> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/configure-ios/communication-protocol-ios/iec-61850-9-2-sv/review-the-driver-connectable-points.md).

# Review the Driver Connectable Points

The driver’s connectable points enable the driver to exchange data with the model. **Once** the driver is configured, these connectable points are exposed.

Exposed connectable points appear in the **I/O Selector** window when clicking the **Edit I/O Connection** icon for a sensor in the HYPERSIM model:

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-7e5f41c6abe0836d7c5b463f2a8079ecf996b572%2FDR-hyp-sv-connectable.png?alt=media" alt=""><figcaption></figcaption></figure>

In the **I/O Selector** window, **connectable points** are color‑coded based on their data direction:

* **Blue** connectable points indicate data **sent** **from the model** to the driver during execution
* **Red** connectable points indicate data **received** from the driver **into the model** during execution

## Time synchronization connectable points

The IEC61850 driver can automatically detect and use an available synchronization source provided by an **Oregano Syn1588 PCIe card**. See the **Time Synchronization Driver** section for detailed information.

Alternatively, clock connectable points can be **explicitly exposed and connected through the model**. When this approach is used, clock synchronization is handled **manually by the model** rather than automatically by the driver.

This mode is intended for advanced configurations where external clock behavior must be controlled or overridden at the model level.

<table><thead><tr><th width="140">Connectable name</th><th width="285">Description</th><th width="115">Direction</th><th width="210">Exposure condition</th></tr></thead><tbody><tr><td><strong>Sync</strong></td><td>Binary synchronization indicator. Use <code>1</code> when the timestamp is synchronized to an accurate external source; otherwise use <code>0</code>. Mapped into the SV <strong>smpSynch</strong> attribute.</td><td>From model</td><td>Exposed when <strong>Time synchronization</strong> is set to <strong>Use connection in model</strong> in the <strong>IEC61850 interface</strong> configuration.</td></tr><tr><td><strong>Epoch</strong></td><td>Represents the second reference for the stream. The value must increment once per second and is used to control the <strong>smpCnt</strong> attribute in Sampled Values messages.</td><td>From model</td><td>Exposed when <strong>Time synchronization</strong> is set to <strong>Use connection in model</strong> in the <strong>IEC61850 interface</strong> configuration.</td></tr><tr><td><strong>Microseconds</strong></td><td>Microsecond count within the current second. This connection is not required for SV.</td><td>From model</td><td>Exposed when <strong>Time synchronization</strong> is set to <strong>Use connection in model</strong> in the <strong>IEC61850 interface</strong> configuration.</td></tr></tbody></table>

## Sampled values (SV) connectable points

### SV publishers (IEC 61850‑9‑2LE)

<table><thead><tr><th width="150">Connectable name</th><th>Description</th><th width="115">Direction</th><th width="165">Exposure condition</th></tr></thead><tbody><tr><td><strong>Settings / Pause</strong></td><td>Controls SV transmission. <code>1</code> suspends transmission; <code>0</code> enables it.</td><td>From model</td><td>Always exposed.</td></tr><tr><td><strong>Current Value</strong></td><td>Vector of 4 currents <strong>[Ia, Ib, Ic, In]</strong> (3‑phase + neutral).</td><td>From model</td><td>Always exposed.</td></tr><tr><td><strong>Current Quality</strong></td><td>Vector of 4 quality words <strong>[QIa, QIb, QIc, QIn]</strong> (each element is a 16‑bit quality value).</td><td>From model</td><td>Always exposed.</td></tr><tr><td><strong>Voltage Value</strong></td><td>Vector of 4 voltages <strong>[Va, Vb, Vc, Vn]</strong> (3‑phase + neutral).</td><td>From model</td><td>Always exposed.</td></tr><tr><td><strong>Voltage Quality</strong></td><td>Vector of 4 quality words <strong>[QVa, QVb, QVc, QVn]</strong> (each element is a 16‑bit quality value).</td><td>From model</td><td>Always exposed.</td></tr></tbody></table>

### SV publishers (IEC 61869‑9)

Each attribute included in the configured SV data set exposes a connectable point (typically voltage/current values and their quality values). Naming follows the full IED path format:

**IED / Access point / Logical device / Logical node / Data object / Data attribute**

<table><thead><tr><th width="175">Direction</th><th width="155">Exposure condition</th><th></th><th></th></tr></thead><tbody><tr><td><strong>Settings / Pause</strong></td><td>Controls SV transmission. <code>1</code> suspends transmission; <code>0</code> enables it.</td><td>From model</td><td>Always exposed.</td></tr><tr><td><strong>Data set attribute (full IED path)</strong></td><td>Value of the corresponding attribute published in the SV message (measurements and quality).</td><td>From model</td><td>Always exposed.</td></tr></tbody></table>

