> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/examples/distribution-and-industrial-power-systems/feeder-20kv-600-node.md).

# Feeder 20kV 600 Node

## Description

The **Feeder 20 kV 600 Node** example, located in **File > Open an Example File > Distribution and Industrial Power Systems**, models a simplified French 20 kV radial distribution network studied in 2012 by researchers from Grenoble Institute of Technology and Université de Lilles \[1].

The objective is to demonstrate power flow management on a radial distribution network, including operation with distributed generation and on-load tap changer control.

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-ab20281ecf9b4171b47c2cc38e27ee74cfaa5270%2Fimage%20(1448).png?alt=media" alt=""><figcaption></figcaption></figure>

## Requirements

This example model does not require any additional hardware or licenses.

## Detailed explanation

The model consists of a simplified version (reduction of the lines number and aggregation of the low-voltage distribution networks into loads) of a real French 20kV network, exploited in a radial topology studied in 2012 by researchers from Grenoble Institute of Technology and Université de Lilles \[1]. This example model was initially designed for power flow management studies using DGs using a radial distribution network.

The substation includes a YY transformer (110 kV/36 kV; 108 MVA) with a 17-tap OLTC. Five feeders are connected to the substation.

The network comprises 205 buses, 205 lines, and 122 loads. The average load is approximately 15 MW, distributed as residential (30%), industrial (40%), and service sector (30%). The total line length is about 68 km, with an average main-line length of 7.5 km.

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-c233e3d01df218ea3ba9bf80da8064ecf5987f63%2Fimage%20(1449).png?alt=media" alt=""><figcaption><p>Schematic of the distribution network</p></figcaption></figure>

Tables summarize the description of the distribution network and list the components used in the model.

| Feeder    | Main Line (km) | Average load (MW) |
| --------- | -------------- | ----------------- |
| Feeder 1  | 7.6            | 2.5               |
| Feeder 2  | 4.3            | 1.4               |
| Feeder 3  | 10.6           | 4.8               |
| Feeder 4  | 6.2            | 2.5               |
| Feeder 5  | 9.1            | 3.6               |
| **Total** | -              | 14.8              |

List of blocks in the HYPERSIM model:

| HYPERSIM Block                     | Amount             |
| ---------------------------------- | ------------------ |
| 3-Phase Bus                        | 205                |
| Nodes                              | 615 (i.e.: 205\*3) |
| Sources                            | 1                  |
| Transformers                       | 1                  |
| Breakers                           | 0                  |
| Fault Breakers                     | 1                  |
| RL-Connections                     | 222                |
| Constant Impedance Loads (R-Loads) | 124                |
| Constant Power Loads               | 124                |

## Simulation and results

The scenario applies a fault at bus B2, located at the transformer output that feeds the five feeders. The fault starts at t = 0.2 s and is cleared at t = 0.3 s (0.1 s duration).

The system returns to steady state in less than 0.1 s after fault clearance. Voltages and currents were measured at the source and at the beginning and end of each feeder; the measurements correspond to the buses indicated in the model.

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-d625832d50284df4b81df89ec4c7b79049f85c98%2Fimage%20(1450).png?alt=media" alt=""><figcaption><p>Source Voltage and Currents</p></figcaption></figure>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-fae5e21f108b97663acc75842d5b936a490b4ad2%2Fimage%20(1451).png?alt=media" alt=""><figcaption><p>Feeder 1 Voltage and Currents</p></figcaption></figure>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-951923837ac4c2ae56d5497d286873a65f4b2e67%2Fimage%20(1452).png?alt=media" alt=""><figcaption><p>Feeder 2 Voltage and Currents</p></figcaption></figure>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-960275eea092783d8ee951977bb787b873e46504%2Fimage%20(1453).png?alt=media" alt=""><figcaption><p>Feeder 3 Voltage and Currents</p></figcaption></figure>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-e79fdcd7b9cdc0707b3a3fcbfe62c0822ae5477c%2Fimage%20(1454).png?alt=media" alt=""><figcaption><p>Feeder 4 Voltage and Currents</p></figcaption></figure>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-b086d34d1ac1243de1196564be0eb1c8e5438ad1%2Fimage%20(1455).png?alt=media" alt=""><figcaption><p>Feeder 5 Voltage and Currents</p></figcaption></figure>

## References

\[ 1 ] A. Teninge, Y. Besanger, F. Colas, H. Fakham and X. Guillaud, "Real-time simulation of a medium scale distribution network: Decoupling method for multi-CPU computation," 2012 Complexity in Engineering (COMPENG). Proceedings, Aachen, Germany, 2012, pp. 1-6, doi: 10.1109/CompEng.2012.6242944. keywords: {Computational modeling;Real time systems;Load modeling;Substations;Reactive power;Delay;Load management;Power distribution network;distributed generation;real-time simulation;voltage var control},


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/examples/distribution-and-industrial-power-systems/feeder-20kv-600-node.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.