> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/courseware/electric-courseware/renewable-energy/photovoltaic-generation-system-pvgs/virtual-test-bench-overview.md).

# Virtual Test Bench Overview

In this section, the PVGS and its functional operation are discussed.\
Figure 1 shows the one-line diagram of a photovoltaic generation system, which is then connected to a distribution system (see figure 2).\
The distribution system, as shown in figure 2, consists of a 100 MVA three-winding transformer that connects a high voltage (154 kV - wye floating) transmission system to a medium (2&#x32;*.*&#x39; kV - wye grounded) distribution feeder.\
The tertiary winding is &#x35;*.*&#x37; kV delta. There is a 5 MVAr capacitor bank connected to the MV (medium voltage) winding of the transformer.\
A load of &#x30;*.*&#x35;244 MW and &#x30;*.*&#x31;669 MWAr is connected at the middle of the feeder.\
The far end of the feeder has the PVGS connected to the point of common coupling (PCC).

<figure><img src="https://4054096626-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FYbyVjpgEQX9nfCkpYoFP%2Fuploads%2FrJmgmOyv77z5X5qFk4ov%2F526a085d-5758-4812-b67c-a5b07f855853.png?alt=media&amp;token=b2643484-8e32-4cdb-8981-5b551e1de27a" alt=""><figcaption><p><strong>Figure 1</strong>: Photovoltaic Generation System</p></figcaption></figure>

<figure><img src="https://4054096626-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FYbyVjpgEQX9nfCkpYoFP%2Fuploads%2FIuFNrPDOaUBHtS1VVNha%2Ff5d30ec5-30c5-4aef-a6ab-5682e57a01a3.png?alt=media&amp;token=b74b0860-606d-45ff-9e5b-8d42e6c495d2" alt=""><figcaption><p><strong>Figure 2</strong>: Distribution System Connected with a Photovoltaic Generation System</p></figcaption></figure>

In the simplest case, a PV cell can be described by a diode (see figure 3).\
The current-voltage characteristic can be determined using

$$
I = I\_{Ph} - I\_S \left(\exp!\left(\frac{U}{m,U\_T}\right) - 1\right) \\\[8pt]
I = I\_{Ph} - I\_D \\\[8pt]
$$

and it is shown in figure 4.\
The photocurrent *I*<sub>Ph</sub> = *c*<sub>0</sub> *· E* depends on the irradiance *E* (see figure 4) and the coefficient *c*<sub>0</sub>. *I*<sub>S</sub> *≈* 10<sup>*−*</sup><sup>10</sup> is the saturation current.\
And the diode factor is *m* = 1 in the case of an ideal diode.\
At a temperature of *ϑ* = 25 *°*&#x43;, *U*<sub>T</sub> is equal to 2&#x35;*.*&#x37; mV.

<figure><img src="https://4054096626-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FYbyVjpgEQX9nfCkpYoFP%2Fuploads%2FW9tPfwhLGinvH7HHMscp%2F5313aec3-65f2-4e82-b4e9-906f94405ca6.png?alt=media&amp;token=503f1943-afd0-444e-bbc7-56e6ee5c389c" alt="" width="275"><figcaption><p><strong>Figure 3</strong>: Photovoltaic Cell (cf. <a href="https://www.opal-rt.com/docs/courseware/electric-courseware/renewable-energy/photovoltaic-generation-system-pvgs/references.md"><strong>[3]</strong></a>)</p></figcaption></figure>

<figure><img src="https://4054096626-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FYbyVjpgEQX9nfCkpYoFP%2Fuploads%2FsvEgCMkWkQgZoe5KZv1d%2Fe1e72b59-c8ce-4ba0-84e6-282084d844db.png?alt=media&amp;token=50e72408-7c4e-4ac9-a35c-52e89a41313b" alt=""><figcaption><p><strong>Figure 4</strong>: Irradiance Dependency of I-U-characteristics of a PV Cell <a href="https://www.opal-rt.com/docs/courseware/electric-courseware/renewable-energy/photovoltaic-generation-system-pvgs/references.md"><strong>[3]</strong></a></p></figcaption></figure>

<figure><img src="https://4054096626-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FYbyVjpgEQX9nfCkpYoFP%2Fuploads%2Fper0nQmg6b2r4bWLWFzn%2Fa15bb7c7-c0a1-4162-b785-b986cfdbba7c.png?alt=media&amp;token=753e1c63-a7b1-443f-9951-b24292b85c09" alt=""><figcaption><p><strong>Figure 5</strong>: I-U-characteristic (in blue) and P-U-characteristic (in red) of a PV Cell <a href="https://www.opal-rt.com/docs/courseware/electric-courseware/renewable-energy/photovoltaic-generation-system-pvgs/references.md"><strong>[3]</strong></a></p></figcaption></figure>

The maximum of the *P*-*V*-characteristic in figure 5 is called Maximum Power Point (MPP).\
The MPP tracker determines the current MPP and enables tracking it.\
In contrast, in the curtailment mode the maximum active power is not aimed, but a reference value *P*<sub>ref</sub> should be reached.


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/courseware/electric-courseware/renewable-energy/photovoltaic-generation-system-pvgs/virtual-test-bench-overview.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.