> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-exciters/ieee-ac8b.md).

# IEEE AC8B

## Description

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-90391f90541909c0dc4e6cf062e992c1eb55fab5%2Fimage%20(813).png?alt=media" alt="" width="236"><figcaption></figcaption></figure>

The **AC8B** block, located in the **Control Exciters** library, is based on the IEEE Std 412.5 type AC8B excitation system model \[1]. The block diagram represents an AC alternator with non-controlled rectifiers and provides alternate options for the under-excitation limiter input.

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-db2e19e56beaf1a1e29a36e2a0ec4f1d1e343345%2Fimage%20(811).png?alt=media" alt=""><figcaption><p>AC8B diagram</p></figcaption></figure>

{% hint style="info" %}
The HYPERSIM<sup>®</sup> simulation option Set Initial Conditions must be checked for the automatic initialization to work properly.
{% endhint %}

## Mask parameters

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-a545d5787360ebfeb6cf5e677d078aeb00971bb3%2FAC8A.jpg?alt=media" alt=""><figcaption></figcaption></figure>

{% tabs %}
{% tab title="AVR" %}

<table><thead><tr><th width="201">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Tr</strong></td><td>Regulator input time constant (s). This input filter is not part of the standard and has no recommended typical values; it was added for flexibility. This parameter can be set to zero if the filter is not used.</td></tr><tr><td><strong>Tdr</strong></td><td>Derivative time constant for the PID controller (s).</td></tr><tr><td><strong>Kpr</strong></td><td>Proportional gain for the PID controller.</td></tr><tr><td><strong>Kdr</strong></td><td>Derivative gain for the PID controller.</td></tr><tr><td><strong>Kir</strong></td><td>Integral gain for the PID controller.</td></tr><tr><td><strong>Ka</strong></td><td>AVR filter gain.</td></tr><tr><td><strong>Ta</strong></td><td>AVR filter time constant (s).</td></tr><tr><td><strong>VRmax</strong></td><td>Maximum regulator internal voltage (pu).</td></tr><tr><td><strong>VRmin</strong></td><td>Minimum regulator internal voltage (pu).</td></tr></tbody></table>
{% endtab %}

{% tab title="Exciter" %}

<table><thead><tr><th width="200.20001220703125">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Ke</strong></td><td>Exciter constant related to self-excited field.</td></tr><tr><td><strong>Te</strong></td><td>Exciter time constant (s).</td></tr><tr><td><strong>Kc</strong></td><td>Rectifier loading factor.</td></tr><tr><td><strong>Kd</strong></td><td>Demagnetizing factor.</td></tr><tr><td><strong>Se1, Se2</strong></td><td>Exciter saturation factor at the corresponding Vex (pu).</td></tr><tr><td><strong>Ve1, Ve2</strong></td><td>Exciter voltage for the exciter saturation function (pu).</td></tr><tr><td><strong>VEmin</strong></td><td>Minimum exciter output voltage (pu).</td></tr><tr><td>Vfemax</td><td>Maximum exciter field current (pu).</td></tr></tbody></table>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-38ac5a9ba4f376aeb25590b1a95273c27ccca8fe%2Fimage%20(812).png?alt=media" alt=""><figcaption><p>Exciter diagram</p></figcaption></figure>
{% endtab %}

{% tab title="Initial values" %}

<table><thead><tr><th width="201.79998779296875">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Ifd0</strong></td><td>Synchronous machine field current initial value (pu).</td></tr><tr><td><strong>Efd0</strong></td><td>Exciter output voltage initial value (pu).</td></tr></tbody></table>

{% hint style="info" %}
The parameters Ifd0 and Efd0 can be entered manually or set automatically from load flow results by referencing the synchronous machine variables. For example, if the connected synchronous machine is named “SM1”:

* If a thermal machine or a hydraulic machine is used: set Ifd0 to “=SM1.IfdInit” multiplied by Xad = Xd – Xl, and set Efd0 to “=SM1.EfdInit”.
* If a pu standard or pu fundamental machine is used: set Ifd0 to “=SM1.IF\_Init” and Efd0 to “=SM1.EFD\_Init”.
  {% endhint %}
  {% endtab %}
  {% endtabs %}

## Inputs

<table><thead><tr><th width="200.4000244140625">Input</th><th>Description</th></tr></thead><tbody><tr><td><strong>Vc1</strong></td><td>Signal proportional to compensated terminal voltage (pu). If a load compensator block is not used upstream from the exciter block, Vc1 equals Vt (main alternator terminal voltage).</td></tr><tr><td><strong>Vref</strong></td><td>Voltage regulator reference voltage (pu).</td></tr><tr><td><strong>Vs</strong></td><td>Output voltage of a power system stabilizer (PSS) (pu).</td></tr><tr><td><strong>Ifd</strong></td><td>Synchronous machine field current (pu).</td></tr></tbody></table>

If a Synch. Machine (Hydraulic or Thermal) from the Network Machines and Generators library is used, multiply the machine observable Ifd by the synchronous machine parameter Xad = Xd – Xl before connecting it to the exciter input. This multiplication is not needed for a Synchronous Machine (pu Standard) or (pu Fundamental).

## Outputs

<table><thead><tr><th width="199.5999755859375">Output</th><th>Description</th></tr></thead><tbody><tr><td><strong>Efd</strong></td><td>Exciter output voltage (pu).</td></tr></tbody></table>

## References

“IEEE Recommended Practice for Excitation System Models for Power System Models forPower System Stability Studies,” IEEE Standard 421.5-2005.


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-exciters/ieee-ac8b.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.