> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-exciters/ieee-exst1.md).

# IEEE EXST1

## Description

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-4e915ca416a8b765a0e41abe98d2264b3f35357b%2Fimage%20(844).png?alt=media" alt="" width="140"><figcaption></figcaption></figure>

The **EXST1** block, located in the **Control Exciters** library, implements the IEEE Std. 412.5 type ST1 excitation system model described in the 1981 IEEE committee report. The component was developed in line with \[1] and \[2].

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-2253d144ed4e8b1aa96727f6f1d65503796715eb%2Fimage%20(845).png?alt=media" alt=""><figcaption><p>EXST1 diagram</p></figcaption></figure>

{% hint style="info" %}
The HYPERSIM<sup>®</sup> simulation option Set Initial Conditions must be checked for the automatic initialization to work properly.
{% endhint %}

## Mask parameters

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-2c679c8be8368e92fa4c60b6edc95939ef8aaed7%2FEXST1.jpg?alt=media" alt=""><figcaption></figcaption></figure>

{% tabs %}
{% tab title="Exciter" %}

<table><thead><tr><th width="201">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Tr</strong></td><td>Regulator input filter time constant (s). This input filter was added for flexibility. Set to 0 to disable.</td></tr><tr><td><strong>VImax</strong></td><td>Maximum regulator input voltage (pu).</td></tr><tr><td><strong>VImin</strong></td><td>Minimum regulator input voltage (pu).</td></tr><tr><td><strong>Tb</strong></td><td>AVR lead-lag numerator time constant (s).</td></tr><tr><td><strong>Tc</strong></td><td>AVR lead-lag denominator time constant (s).</td></tr><tr><td><strong>Ka</strong></td><td>AVR filter gain.</td></tr><tr><td><strong>Ta</strong></td><td>AVR filter time constant.</td></tr><tr><td><strong>VRmax</strong></td><td>Maximum voltage regulator output (pu).</td></tr><tr><td><strong>VRmin</strong></td><td>Minimum voltage regulator output (pu).</td></tr><tr><td><strong>Kf</strong></td><td>Excitation control system stabilizer gain.</td></tr><tr><td>Tf</td><td>Excitation control system stabilizer time constant (s).<br>Constraint: Tf > 0.3; otherwise Tf = 0.3.</td></tr><tr><td><strong>Kc</strong></td><td>Rectifier loading factor.</td></tr></tbody></table>
{% endtab %}

{% tab title="Initial value" %}

<table><thead><tr><th width="200.199951171875">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Efd0</strong></td><td>Exciter output voltage initial value (pu).</td></tr></tbody></table>

{% hint style="info" %}
Efd0 can be set manually by entering a numerical value, or automatically from load flow results by referencing a synchronous machine variable. If the machine name is “SM1”: set Efd0 to “=SM1.EfdInit” for a thermal or hydraulic machine; set Efd0 to “=SM1.EFD\_Init” for a pu standard or pu fundamental machine.
{% endhint %}
{% endtab %}
{% endtabs %}

## Inputs

<table><thead><tr><th width="200">Input</th><th>Description</th></tr></thead><tbody><tr><td><strong>Voel</strong></td><td>Over-excitation limiter output (pu).</td></tr><tr><td><strong>Vc1</strong></td><td>Signal proportional to compensated terminal voltage (pu). If the Load Compensator block is not used upstream of the exciter block, connect Vc1 to the machine Vt.</td></tr><tr><td><strong>Vt</strong></td><td>Machine terminal voltage (pu).</td></tr><tr><td><strong>Vuel</strong></td><td>Under-excitation limiter output (pu).</td></tr><tr><td><strong>Vref</strong></td><td>Voltage regulator reference voltage (pu).</td></tr><tr><td><strong>Vs</strong></td><td>Output voltage of a Power System Stabilizer (PSS) (pu).</td></tr><tr><td><strong>Ifd</strong></td><td>Synchronous machine field current (pu).</td></tr></tbody></table>

{% hint style="danger" %}
**Vuel** and **Voel** are normally inputs for this excitation system. You can choose fixed constant values directly in the mask by selecting the “internal” option.
{% endhint %}

If a Synch. Machine (Hydraulic or Thermal) from the Network Machines and Generators library is used, multiply the machine observable Ifd by Xad = Xd – Xl before connecting it to the exciter. This multiplication is not needed for a Synchronous Machine (pu Standard) or (pu Fundamental).

## Outputs

<table><thead><tr><th width="200">Output</th><th>Description</th></tr></thead><tbody><tr><td><strong>Efd</strong></td><td>Exciter output voltage (pu).</td></tr></tbody></table>

## References

\[1] I. C. Report, "Excitation System Models for Power System Stability Studies," in IEEE Transactions on Power Apparatus and Systems, vol. PAS-100, no. 2, pp. 494-509, Feb. 1981.

\[2] PSS®E 34.2.0 Model Library. NY, USA: Siemens Industry, Inc., 2017.


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-exciters/ieee-exst1.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.