> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/examples/benchmarks/hvac-230kv-172bus-ieee-rts96.md).

# HVAC 230kV 172Bus IEEE RTS96

## Description

The **HVAC 230kV 172Bus IEEE RTS96** example, located in **File > Open an Example File > Benchmarks**, simulates the IEEE RTS-96 Reliability Test System used for bulk power system reliability evaluation studies. The main objective is to support comparative and benchmark studies of reliability evaluation techniques and illustrate system response to cleared three-phase faults.

The test system was developed by modifying and updating the original IEEE RTS-79. RTS-96 consists of three interconnected RTS-79 models; each RTS-79 model forms one area (Area 1, Area 2, Area 3) \[1]. Bus load, generation, and transmission line parameters are from \[2].

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-d8503e96c55e0f78497d69f40f65282d2d9cd86f%2FHVAC_230_172bus_IEEERTS96_example.png?alt=media" alt=""><figcaption></figcaption></figure>

## Requirements

This example model does not require any additional hardware or licenses.

## Detailed explanation

The model contains 51 loads, 73 buses, and 100 generators connected by lines or autotransformers at four voltage levels: 15 kV, 18 kV, 138 kV, and 230 kV. Three three-phase faults are configured at Buses 104, 119, and 325. Users can modify fault timing or add faults on other buses.

All the machines of the generation system are controlled by internal exciters, governors (speed regulators), and stabilizers. To change this configuration, double-click on the machine subsystem and edit the mask parameters.

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-5d572c7015792378556c079713ac55dca23f65c7%2FHVAC_230_172bus_IEEERTS96_param.png?alt=media" alt="" width="563"><figcaption><p>Synchronous machine configuration settings</p></figcaption></figure>

Three fault subsystems—Fault1 (Bus 104), Fault2 (Bus 119), and Fault3 (Bus 325)—are provided. Each fault uses parameters T1 and T2 to set activation and clearing times, respectively. By default, faults activate at 0.1 s and clear 0.05 s later.

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-7913937d9f769de9646352a5d11e7f288c8ef547%2Fimage%20(1362)%20(1).png?alt=media" alt="" width="563"><figcaption><p>To enable or disable a Fault block and adjust T1 and T2 in the block parameter.</p></figcaption></figure>

## Simulation and results

The example includes three scenario with a ready-to-use ScopeView template to display key signals.

To run a specific scenario:

* Scenario 1 (Bus 104): Enable Fault1; disable Fault2 and Fault3.
* Scenario 2 (Bus 119): Enable Fault2; disable Fault1 and Fault3. By default, Fault2 is disabled.
* Scenario 3 (Bus 325): Enable Fault3; disable Fault1 and Fault2. By default, Fault3 is enabled.

### Scenario 1: Three-phase fault on Bus 104

This scenario gives the user an idea of reliability in power systems, and how it reacts after clearing a fault.\
Apply a three-phase fault at 0.1 s on Bus 104 and clear it 0.05 s later (Fault1), Fault2 and Fault3 are disabled.

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-c4b2f762d3756f3e1141aead2a70100f3eccb35d%2FHVAC_230_172bus_IEEERTS96_simul1.png?alt=media" alt=""><figcaption><p>Voltage of Buses 103, 111 and 117 (Area-1) with a three-phase to ground fault at Bus 104.</p></figcaption></figure>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-d39a97fcb75429d517213b3028c28934db040712%2FHVAC_230_172bus_IEEERTS96_simul2.png?alt=media" alt=""><figcaption><p>Voltage of Buses 204, 217, and 219 (Area-2) with a three-phase to ground fault at Bus 104.</p></figcaption></figure>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-3ab591aebe3e0b6d492efe3dae437d743d4a2343%2FHVAC_230_172bus_IEEERTS96_simul3.png?alt=media" alt=""><figcaption><p>Voltage of Buses 304, 317, and 319 (Area-3) with a three-phase to ground fault at Bus 104.</p></figcaption></figure>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-30f7f3009393f10cb45515d7975798760058829a%2FHVAC_230_172bus_IEEERTS96_simul4.png?alt=media" alt=""><figcaption><p>Bus Voltage and Fault current with a three-phase to ground fault at Bus 104 (Area-1)</p></figcaption></figure>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-fa6f264383d99eca8ee45911aaeffbfe4a6b2f92%2FHVAC_230_172bus_IEEERTS96_simul5.png?alt=media" alt=""><figcaption><p>Machine voltages with a three-phase to-ground fault at Bus 104.</p></figcaption></figure>

### Scenario 2: Three-phase fault on Bus 119

Apply a three-phase fault at 0.1 s on Bus 119 and clear it 0.05 s later (Fault2), Fault1 and Fault3 are disabled.

