> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-exciters/ieee-ac2a.md).

# IEEE AC2A

## Description

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-96dfe98b44bfa90c4b67c3182fcfcace1b39b61c%2Fimage%20(831).png?alt=media" alt="" width="176"><figcaption></figcaption></figure>

**AC2A excitation system** block, located in the **Control Exciters** library, is based on the IEEE Std. 412.5 type AC2A excitation system model.

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-cb072b3dbc823c2265a4a580bcf0efee079d2032%2Fimage%20(819).png?alt=media" alt=""><figcaption><p>AVR Block diagram</p></figcaption></figure>

{% hint style="info" %}
The HYPERSIM<sup>®</sup> simulation option Set Initial Conditions must be checked for the automatic initialization to work properly.
{% endhint %}

## Mask parameters

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-3e313e975f581cb01fc709dde869c81d86c58208%2FAC2A.jpg?alt=media" alt=""><figcaption></figcaption></figure>

{% tabs %}
{% tab title="AVR" %}

<table><thead><tr><th width="200.199951171875">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Tr</strong></td><td>Regulator input filter time constant (s). Not part of the standard; added for flexibility. Set to 0 if the filter is not used.</td></tr><tr><td><strong>Tb</strong></td><td>AVR lead-lag numerator (regulator) time constant (s).</td></tr><tr><td><strong>Tc</strong></td><td>AVR lead-lag denominator (regulator) time constant (s).</td></tr><tr><td><strong>Ka</strong></td><td>Voltage regulator/AVR filter gain (-).</td></tr><tr><td><strong>Ta</strong></td><td>AVR filter/regulator time constant (s).</td></tr><tr><td><strong>Kb</strong></td><td>Second-stage regulator gain (-).</td></tr><tr><td><strong>Kh</strong></td><td>High band gain (-).</td></tr><tr><td><strong>Kf</strong></td><td>Excitation control system stabilization gain (-).</td></tr><tr><td><strong>Tf</strong></td><td>Excitation control system stabilizer time constant (s).</td></tr><tr><td><strong>Vamax</strong></td><td>Maximum regulator internal voltage (pu).</td></tr><tr><td><strong>Vamin</strong></td><td>Minimum regulator internal voltage (pu).</td></tr><tr><td><strong>Vrmax</strong></td><td>Maximum voltage regulator output (pu).</td></tr><tr><td><strong>Vrmin</strong></td><td>Minimum voltage regulator output (pu).</td></tr></tbody></table>
{% endtab %}

{% tab title="Exciter" %}

<table><thead><tr><th width="200.20001220703125">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Te</strong></td><td>Exciter time constant (s).</td></tr><tr><td><strong>Ke</strong></td><td>Exciter constant related to self-excited field (-).</td></tr><tr><td><strong>Kd</strong></td><td>Demagnetization factor (-).</td></tr><tr><td><strong>Kc</strong></td><td>Rectifier loading factor (-).</td></tr><tr><td><strong>Se1, Se2</strong></td><td>Exciter saturation factor at the corresponding Vex (pu).</td></tr><tr><td><strong>Ve1, Ve2</strong></td><td>Exciter voltage for the exciter saturation function (pu).</td></tr><tr><td><strong>Vfemax</strong></td><td>Maximum exciter field current (pu).</td></tr></tbody></table>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-9131b723c23e9b597ec547d8f113a87851ca76fb%2Fimage%20(832).png?alt=media" alt=""><figcaption></figcaption></figure>
{% endtab %}

{% tab title="Initial value" %}

<table><thead><tr><th width="200.199951171875">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Ifd0</strong></td><td>Synchronous machine field current initial value (pu).</td></tr><tr><td><strong>Efd0</strong></td><td>Exciter output voltage initial value (pu).</td></tr></tbody></table>

{% hint style="info" %}
The parameters Ifd0 and Efd0 can be set manually by entering numerical values. They can also be set automatically, based on load flow calculations, by entering a referenced synchronous machine variable. For example, if the synchronous machine name is “SM1”:

* If a thermal machine or a hydraulic machine is used, set Ifd0 to “=SM1.IfdInit” multiplied by the synchronous machine parameter Xad = Xd – Xl, and set Efd0 to “=SM1.EfdInit”.
* If a pu standard or pu fundamental machine is used, set Ifd0 to “=SM1.IF\_Init” and Efd0 to “=SM1.EFD\_Init”.
  {% endhint %}
  {% endtab %}
  {% endtabs %}

## Inputs

<table><thead><tr><th width="201.20001220703125">Input</th><th>Description</th></tr></thead><tbody><tr><td><strong>Voel</strong></td><td>Over-excitation limiter output (pu).</td></tr><tr><td><strong>VC1</strong></td><td>Signal proportional to compensated terminal voltage. If the load compensator block is not used upstream from the exciter block, VC1 equals Vt (main alternator terminal voltage) (pu).</td></tr><tr><td><strong>Vuel</strong></td><td>Under-excitation limiter output (pu).</td></tr><tr><td><strong>Vref</strong></td><td>Voltage regulator reference voltage (pu).</td></tr><tr><td><strong>Vs</strong></td><td>Power system stabilizer (PSS) output voltage (pu).</td></tr><tr><td><strong>Ifd</strong></td><td>Synchronous machine field current (pu). See Useful tips for scaling requirements.</td></tr></tbody></table>

{% hint style="danger" %}
**Vuel** and **Voel** are normally inputs for this excitation system. You can choose fixed constant values directly in the mask by selecting the “internal” option.
{% endhint %}

If a Synch. Machine (Hydraulic or Thermal) from the Network Machines and Generators library is used, multiply the machine observable Ifd by the synchronous machine parameter Xad = Xd – Xl before applying it to the exciter input. This multiplication is not needed if a Synchronous Machine (pu Standard) or (pu Fundamental) is used.

## Outputs

| Output  | Description                  |
| ------- | ---------------------------- |
| **Efd** | Exciter output voltage (pu). |

## References

“IEEE Recommended Practice for Excitation System Models for Power System Models for Power System Stability Studies,” IEEE Standard 421.5-2005.


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-exciters/ieee-ac2a.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.