### SV subscribers (IEC 61850‑9‑2LE)

<table><thead><tr><th width="145">Connectable name</th><th>Description</th><th width="120">Direction</th><th width="160">Exposure condition</th></tr></thead><tbody><tr><td><strong>Settings / Pause</strong></td><td>Controls SV reception. <strong><code>1</code></strong> suspends reception; <code>0</code> enables it.</td><td>From model</td><td>Always exposed.</td></tr><tr><td><strong>Settings / Timestamp</strong></td><td>Capture time for each SV message: an increasing microsecond counter provided by the Ethernet adapter.</td><td>To model</td><td>Always exposed.</td></tr><tr><td><strong>Settings / smpCnt</strong></td><td>Number of SV messages since the last second boundary. Example (80 samples/cycle at 60 Hz): increases from 0 to 4799 then wraps every second.</td><td>To model</td><td>Always exposed.</td></tr><tr><td><strong>Settings / Header simulated bit</strong></td><td>Simulation bit from the Reserved 1 header field. <code>1</code> indicates the data is considered to be sent by a simulated device.</td><td>To model</td><td>Always exposed.</td></tr><tr><td><strong>Current Value</strong></td><td>Vector of 4 currents <strong>[Ia, Ib, Ic, In]</strong>.</td><td>To model</td><td>Always exposed.</td></tr><tr><td><strong>Current Quality</strong></td><td>Vector of 4 quality words <strong>[QIa, QIb, QIc, QIn]</strong> (16‑bit each).</td><td>To model</td><td>Always exposed.</td></tr><tr><td><strong>Voltage Value</strong></td><td>Vector of 4 voltages <strong>[Va, Vb, Vc, Vn]</strong>.</td><td>To model</td><td>Always exposed.</td></tr><tr><td><strong>Voltage Quality</strong></td><td>Vector of 4 quality words <strong>[QVa, QVb, QVc, QVn]</strong> (16‑bit each).</td><td>To model</td><td>Always exposed.</td></tr></tbody></table>

### SV subscribers (IEC 61869‑9)

Each attribute included in the configured SV data set exposes a connectable point. Naming follows the full IED path format:

**IED / Access point / Logical device / Logical node / Data object / Data attribute**

<table><thead><tr><th width="170">Connectable name</th><th>Description</th><th width="120">Direction</th><th width="160">Exposure condition</th></tr></thead><tbody><tr><td><strong>Settings / Pause</strong></td><td>Controls SV reception. <code>1</code> suspends reception; <code>0</code> enables it.</td><td>From model</td><td>Always exposed.</td></tr><tr><td><strong>Settings / Timestamp</strong></td><td>Capture time for each SV message: an increasing microsecond counter provided by the Ethernet adapter.</td><td>To model.</td><td>Always exposed.</td></tr><tr><td><strong>Settings / smpCnt</strong></td><td>Number of SV messages since the last second boundary (wraps each second based on configured sampling rate).</td><td>To model</td><td>Always exposed.</td></tr><tr><td><strong>Settings / Header simulated bit</strong></td><td>Simulation bit from the Reserved 1 header field. <strong>1</strong> indicates the data is considered to be sent by a simulated device.</td><td>To model</td><td>Always exposed.</td></tr><tr><td><strong>Data set attribute (full IED path)</strong></td><td>Value of the corresponding received attribute (measurements and quality).</td><td>To model</td><td>Always exposed.</td></tr></tbody></table>

{% hint style="info" %}
This applies to both **9‑2LE** and **IEC 61869‑9** publishers and subscribers. Quality is represented as a **16‑bit word** per measurement. Use the standard interpretation used by your SV profile and tools.
{% endhint %}

## SV fault injection (9‑2LE Publishers) connectable points

### Stop transmission

Simulates packet loss by preventing SV frames from being transmitted for a configured number of frames. Stop transmission connectable points are exposed only when **Enable Sampled Values data integrity manipulation** is **checked** in the **IEC61850 interface** configuration.

