# HVAC 230kV 6Bus

## Description

The **HVAC 230kV 6Bus** example, located in **File > Open an Example File > Benchmarks**, evaluates electromagnetic transient overvoltages caused by line switching, fault initiation, and clearing. The model includes two synchronous machines with built-in voltage and speed regulators, one voltage source, four two-winding transformers, and six constant-parameter lines operating at 13.8 kV, 110 kV, and 230 kV.

The objective is to analyze system response to three-phase faults at selected buses and assess the resulting bus voltages, fault currents, and machine dynamics.

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-093511280c49f65a7d969734ae47c489e4f342b8%2Fimage%20(1295).png?alt=media" alt=""><figcaption></figcaption></figure>

## Requirements

This example model does not require any additional hardware or licenses.

## Detailed explanation

The transmission model provides three configurable three-phase faults at different buses. Users can modify the activation and clearing times and enable or disable each fault independently.

* Fault locations and subsystems:
  * Bus 7x (Fault1)
  * Bus 6x (Fault2)
  * Bus 11 (Fault3)
* Timing parameters within each fault subsystem:
  * **T1**: fault activation time
  * **T2**: fault clearing time
* Default timing for each fault: activate at 0.1 s and clear 0.1 s later.
* Default enable state: Fault1 is enabled by default; Fault2 and Fault3 are disabled.
* To run a specific scenario, enable the corresponding fault subsystem and disable the others.
* Users can add additional three-phase faults on other buses as needed.

## Simulation and results

The example includes three scenarios. Results are viewed in ScopeView and include bus voltages, fault currents, and machine terminal voltages and speeds.

### Scenario 1: Three-phase fault on Bus 7x

* Configuration: enable Fault1; disable Fault2 and Fault3.
* Default timing: activate at 0.1 s and clear 0.1 s later.

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-1e738d9d77c46a84a06f0d49b043429d101ea2a4%2Fimage%20(1296).png?alt=media" alt=""><figcaption><p>Fault configuration settings</p></figcaption></figure>

ScopeView plots show bus voltage and fault current at Bus 7x, and machine terminal voltages and speeds during the fault and after clearing.

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-e42d22c167011d089afb35e5fec3a7b5594ff64c%2Fimage%20(1297).png?alt=media" alt=""><figcaption><p>Bus Voltage and Fault current with a three-phase to ground fault at Bus 7x</p></figcaption></figure>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-69141716235964e84a5570884a56b43157974707%2Fimage%20(1298).png?alt=media" alt=""><figcaption><p>Machine Terminal Voltages and Speeds with a three-phase to-ground fault at Bus 7x</p></figcaption></figure>

### Scenario 2: Three-phase fault on Bus 6x

* Configuration: enable Fault2; disable Fault1 and Fault3.
* Default timing: activate at 0.1 s and clear 0.1 s later.

ScopeView plots show bus voltage and fault current on Bus 7x with a three-phase to-ground fault applied at Bus 6x, and machine terminal voltages and speeds.

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-e2416ec0e3cf18bf4edeea478bdfb32cf9d9aaf3%2Fimage%20(1299).png?alt=media" alt=""><figcaption><p>Bus Voltage and Fault current on Bus7x with a three-phase to ground fault at Bus 6x</p></figcaption></figure>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-4ed3622d1dacd631fbd0dc45c70f8333fa93b22e%2Fimage%20(1300).png?alt=media" alt=""><figcaption><p>Machine Terminal Voltages and Speeds with a three-phase to-ground fault at Bus 6x</p></figcaption></figure>

### Scenario 3: Three-phase fault on Bus 11

* Configuration: enable Fault3; disable Fault1 and Fault2.
* Default timing: activate at 0.1 s and clear 0.1 s later.

ScopeView plots show bus voltage and fault current on Bus 7x with a three-phase to-ground fault applied at Bus 11, and machine terminal voltages and speeds.

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-61942301a5df06a114945d61818f3ffae50ebb7f%2Fimage%20(1301).png?alt=media" alt=""><figcaption><p>Bus Voltage and Fault current on Bus7x with a three-phase to ground fault at Bus 11</p></figcaption></figure>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-3bd96b381ce3f01058147df02eb6d9219983a572%2Fimage%20(1302).png?alt=media" alt=""><figcaption><p>Machine Terminal Voltages and Speeds with a three-phase to-ground fault at Bus 11</p></figcaption></figure>


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/examples/benchmarks/hvac-230kv-6bus.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.