> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/examples/facts-and-hvdc/static-synchronous-compensator-statcom.md).

# Static Synchronous Compensator (STATCOM)

## Description

The **STATCOM** example, located in **File > Open an Example File > FACTS & HVDC**, demonstrates the use of a STATCOM in a transmission network for reactive power control and voltage regulation.

The objective is to show STATCOM operation in voltage regulation (with and without droop) and reactive power control modes on a three-bus, 500 kV system.

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-ff3858af64b111240eaffe6c2108a96a61e92a0b%2Fimage%20(74).png?alt=media" alt=""><figcaption></figcaption></figure>

## Requirements

This example model does not require any additional hardware or licenses.

## Detailed explanation

In this demo, a 66 kV, 300 MVAR STATCOM is used on a three-bus, 500 kV transmission system. The STATCOM is composed of a three-level neutral point clamped (NPC) converter and it is connected to the Point of Common Coupling (PCC) through a 66/500 kV transformer. The STATCOM is designed to have a power rating of around 300 MVA and a rated DC link voltage set-point at 160 kV. The carrier frequency of the converter is 1650 Hz.

## Simulation and results

The STATCOM is designed to operate in two control modes and each mode shows two different cases as explained below.

**Case 1 and 2** - AC voltage regulation with and without droop: converter supplies enough reactive power to maintain voltage at PCC at 1.0 pu (without droop) or at voltage as specified by droop (with droop)

**Case 3 and 4** -Reactive power control: the converter supplies the reactive power as demanded.

### Case 1: Voltage regulation, without droop

In this mode the voltage at the PCC is maintained at 1.0 pu. The source (grid) voltage at PCC is initially 1.0 pu and STATCOM supplies 0 MVAR.

When the source voltage from 1 to 0.97 pu, at 1.0 sec, STATCOM injects reactive power to maintain it at reference voltage of 1.0 pu. Alternatively, when the source voltage was changed from 0.97 to 1.045 pu at 1.5 sec, the STATCOM absorbs reactive power.

Set mode of operation to "**Voltage regulation**" and **droop value** to zero

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-379bae4874e0332aefd5285724413b82546e09da%2Fimage%20(75).png?alt=media" alt=""><figcaption></figcaption></figure>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-5f216b314ec37a61a4fcf6e2df94dbefb7c82dc0%2Fimage%20(76).png?alt=media" alt=""><figcaption></figcaption></figure>

### Case 2: Voltage regulation, with 2% droop

A droop of 2% is considered in this example which is a standard droop for practical systems.

The source (grid) voltage at PCC is initially 1.0 pu and STATCOM supplies 0 MVAR. When the source voltage from 1 to 0.97 pu, at 1.0 sec, STATCOM injects reactive power inline with its droop characteristics to maintain and increases the voltage to a level as determined by the droop.

It can be observed that the voltage is not exactly 1 pu but less, which is expected. Alternatively, when the source voltage was changed from 0.97 to 1.045 pu at 1.5 sec, the STATCOM absorbs reactive power.

Set mode of operation to "**Voltage regulation**" and **droop value** to 0.02

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-b60100b1aa559d369f35d5dd6eec9aca80330517%2Fimage%20(77).png?alt=media" alt=""><figcaption></figcaption></figure>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-fbb85f03394523a5fe0ea4db164f8e74050f78e4%2Fimage%20(78).png?alt=media" alt=""><figcaption></figcaption></figure>

### Case 3: Reactive power control, Q generating mode

In this mode, the Q reference is set as 0.6 pu. STATCOM is generating the reactive power as requested by user.

Set mode of operation to "**Q regulation**", **droop value** to 0 and **Qref** to 0.6

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-e360217263cb3979eab8b2ac1f8c521e283f9776%2Fimage%20(79).png?alt=media" alt=""><figcaption></figcaption></figure>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-4940130ec865c334ff79daa58ac8be3594e959ee%2Fimage%20(80).png?alt=media" alt=""><figcaption></figcaption></figure>

### Case 4: Reactive power control, Q absorbing mode

In this mode, the Q reference provided is set as -0.4 pu. STATCOM is generating the reactive power as requested by user.

Set mode of operation to "**Q regulation**", **droop value** to 0 and **Qref** to -0.4

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-28695134197b960dc75d69f4739b23bfb39283b1%2Fimage%20(81).png?alt=media" alt=""><figcaption></figcaption></figure>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-6a0c71a649c43f62c13e3017f5b45965eb6a8051%2Fimage%20(82).png?alt=media" alt=""><figcaption></figcaption></figure>

## References

1. G. Hingorani, L. Gyugyi, “Understanding FACTS; Concepts and Technology of Flexible AC Transmission Systems,” *IEEE*<sup>*®*</sup>*Press book*, 2000.


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/examples/facts-and-hvdc/static-synchronous-compensator-statcom.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.