<table><thead><tr><th width="185">Connectable name</th><th>Description</th><th width="115">Direction</th><th width="175">Exposure condition</th></tr></thead><tbody><tr><td><strong>Faults / Stop Transmission / Trigger</strong></td><td>Applies the fault on a rising edge (0→1). Reset to <code>0</code> to rearm.</td><td>From model</td><td>When manipulation is enabled.</td></tr><tr><td><strong>Faults / Stop Transmission / Mode</strong></td><td><code>0</code> = apply immediately after trigger<br><code>1</code> = apply when smpCnt reaches the configured wait value</td><td>From model</td><td>When manipulation is enabled.</td></tr><tr><td><strong>Faults / Stop Transmission / Number of frames</strong></td><td>Number of frames to drop (not transmitted).</td><td>From model</td><td>When manipulation is enabled.</td></tr><tr><td><strong>Faults / Stop Transmission / Wait for smpCnt</strong></td><td>smpCnt target used when Mode = <code>1</code>.</td><td>From model</td><td>When manipulation is enabled.</td></tr></tbody></table>

### Delay transmission

Simulates an unwanted delay by buffering SV frames and releasing them after a configured delay. Delay transmission connectable points are exposed only when **Enable Sampled Values data integrity manipulation** is **checked** in the **IEC61850 interface** configuration.

<table><thead><tr><th width="185">Connectable name</th><th>Description</th><th width="120">Direction</th><th width="170">Exposure condition</th></tr></thead><tbody><tr><td><strong>Faults / Delay Transmission / Trigger</strong></td><td>Applies the fault on a rising edge (0→1). Reset to <code>0</code> to rearm.</td><td>From model</td><td>When manipulation is enabled.</td></tr><tr><td><strong>Faults / Delay Transmission / Mode</strong></td><td><code>0</code> = apply immediately after trigger<br><code>1</code> = apply when smpCnt reaches the configured wait value</td><td>From model</td><td>When manipulation is enabled.</td></tr><tr><td><strong>Faults / Delay Transmission / Delay (us)</strong></td><td>Delay applied to frames (0 to 1,000,000 µs). Internal buffer retains data until released.</td><td>From model</td><td>When manipulation is enabled.</td></tr><tr><td><strong>Faults / Delay Transmission / Wait for smpCnt</strong></td><td>smpCnt target used when Mode = <code>1</code>.</td><td>From model</td><td>When manipulation is enabled.</td></tr><tr><td><strong>Faults / Delay Transmission / Discard buffer</strong></td><td>Clears the internal buffer and resets delay to 0 (buffered values are discarded).</td><td>From model</td><td>When manipulation is enabled.</td></tr><tr><td><strong>Faults / Delay Transmission / Flush on Network</strong></td><td>Clears the delay and immediately flushes buffered frames onto the network.</td><td>From model</td><td>When manipulation is enabled.</td></tr></tbody></table>

### Duplicate transmission

Simulates duplicated frames by transmitting the same SV frame multiple times. Duplicate transmission connectable points are exposed only when **Enable Sampled Values data integrity manipulation** is **checked** in the **IEC61850 interface** configuration.

<table><thead><tr><th width="205">Connectable name</th><th>Description</th><th width="115">Direction</th><th width="175">Exposure condition</th></tr></thead><tbody><tr><td><strong>Faults / Duplicate Transmission / Trigger</strong></td><td>Applies the fault on a rising edge (0→1). Reset to <code>0</code> to rearm.</td><td>From model</td><td>When manipulation is enabled.</td></tr><tr><td><strong>Faults / Duplicate Transmission / Mode</strong></td><td><code>0</code> = apply immediately after trigger<br><code>1</code> = apply when smpCnt reaches the configured wait value</td><td>From model</td><td>When manipulation is enabled.</td></tr><tr><td><strong>Faults / Duplicate Transmission / Number of frames</strong></td><td>Number of frames on which duplication is applied.</td><td>From model</td><td>When manipulation is enabled.</td></tr><tr><td><strong>Faults / Duplicate Transmission / Number of duplications</strong></td><td>Number of times each affected frame is duplicated (e.g., <code>5</code> = send each frame 5 times).</td><td>From model</td><td>When manipulation is enabled.</td></tr><tr><td><strong>Faults / Duplicate Transmission / Wait for smpCnt</strong></td><td>smpCnt target used when Mode = 1.</td><td>From model</td><td>When manipulation is enabled.</td></tr></tbody></table>

### smpCnt manipulation

Simulates tampering by overriding the **smpCnt** field in SV messages. smpCnt manipulation connectable points are exposed only when **Enable Sampled Values data integrity manipulation** is **checked** in the **IEC61850 interface** configuration.