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-e19b327b59a5fc96afcc2ee1e68b8c07a3e36077%2FHVAC_230_172bus_IEEERTS96_simul6.png?alt=media" alt=""><figcaption><p>Voltage of Buses 103, 111, and 117 (Area-1) with a three-phase to ground fault at Bus 119.</p></figcaption></figure>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-0a2b59d1ff5cc44409214add1b7cebbc77ca94e6%2FHVAC_230_172bus_IEEERTS96_simul7.png?alt=media" alt=""><figcaption><p>Voltage of Buses 204, 217 and 219 (Area-2) with a three-phase to ground fault at Bus 119.</p></figcaption></figure>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-80fd6e1b672b819d57e314add3a18f116941f56b%2FHVAC_230_172bus_IEEERTS96_simul8.png?alt=media" alt=""><figcaption><p>Voltage of Buses 304, 317 and 319 (Area-3) with a three-phase to ground fault at Bus 119.</p></figcaption></figure>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-84d007274a087cede6ccb971f71b390cbf54b9f3%2FHVAC_230_172bus_IEEERTS96_simul9.png?alt=media" alt=""><figcaption><p>Bus Voltage and Fault current with a three-phase to ground fault at Bus 119.</p></figcaption></figure>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-71f4bb0afd3995ef6bb42a8f538e4f41f04bf14f%2FHVAC_230_172bus_IEEERTS96_simul10.png?alt=media" alt=""><figcaption><p>Machine voltages with a three-phase to-ground fault at Bus 119.</p></figcaption></figure>

### Scenario 3: Three-phase fault on Bus 325

Apply a three-phase fault at 0.1 s on Bus 325 and clear it 0.05 s later (Fault3), Fault1 and Fault2 are disabled.

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-60b23d20930a97059a69070c87a954655ddfb205%2FHVAC_230_172bus_IEEERTS96_simul11.png?alt=media" alt=""><figcaption><p>Voltage of Buses 103, 111, and 117 (Area-1) with a three-phase to ground fault at Bus 325.</p></figcaption></figure>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-1e8686103eb6b2db0c5e4aaa0982f475303388fe%2FHVAC_230_172bus_IEEERTS96_simul12.png?alt=media" alt=""><figcaption><p>Voltage of Buses 204, 217, and 219 (Area-2) with a three-phase to ground fault at Bus 325.</p></figcaption></figure>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-8802ce9f3a4e10ff6480dfff58a9cd865c2d2335%2FHVAC_230_172bus_IEEERTS96_simul13.png?alt=media" alt=""><figcaption><p>Voltage of Buses 304, 317, and 319 (Area-3) with a three-phase to ground fault at Bus 325.</p></figcaption></figure>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-306c23c641b4d9284a72cfc1263371bd272cca0d%2FHVAC_230_172bus_IEEERTS96_simul14.png?alt=media" alt=""><figcaption><p>Bus Voltage and Fault current with a three-phase to ground fault at Bus 325 (Area-3)</p></figcaption></figure>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-2a43f6bdb0355a3599d0bb78eca32eed82625669%2FHVAC_230_172bus_IEEERTS96_simul15.png?alt=media" alt=""><figcaption><p>Machine voltages with a three-phase to-ground fault at Bus 325.</p></figcaption></figure>

## References

\[1] IEEE RTS Task Force of APM Subcommittee, "IEEE Reliability Test System', IEEE PAS, Vol-98, No. 6, Nov/Dec. 1979, pp 2047- 2054

\[2] The IEEE Reliability Test System – 1996, IEEE Transaction on Power Systems, Vol. 14, No. 3, August 1999.


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/examples/benchmarks/hvac-230kv-172bus-ieee-rts96.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.