> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-exciters/ieee-exac1.md).

# IEEE EXAC1

## Description

The **EXAC1** block, located in the **Control Exciters** library,is based on the IEEE Std. 412.5 type AC1 excitation system model described in the 1981 IEEE committee report . The component was developed in line with references \[1] and \[2].

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-70fbcb033626dcd88a10d60cae5a0bdc263873bc%2Fimage%20(806).png?alt=media" alt=""><figcaption><p>EXAC1 diagram</p></figcaption></figure>

{% hint style="info" %}
The HYPERSIM<sup>®</sup> simulation option Set Initial Conditions must be checked for the automatic initialization to work properly.
{% endhint %}

## Mask parameters

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-7047b67167d26903ae913834a055916b511d7a76%2FEXAC1.jpg?alt=media" alt=""><figcaption></figcaption></figure>

{% tabs %}
{% tab title="AVR" %}

<table><thead><tr><th width="201">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Tr</strong></td><td>Regulator input filter time constant. This filter is not part of [1]; it was added for flexibility.<br>Set Tr = 0 to disable. Unit: s. Range: 0 &#x3C; Tr &#x3C; 0.5.</td></tr><tr><td><strong>Tb</strong></td><td>AVR lead-lag numerator time constant (s). Range: 0 &#x3C; Tb &#x3C; 20.</td></tr><tr><td><strong>Tc</strong></td><td>AVR lead-lag denominator time constant (s). Range: 0 &#x3C; Tc &#x3C; 20.</td></tr><tr><td><strong>Ka</strong></td><td>AVR filter gain. Range: 0 &#x3C; Ka &#x3C; 1000.</td></tr><tr><td><strong>Ta</strong></td><td>AVR filter time constant (s). Range: 0 &#x3C; Ta &#x3C; 10.0.</td></tr><tr><td><strong>VRmax</strong></td><td>Maximum voltage regulator output. Unit: pu. Range: 0 &#x3C; VRmax ≤ 10.</td></tr><tr><td><strong>VRmin</strong></td><td>Minimum voltage regulator output. Unit: pu. Range: -10 ≤ VRmin &#x3C; 0.</td></tr><tr><td><strong>Kf</strong></td><td>Excitation control system stabilizer gain. Unit: --. Range: 0 &#x3C; Kf ≤ 0.3.</td></tr><tr><td><strong>Tf</strong></td><td>Excitation control system stabilizer time constant (s).<br>Range: 0.02 &#x3C; Tf &#x3C; 1.5.</td></tr></tbody></table>
{% endtab %}

{% tab title="Exciter" %}

<table><thead><tr><th width="201">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Ke</strong></td><td>Exciter constant related to self-excited field. Range: 0 &#x3C; Ke ≤ 1.</td></tr><tr><td><strong>Te</strong></td><td>Exciter time constant (s). Range: 0.02 &#x3C; Te &#x3C; 2.</td></tr><tr><td><strong>Kd</strong></td><td>Demagnetizing factor. Range: 0 ≤ Kd ≤ 1.</td></tr><tr><td><strong>Kc</strong></td><td>Rectifier loading factor. Range: 0 ≤ Kc ≤ 1.</td></tr><tr><td><strong>Se2, Se1</strong></td><td>Exciter saturation factor at the corresponding Vex (pu).</td></tr><tr><td><strong>Ve2, Ve1</strong></td><td>Exciter voltage for the exciter saturation function (pu).</td></tr></tbody></table>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-59d6d72d63cbeae78470dd26fd64354def7a5b5f%2Fjfx13260516802321503306.png?alt=media" alt=""><figcaption><p>Exciter diagram</p></figcaption></figure>
{% endtab %}

{% tab title="Initial values" %}

<table><thead><tr><th width="200.39178466796875">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Ifd0</strong></td><td>Synchronous machine field current initial value (pu).</td></tr><tr><td><strong>Efd0</strong></td><td>Exciter output voltage initial value (pu).</td></tr></tbody></table>

{% hint style="info" %}
The parameters Ifd0 and Efd0 can be set manually by entering numeric values, or automatically from load flow results by referencing synchronous machine variables. For example, if the synchronous machine name is “SM1”:

* If a thermal or hydraulic machine is used, set Ifd0 to “=SM1.IfdInit” multiplied by Xad = Xd – Xl, and set Efd0 to “=SM1.EfdInit”.
* If a pu standard or pu fundamental machine is used, set Ifd0 to “=SM1.IF\_Init” and Efd0 to “=SM1.EFD\_Init”.
  {% endhint %}
  {% endtab %}
  {% endtabs %}

## Inputs

<table><thead><tr><th width="199.87322998046875">Input</th><th>Description</th></tr></thead><tbody><tr><td><strong>Voel</strong></td><td>Over-excitation limiter output.</td></tr><tr><td><strong>Vc1</strong></td><td>Signal proportional to compensated terminal voltage (see the Load Compensator block documentation). If the Load Compensator block is not used upstream of the exciter, Vc1 equals Vt (main alternator terminal voltage).</td></tr><tr><td><strong>Vuel</strong></td><td>Under-excitation limiter output.</td></tr><tr><td><strong>Vref</strong></td><td>Voltage regulator reference voltage.</td></tr><tr><td><strong>Vs</strong></td><td>Output voltage of a Power System Stabilizer (PSS).</td></tr><tr><td><strong>Ifd</strong></td><td>Synchronous machine field current.</td></tr></tbody></table>

{% hint style="danger" %}
**Vuel** and **Voel** are the usual inputs for this excitation system, but you can choose fixed constant values directly in the mask by selecting “internal.”
{% endhint %}

If a Synch. Machine (Hydraulic or Thermal) from the Network Machines and Generators library is used, multiply the machine observable Ifd by the synchronous machine parameter Xad = Xd – Xl before connecting it to the exciter. This multiplication is not needed if a Synchronous Machine (pu Standard) or (pu Fundamental) is used.

## Outputs

| Output  | Description             |
| ------- | ----------------------- |
| **Efd** | Exciter output voltage. |

## References

\[1] I. C. Report, "Excitation System Models for Power System Stability Studies," in IEEE Transactions on Power Apparatus and Systems, vol. PAS-100, no. 2, pp. 494-509, Feb. 1981.

\[2] PSS<sup>®</sup>E 34.2.0 Model Library. NY, USA: Siemens Industry, Inc., 2017.


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-exciters/ieee-exac1.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.