> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-exciters/ieee-exac3.md).

# IEEE EXAC3

## Description

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-816eb67a4cffb1464865b70379562ba0c82da93a%2Fimage%20(795).png?alt=media" alt="" width="154"><figcaption></figcaption></figure>

The **EXAC3** block, located in the **Control Exciters** library, models the IEEE Std. 412.5 type AC3 excitation system as described in the 1981 IEEE committee report. The block was developed in line with the references \[1] and \[2].

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-7e35ef0e871370752a6211c3a0f2397de7d98184%2Fimage%20(796).png?alt=media" alt=""><figcaption><p>EXAC3 diagram</p></figcaption></figure>

{% hint style="info" %}
The HYPERSIM<sup>®</sup> simulation option Set Initial Conditions must be checked for the automatic initialization to work properly.
{% endhint %}

## Mask parameters

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-07def712b86d7fc9251554963483a1cade3a284a%2FEXAC3.jpg?alt=media" alt=""><figcaption></figcaption></figure>

{% tabs %}
{% tab title="AVR" %}

<table><thead><tr><th width="201.14239501953125">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Tr</strong></td><td>Regulator input filter time constant (s). This filter was added for flexibility. Set Tr = 0 to disable. Range: 0 &#x3C; Tr &#x3C; 0.5.</td></tr><tr><td><strong>K</strong><sub><strong>r</strong></sub></td><td>Constant associated with the regulator and alternator field power supply.</td></tr><tr><td><strong>Tb</strong></td><td>AVR lead-lag numerator time constant (s). Range: 0 &#x3C; Tb &#x3C; 20.</td></tr><tr><td><strong>Tc</strong></td><td>AVR lead-lag denominator time constant (s). Range: 0 &#x3C; Tc &#x3C; 20.</td></tr><tr><td><strong>Ka</strong></td><td>AVR filter gain. Range: 0 &#x3C; Ka &#x3C; 1000.</td></tr><tr><td><strong>Ta</strong></td><td>AVR filter time constant (s). Range: 0 &#x3C; Ta &#x3C; 10.0.</td></tr><tr><td><strong>Kf</strong></td><td>Excitation control system stabilizer gain. Range: 0 &#x3C; Kf ≤ 0.3.</td></tr><tr><td><strong>Tf</strong></td><td>Excitation control system stabilizer time constant (s).<br>Range: 0.02 &#x3C; Tf &#x3C; 1.5.</td></tr><tr><td><strong>VAmax</strong></td><td>Maximum regulator internal voltage (pu).<br>Range: 0 &#x3C; VAmax ≤ 15.</td></tr><tr><td><strong>VAmin</strong></td><td>Minimum regulator internal voltage (pu).<br>Range: −15 ≤ VAmin &#x3C; 0.</td></tr><tr><td><strong>Klv</strong></td><td>Gain used in the minimum field voltage limiter loop.</td></tr><tr><td><strong>Vlv</strong></td><td>Field voltage used in the minimum field voltage limiter loop (pu).</td></tr></tbody></table>
{% endtab %}

{% tab title="Exciter" %}

<table><thead><tr><th width="199.8731689453125">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Ke</strong></td><td>Exciter constant related to self-excited field (pu).<br>Range: 0 &#x3C; Ke ≤ 1.</td></tr><tr><td><strong>Te</strong></td><td>Exciter time constant (s). Range: 0.02 &#x3C; Te &#x3C; 2.</td></tr><tr><td><strong>Kd</strong></td><td>Demagnetizing factor (pu). Range: 0 ≤ Kd ≤ 1.</td></tr><tr><td><strong>Kc</strong></td><td>Rectifier loading factor (pu). Range: 0 ≤ Kc ≤ 1.</td></tr><tr><td><strong>Kn</strong></td><td>Excitation control system stabilizer gain.</td></tr><tr><td><strong>EFDN</strong></td><td>Value of EFD (pu) at which the feedback gain changes.</td></tr><tr><td><strong>Se2, Se1</strong></td><td>Exciter saturation factor (pu) at the corresponding Vex.</td></tr><tr><td><strong>Ve2, Ve1</strong></td><td>Exciter voltage (pu) for the exciter saturation function.</td></tr></tbody></table>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-75702c7777aa945ef3bd740f460f09035ea0002c%2Fimage%20(797).png?alt=media" alt=""><figcaption><p>Exciter diagram</p></figcaption></figure>
{% endtab %}

{% tab title="Initial values" %}

<table><thead><tr><th width="200.39178466796875">parameter</th><th>Descrption</th></tr></thead><tbody><tr><td><strong>Ifd0</strong></td><td>Synchronous machine field current initial value (pu).</td></tr><tr><td><strong>Efd0</strong></td><td>Exciter output voltage initial value (pu).</td></tr></tbody></table>

{% hint style="info" %}
Ifd0 and Efd0 can be set manually or automatically using referenced synchronous machine variables. For example, if the synchronous machine name is “SM1”:

* If a thermal machine or a hydraulic machine is used, set Ifd0 to “=SM1.IfdInit” multiplied by Xad = Xd – Xl, and set Efd0 to “=SM1.EfdInit”.
* If a pu standard or pu fundamental machine is used, set Ifd0 to “=SM1.IF\_Init” and Efd0 to “=SM1.EFD\_Init”.
  {% endhint %}
  {% endtab %}
  {% endtabs %}

## Inputs

<table><thead><tr><th width="200.62384033203125">Input</th><th>Description</th></tr></thead><tbody><tr><td><strong>Voel</strong></td><td>Over-excitation limiter output.</td></tr><tr><td><strong>Vc1</strong></td><td>Signal proportional to compensated terminal voltage (see Load Compensator block). If the Load Compensator block is not used upstream of the exciter, Vc1 equals Vt (main alternator terminal voltage).</td></tr><tr><td><strong>Vuel</strong></td><td>Under-excitation limiter output.</td></tr><tr><td><strong>Vref</strong></td><td>Voltage regulator reference voltage.</td></tr><tr><td><strong>Vs</strong></td><td>Output voltage of a Power System Stabilizer (PSS) [1].</td></tr><tr><td><strong>Ifd</strong></td><td>Synchronous machine field current.</td></tr></tbody></table>

{% hint style="danger" %}
**Vuel** is the usual input for this excitation system. You can alternatively use a fixed constant value by selecting the “internal” option in the mask.
{% endhint %}

If a Synch. Machine (Hydraulic or Thermal) from the Network Machines and Generators library is used, the machine observable Ifd must be multiplied by the synchronous machine parameter Xad = Xd – Xl before it is applied to the exciter. This multiplication is not needed if a Synchronous Machine (pu Standard) or (pu Fundamental) is used.

## Outputs

<table><thead><tr><th width="199.12261962890625">Output</th><th>Description</th></tr></thead><tbody><tr><td><strong>Efd</strong></td><td>Exciter output voltage.</td></tr></tbody></table>

## References

\[1] I. C. Report, "Excitation System Models for Power System Stability Studies," in IEEE Transactions on Power Apparatus and Systems, vol. PAS-100, no. 2, pp. 494-509, Feb. 1981.

\[2] PSS<sup>®</sup>E 34.2.0 Model Library. NY, USA: Siemens Industry, Inc., 2017.


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-exciters/ieee-exac3.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.