> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-exciters/ieee-exac2.md).

# IEEE EXAC2

## Description

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-d70e9fe98c0d19aa26aeb857ba11af68659bca7d%2Fimage%20(792).png?alt=media" alt="" width="160"><figcaption></figcaption></figure>

The **EXAC2** block, located in the **Control Exciters** library, is based on the IEEE Std. 412.5 type AC2 excitation system model described in the 1981 IEEE committee report. The EXAC2 component was developed in line with \[1] and \[2].

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-5592ee1ef4bb49603d8f7b84d31db2afc30f5d65%2Fimage%20(793).png?alt=media" alt=""><figcaption><p>EXAC2 diagram</p></figcaption></figure>

{% hint style="info" %}
The HYPERSIM<sup>®</sup> simulation option Set Initial Conditions must be checked for the automatic initialization to work properly.
{% endhint %}

## Mask parameters

{% tabs %}
{% tab title="AVR" %}

<table><thead><tr><th width="199.8731689453125">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Tr</strong></td><td>Regulator input filter time constant (s). This input filter is not part of the IEEE committee report [1] and was added for flexibility. Set to 0 to disable. Valid range: 0 &#x3C; Tr &#x3C; 0.5.</td></tr><tr><td><strong>Tb</strong></td><td>AVR lead–lag numerator time constant (s). Valid range: 0 &#x3C; Tb &#x3C; 20.</td></tr><tr><td><strong>Tc</strong></td><td>AVR lead–lag denominator time constant (s). Valid range: 0 &#x3C; Tc &#x3C; 20.</td></tr><tr><td><strong>Ka</strong></td><td>AVR filter gain. Valid range: 0 &#x3C; Ka &#x3C; 1000.</td></tr><tr><td><strong>Ta</strong></td><td>AVR filter time constant (s). Valid range: 0 &#x3C; Ta &#x3C; 10.0.</td></tr><tr><td><strong>VRmax</strong></td><td>Maximum voltage regulator output (pu). Valid range: 0 &#x3C; VRmax ≤ 10.</td></tr><tr><td><strong>VRmin</strong></td><td>Minimum voltage regulator output (pu). Valid range: −10 ≤ VRmin &#x3C; 0.</td></tr><tr><td><strong>Kf</strong></td><td>Excitation control system stabilizer gain. Valid range: 0 &#x3C; Kf ≤ 0.3.</td></tr><tr><td><strong>Tf</strong></td><td>Excitation control system stabilizer time constant (s). Valid range: 0.02 &#x3C; Tf &#x3C; 1.5.</td></tr><tr><td><strong>VAmax</strong></td><td>Maximum regulator internal voltage (pu). Valid range: 0 &#x3C; VAmax ≤ 15.</td></tr><tr><td><strong>VAmin</strong></td><td>Minimum regulator internal voltage (pu). Valid range: −15 ≤ VAmin &#x3C; 0.</td></tr><tr><td><strong>Kb</strong></td><td>Second-stage regulator gain.</td></tr><tr><td><strong>Kl</strong></td><td>Exciter field current limiter gain.</td></tr><tr><td><strong>Kh</strong></td><td>Exciter field current feedback gain.</td></tr><tr><td><strong>Vlr</strong></td><td>Maximum exciter field current (pu).</td></tr></tbody></table>
{% endtab %}

{% tab title="Exciter" %}

<table><thead><tr><th width="199.87322998046875">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Ke</strong></td><td>Exciter constant related to self-excited field. Valid range: 0 &#x3C; Ke ≤ 1.</td></tr><tr><td><strong>Te</strong></td><td>Exciter time constant (s). Valid range: 0.02 &#x3C; Te &#x3C; 2.</td></tr><tr><td><strong>Kd</strong></td><td>Demagnetizing factor. Valid range: 0 ≤ Kd ≤ 1.</td></tr><tr><td><strong>Kc</strong></td><td>Rectifier loading factor. Valid range: 0 ≤ Kc ≤ 1.</td></tr><tr><td><strong>Se2, Se1</strong></td><td>Exciter saturation factors (pu) at the corresponding Vex.</td></tr><tr><td><strong>Ve2, Ve1</strong></td><td>Exciter voltages (pu) for the exciter saturation function.</td></tr></tbody></table>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-7f2d9c7e2a7fa703a05ad6c556ca6b0f9a9bacc4%2Fimage%20(794).png?alt=media" alt=""><figcaption><p>Exciter diagram</p></figcaption></figure>
{% endtab %}

{% tab title="Initial values" %}

<table><thead><tr><th width="200.62371826171875">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Ifd0</strong></td><td>Initial value of the synchronous machine field current (pu).</td></tr><tr><td><strong>Efd0</strong></td><td>Initial value of the exciter output voltage (pu).</td></tr></tbody></table>

{% hint style="info" %}
The parameters Ifd0 and Efd0 can be set manually by entering numerical values, or automatically from load flow results by referencing synchronous machine variables. For example, if the synchronous machine name is "SM1":

* If a thermal machine or a hydraulic machine is used, set Ifd0 to "=SM1.IfdInit" multiplied by Xad = Xd − Xl, and set Efd0 to "=SM1.EfdInit".
* If a pu standard or pu fundamental machine is used, set Ifd0 to "=SM1.IF\_Init" and Efd0 to "=SM1.EFD\_Init".
  {% endhint %}
  {% endtab %}
  {% endtabs %}

## Inputs

<table><thead><tr><th width="198.37213134765625">Input</th><th>Description</th></tr></thead><tbody><tr><td><strong>Voel</strong></td><td>Over-excitation limiter output. Normally provided as an input; you can select an internal fixed value in the mask.</td></tr><tr><td><strong>Vc1</strong></td><td>Signal proportional to the compensated terminal voltage (see Load Compensator documentation). If the Load Compensator block is not used upstream of the exciter, Vc1 equals Vt (main alternator terminal voltage).</td></tr><tr><td><strong>Vuel</strong></td><td>Under-excitation limiter output. Normally provided as an input; you can select an internal fixed value in the mask.</td></tr><tr><td><strong>Vref</strong></td><td>Voltage regulator reference voltage.</td></tr><tr><td><strong>Vs</strong></td><td>Output voltage of a Power System Stabilizer (PSS).</td></tr><tr><td><strong>Ifd</strong></td><td>Synchronous machine field current. If a Synch. Machine (Hydraulic or Thermal) from the Network Machines and Generators library is used, multiply the machine observable Ifd by Xad = Xd − Xl before connecting it to the exciter. This multiplication is not needed for a Synchronous Machine (pu Standard) or (pu Fundamental).</td></tr></tbody></table>

## Outputs

<table><thead><tr><th width="199.87322998046875">Output</th><th>Description</th></tr></thead><tbody><tr><td><strong>Efd</strong></td><td>Exciter output voltage.</td></tr></tbody></table>

## References

\[1] I. C. Report, "Excitation System Models for Power System Stability Studies," in IEEE Transactions on Power Apparatus and Systems, vol. PAS-100, no. 2, pp. 494-509, Feb. 1981.

\[2] PSS<sup>®</sup>E 34.2.0 Model Library. NY, USA: Siemens Industry, Inc., 2017.


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-exciters/ieee-exac2.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.