<table><thead><tr><th width="185">Connectable name</th><th>Description</th><th width="120">Direction</th><th width="170">Exposure condition</th></tr></thead><tbody><tr><td><strong>Faults / smpCnt Manipulation / Trigger</strong></td><td>Applies the fault on a rising edge (0→1). Reset to <code>0</code> to rearm.</td><td>From model</td><td>When manipulation is enabled.</td></tr><tr><td><strong>Faults / smpCnt Manipulation / Mode</strong></td><td><code>0</code> = apply immediately after trigger<br><code>1</code> = apply when smpCnt reaches the configured wait value</td><td>From model</td><td>When manipulation is enabled.</td></tr><tr><td><strong>Faults / smpCnt Manipulation / New smpCnt</strong></td><td>Overrides smpCnt with this value while the fault is active. Validity is user-controlled.</td><td>From model</td><td>When manipulation is enabled.</td></tr><tr><td><strong>Faults / smpCnt Manipulation / Wait for smpCnt</strong></td><td>smpCnt target used when Mode = <code>1</code>.</td><td>From model</td><td>When manipulation is enabled.</td></tr></tbody></table>

### smpSynch manipulation

Simulates tampering by overriding the **smpSynch** field for a configured number of frames. smpSynch manipulation connectable points are exposed only when **Enable Sampled Values data integrity manipulation** is **checked** in the **IEC61850 interface** configuration.

<table data-header-hidden><thead><tr><th>Connectable name</th><th>Description</th><th width="125">Direction</th><th width="175">Exposure condition</th></tr></thead><tbody><tr><td><strong>Faults / smpSynch Manipulation / Trigger</strong></td><td>Applies the fault on a rising edge (0→1). Reset to <code>0</code> to rearm.</td><td>From model</td><td>When manipulation is enabled.</td></tr><tr><td><strong>Faults / smpSynch Manipulation / Mode</strong></td><td><code>0</code> = apply immediately after trigger<br><code>1</code> = apply when smpCnt reaches the configured wait value</td><td>From model</td><td>When manipulation is enabled.</td></tr><tr><td><strong>Faults / smpSynch Manipulation / Number of frames</strong></td><td>Number of frames on which the override is applied.</td><td>From model</td><td>When manipulation is enabled.</td></tr><tr><td><strong>Faults / smpSynch Manipulation / smpSynch</strong></td><td>Overrides the smpSynch value while the fault is active.</td><td>From model</td><td>When manipulation is enabled.</td></tr><tr><td><strong>Faults / smpSynch Manipulation / Wait for smpCnt</strong></td><td>smpCnt target used when Mode = <code>1</code>.</td><td>From model</td><td>When manipulation is enabled.</td></tr></tbody></table>

### Quality manipulation

Simulates tampering by overriding voltage and/or current quality words for a configured number of frames. Quality manipulation connectable points are exposed only when **Enable Sampled Values data integrity manipulation** is **checked** in the **IEC61850 interface** configuration.

<table><thead><tr><th width="185">Connectable name</th><th>Description</th><th width="115">Direction</th><th width="175">Exposure condition</th></tr></thead><tbody><tr><td><strong>Faults / Quality Manipulation / Trigger</strong></td><td>Applies the fault on a rising edge (0→1). Reset to <code>0</code> to rearm.</td><td>From model</td><td>When manipulation is enabled.</td></tr><tr><td><strong>Faults / Quality Manipulation / Mode</strong></td><td><code>0</code> = apply immediately after trigger<br><code>1</code> = apply when smpCnt reaches the configured wait value</td><td>From model</td><td>When manipulation is enabled.</td></tr><tr><td><strong>Faults / Quality Manipulation / Number of frames</strong></td><td>Number of frames on which the quality override is applied.</td><td>From model</td><td>When manipulation is enabled.</td></tr><tr><td><strong>Faults / Quality Manipulation / Voltage Quality</strong></td><td>Overrides voltage quality values while the fault is active.</td><td>From model</td><td>When manipulation is enabled.</td></tr><tr><td><strong>Faults / Quality Manipulation / Current Quality</strong></td><td>Overrides current quality values while the fault is active.</td><td>From model</td><td>When manipulation is enabled.</td></tr><tr><td><strong>Faults / Quality Manipulation / Wait for smpCnt</strong></td><td>smpCnt target used when Mode = <code>1</code>.</td><td>From model</td><td>When manipulation is enabled.</td></tr></tbody></table>


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/configure-ios/communication-protocol-ios/iec-61850-9-2-sv/review-the-driver-connectable-points.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.