristor rectifier in the voltage (*e*<sub>*d*</sub>) current (*i*<sub>*d*</sub>) plane. The variation of the DC side voltage (*e*<sub>*d*</sub>) as a function of alpha (α) and the thyristor rectifier operational modes (rectification, inversion) are shown in Fig. 2 (b). Positive values of *e*<sub>*d*</sub> and *i*<sub>*d*</sub>  imply rectification, whereas a negative value of *e*<sub>*d*</sub> and positive *i*<sub>*d*</sub> implies inversion. The inverter mode of operation on a sustained basis is only possible if a source of power such as a battery is present on the DC side.

<figure><img src="https://4054096626-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FYbyVjpgEQX9nfCkpYoFP%2Fuploads%2Fm7qTurjDzznAOd558FMF%2Fimage.png?alt=media&amp;token=87de3f62-9ea1-43c6-b919-e270df2c3aa0" alt=""><figcaption><p>Figure 2: (a) Output I-V diagram thyristor rectifier (b) Output average DC voltage<br>as a function of delay angle α.</p></figcaption></figure>

## Performance indices for three-phase full-wave six-pulse rectifiers.

The objective of any performance index is to evaluate quantitatively and qualitatively the operation of an equipment and allow comparisons to be made between various configurations. In this example the equipment is based upon an electric supply - static converter - load interaction and, therefore, the performance indices are derived from measured electric variables as voltages and currents. The most used indices are presented in the following table.

<table data-search="false"><thead><tr><th>Performance Index</th><th align="center">Diode Rectifier</th><th align="center">Thyristor Rectifier</th></tr></thead><tbody><tr><td>Supply phase voltage</td><td align="center"><span class="math">V_S</span></td><td align="center"><span class="math">V_S</span></td></tr><tr><td>Supply line current</td><td align="center"><span class="math">\sqrt{\frac{2}{3}}i_d</span></td><td align="center"><span class="math">\sqrt{\frac{2}{3}}i_d</span></td></tr><tr><td>Supply fundamental line current</td><td align="center"><span class="math">\frac{\sqrt 6}{\pi}   i_d</span></td><td align="center"><span class="math">\frac{\sqrt 6}{\pi}   i_d</span></td></tr><tr><td>Active power</td><td align="center"><span class="math">\frac{3}{\pi}\sqrt{6}V_{S} i_{d}</span></td><td align="center"><span class="math">\frac{3}{\pi}\sqrt{6}V_{S} i_{d}\cos(\alpha)</span></td></tr><tr><td>Apparent power</td><td align="center"><span class="math">\sqrt{6} V_S i_d</span></td><td align="center"><span class="math">\sqrt{6} V_S i_d</span></td></tr><tr><td>Power factor</td><td align="center"><span class="math">\frac{3}{\pi}=0.955</span></td><td align="center"><span class="math">\frac{3}{\pi} cos(\alpha)</span><span class="math">\frac{3}{\pi}cos(\alpha}</span></td></tr><tr><td>DC current</td><td align="center"><span class="math">i_d</span></td><td align="center"><span class="math">i_d</span></td></tr><tr><td>DC voltage</td><td align="center"><span class="math">1.35 V_L</span></td><td align="center"><span class="math">1.35 V_L cos(\alpha)</span></td></tr><tr><td>Semiconductor average current</td><td align="center"><span class="math">\frac{i_d}{3}</span></td><td align="center"><span class="math">\frac{i_d}{3}</span></td></tr><tr><td>Semiconductor RMS current</td><td align="center"><span class="math">\frac{i_d}{\sqrt 3}</span></td><td align="center"><span class="math">\frac{i_d}{\sqrt 3}</span></td></tr></tbody></table>

<figure><img src="https://4054096626-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FYbyVjpgEQX9nfCkpYoFP%2Fuploads%2FMeVVgh2ZxbPWk0qF6klF%2Fimage.png?alt=media&amp;token=f900b975-797a-44d4-8b81-a800980edd7b" alt=""><figcaption><p>Figure 3: Three-phase full-bridge ideal diode rectifier waveforms. (a) Supply phase voltage and supply line current, (b) DC rectifier voltage and current, (c) Diode voltage and current, (d) Supply line current spectrum, (e) DC rectifier voltage spectrum.</p></figcaption></figure>

<figure><img src="https://4054096626-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FYbyVjpgEQX9nfCkpYoFP%2Fuploads%2FZjUEtNxnVcRu5HfUMfRv%2Fimage.png?alt=media&amp;token=1f2f41f7-becb-4e2c-b08a-36194c873f35" alt=""><figcaption><p>Figure 4: Three-phase full-bridge ideal thyristor rectifier waveforms. (a) Supply phase voltage and supply line current, (b) DC rectifier voltage and current, (c) Thyristor voltage and current, (d) Supply line current spectrum, (e) DC rectifier voltage spectrum.</p></figcaption></figure>

## Application examples

One important application of thyristor rectifiers is in **static excitation systems for synchronous generators**. These systems provide the DC power required by the generator field winding and perform essential control and protection functions necessary for the reliable operation of the electric power system.

A static excitation system typically consists of the following components:

* An **exciter**, which supplies DC power to the generator field winding.
* A **regulator**, which processes control signals and adjusts the exciter output accordingly.
* A **terminal voltage transducer and load compensator**, which monitors the generator terminal voltage and converts it into a filtered DC signal for use by the control system.
* A **power system stabilizer (PSS)**, which provides supplementary control signals to the regulator to damp power system oscillations and improve system stability.
* **Limiters and protective circuits**, which ensure that the operating limits of both the exciter and generator are not exceeded.

In a static excitation system, all major components are stationary. DC power is supplied directly to the main generator field winding through slip rings, while the AC power required by the rectifier system is obtained either from the main generator terminals or from a station auxiliary bus. Thyristor rectifiers are used for the controlled AC-to-DC power conversion stage of the excitation system, as illustrated in Figure 5. Additional details regarding static excitation systems can be found in References \[2] through \[4].

<figure><img src="https://4054096626-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FYbyVjpgEQX9nfCkpYoFP%2Fuploads%2FsgezYtKBsTgdLOv636xP%2Fimage.png?alt=media&amp;token=431e4109-f7bc-4221-97b6-844601ba94b0" alt=""><figcaption><p>Figure 5: Elements of an excitement system.</p></figcaption></figure>

## Authors <a href="#authors" id="authors"></a>

* Innocent Kamwa, Professor, Laval University
* Wolf Peter Jean Philippe, Courseware Analyst, OPAL-RT Technologies


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/courseware/electric-courseware/power-electronics-ii/synchronous-generator-static-excitation-systems.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.