> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-exciters/ieee-expic1.md).

# IEEE EXPIC1

## Description

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-059054c7e4d9d391ed2579e93a5c316d1c3ae5f2%2Fimage%20(801).png?alt=media" alt="" width="175"><figcaption></figcaption></figure>

The **EXPIC1** block, located in the **Control Exciters** library, is based on the IEEE Std. 412.5 type EXPIC1 excitation system model in which the voltage regulator includes a proportional–integral (PI) control element. The EXPIC1 block was developed in line with references \[1] and \[2].

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-b70cc4a1d4de49f4e58c8213b6df506986849a67%2Fimage%20(805).png?alt=media" alt=""><figcaption><p>EXPC1 diagram</p></figcaption></figure>

{% hint style="info" %}
The HYPERSIM<sup>®</sup> simulation option Set Initial Conditions must be checked for the automatic initialization to work properly.
{% endhint %}

## Mask parameters

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-e9258df855c3bb970504be69c0444a715100073b%2FEXPC1.jpg?alt=media" alt=""><figcaption></figcaption></figure>

{% tabs %}
{% tab title="AVR" %}

<table><thead><tr><th width="199.64129638671875">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Tr</strong></td><td>Regulator input filter time constant (s). Not part of the IEEE committee report and no typical values are recommended in [1]; this filter is added for flexibility.<br>Note: set Tr = 0 to disable the filter.</td></tr><tr><td><strong>Ka</strong></td><td>PI controller gain.</td></tr><tr><td><strong>Ta1</strong></td><td>PI controller time constant (s).</td></tr><tr><td><strong>VR1</strong></td><td>PI controller maximum limit (pu).</td></tr><tr><td><strong>VR2</strong></td><td>PI controller minimum limit (pu).</td></tr><tr><td><strong>Ta2</strong></td><td>Voltage regulator time constant (s).</td></tr><tr><td><strong>Ta3</strong></td><td>Voltage regulator time constant (s).</td></tr><tr><td><strong>Ta4</strong></td><td>Voltage regulator time constant (s).</td></tr><tr><td><strong>VRmax</strong></td><td>Maximum voltage regulator output (pu).</td></tr><tr><td><strong>VRmin</strong></td><td>Minimum voltage regulator output (pu).</td></tr><tr><td><strong>Kf</strong></td><td>Rate feedback gain.</td></tr><tr><td><strong>Tf1</strong></td><td>Rate feedback time constant (s). Constraint: Tf1 > 0.04; otherwise Tf1 = 0.04.</td></tr><tr><td><strong>Tf2</strong></td><td>Rate feedback time constant (s).</td></tr></tbody></table>
{% endtab %}

{% tab title="Exciter" %}

<table><thead><tr><th width="199.6412353515625">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Ke</strong></td><td>Exciter constant related to self-excited field.</td></tr><tr><td><strong>Te</strong></td><td>Exciter time constant (s).</td></tr><tr><td><strong>Kp</strong></td><td>Potential circuit real part gain coefficient.</td></tr><tr><td><strong>Ki</strong></td><td>Potential circuit imaginary part gain coefficient.</td></tr><tr><td><strong>Kc</strong></td><td>Rectifier loading factor proportional to commutating reactance.</td></tr><tr><td><strong>Se2, Se1</strong></td><td>Exciter saturation factor at the corresponding Vex (pu). Constraint: Se1 ≥ Se2.</td></tr><tr><td><strong>Ve2, Ve1</strong></td><td>Exciter voltage for the exciter saturation function (pu). Constraints: Ve1 > 0 and Ve1 > Ve2.</td></tr></tbody></table>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-76d108ff5f53da71026887842b21699fe09e3a5e%2Fimage%20(802).png?alt=media" alt=""><figcaption><p>Exciter diagram</p></figcaption></figure>
{% endtab %}

{% tab title="Initial values" %}

<table><thead><tr><th width="201.142333984375">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Ifd0</strong></td><td>Synchronous machine field current initial value (pu).</td></tr><tr><td><strong>Efd0</strong></td><td>Exciter output voltage initial value (pu).</td></tr></tbody></table>

{% hint style="info" %}
You can set Ifd0 and Efd0 manually (enter a numeric value) or automatically from load-flow results by referencing synchronous machine variables. For example, if the synchronous machine name is “SM1”:

* If a thermal machine or a hydraulic machine is used, set Ifd0 to “=SM1.IfdInit” multiplied by Xad = Xd − Xl, and set Efd0 to “=SM1.EfdInit”.
* If a pu standard or pu fundamental machine is used, set Ifd0 to “=SM1.IF\_Init” and Efd0 to “=SM1.EFD\_Init”.
  {% endhint %}
  {% endtab %}
  {% endtabs %}

## Inputs

<table><thead><tr><th width="199.87322998046875">Input</th><th>Description</th></tr></thead><tbody><tr><td><strong>Voel</strong></td><td>Over-excitation limiter output.</td></tr><tr><td><strong>Vc1</strong></td><td>Signal proportional to compensated terminal voltage <mark style="background-color:yellow;">(see the Load Compensator block documentation). I</mark>f the Load Compensator block is not used upstream of the exciter block, Vc1 equals Vt (main alternator terminal voltage).</td></tr><tr><td><strong>Vuel</strong></td><td>Under-excitation limiter output.</td></tr><tr><td><strong>Vref</strong></td><td>Voltage regulator reference voltage.</td></tr><tr><td><strong>Vs</strong></td><td>Output voltage of a Power System Stabilizer (PSS).</td></tr><tr><td><strong>Id</strong></td><td>d-axis component of generator terminal current.</td></tr><tr><td><strong>Iq</strong></td><td>q-axis component of generator terminal current.</td></tr><tr><td><strong>Vd</strong></td><td>d-axis component of generator terminal voltage.</td></tr><tr><td><strong>Vq</strong></td><td>q-axis component of generator terminal voltage.</td></tr><tr><td><strong>Ifd</strong></td><td>Synchronous machine field current.</td></tr></tbody></table>

{% hint style="danger" %}
**Vuel** and **Voel** are the usual inputs for this excitation system, but you can choose fixed constant values directly in the mask by selecting “internal.”
{% endhint %}

If a Synchronous Machine (Hydraulic or Thermal) from the Network Machines and Generators library is used, multiply the machine observable Ifd by Xad = Xd – Xl before connecting it to the exciter. This multiplication is not needed for a Synchronous Machine (pu Standard) or (pu Fundamental).

## Outputs

<table><thead><tr><th width="199.87322998046875">Output</th><th>Description</th></tr></thead><tbody><tr><td><strong>Efd</strong></td><td>Exciter output voltage (pu).</td></tr></tbody></table>

The terminal current is computed from Id and Iq as: ![](https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-ef212612c372a3b581b664f4c2d8ab08bf82ae6a%2Fimage%20\(803\).png?alt=media)

The terminal voltage is computed from Vd and Vq as: ![](https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-e921be76c546bb9d40dac069f435e9a6e4623004%2Fimage%20\(804\).png?alt=media)

## References

1. S. Paszek, A. Boboń, S. Berhausen, Ł. Majka, A. Nocoń, and P. Pruski, “Simulation Models of Generating Unit Elements,” in Synchronous generators and excitation systems operating in a power system: measurement methods and modeling, Cham, Switzerland: Springer, 2020, pp. 36–37.
2. PSS<sup>®</sup>E 34.2.0 Model Library. NY, USA: Siemens Industry, Inc., 2017.


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-exciters/ieee-expic1.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.