> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-exciters/ieee-exst3.md).

# IEEE EXST3

## Description

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-c17e9a5a1b0645f8bc74357ce900a6e1bc691e99%2Fimage%20(847).png?alt=media" alt="" width="200"><figcaption></figcaption></figure>

The **EXST3** block, located in the **Control Exciters** library, is a compound source controlled-rectifier excitation system based on the IEEE Std. 412.5 type ST3 model described in the 1981 IEEE committee report. The EXST3 component was developed in line with references \[1] and \[2].

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-f7eaffefe405cdacac6e3873372a95922f2f7e99%2Fimage%20(846).png?alt=media" alt=""><figcaption><p>EXST3 Diagram</p></figcaption></figure>

{% hint style="info" %}
The HYPERSIM<sup>®</sup> simulation option Set Initial Conditions must be checked for the automatic initialization to work properly.
{% endhint %}

## Mask parameters

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-1601b2bb9de66c0c16be2298db726f93e3153e46%2FEXST3.jpg?alt=media" alt=""><figcaption></figcaption></figure>

{% tabs %}
{% tab title="AVR" %}

| Parameter    | Description                                                                                                                                             |
| ------------ | ------------------------------------------------------------------------------------------------------------------------------------------------------- |
| **Tr**       | Regulator input filter time constant (s). This filter is not part of \[1] and has no typical values; it was added for flexibility. Set to 0 to disable. |
| **VImax**    | Maximum regulator input voltage (pu).                                                                                                                   |
| **VImin**    | Minimum regulator input voltage (pu).                                                                                                                   |
| **Tb**       | AVR lead-lag numerator time constant (s).                                                                                                               |
| **Tc**       | AVR lead-lag denominator time constant (s).                                                                                                             |
| **Ka**       | AVR filter gain (unitless).                                                                                                                             |
| **Ta**       | AVR filter time constant (s).                                                                                                                           |
| **VRmax**    | Maximum voltage regulator output (pu).                                                                                                                  |
| **VRmin**    | Minimum voltage regulator output (pu).                                                                                                                  |
| **Kj**       | Voltage regulator gain (unitless).                                                                                                                      |
| {% endtab %} |                                                                                                                                                         |

{% tab title="Exciter" %}

| Input      | Description                                                                |
| ---------- | -------------------------------------------------------------------------- |
| **EFDmax** | Maximum exciter output voltage (pu).                                       |
| **Kg**     | Feedback gain constant of the inner loop field regulator (unitless).       |
| **VGmax**  | Maximum inner loop voltage feedback (pu).                                  |
| **Kp**     | Potential circuit real part gain coefficient (unitless).                   |
| **Ki**     | Potential circuit imaginary part gain coefficient (unitless).              |
| **Kc**     | Rectifier loading factor proportional to commutating reactance (unitless). |
| **Xl**     | Reactance associated with potential source (pu).                           |
| **ThetaP** | Potential circuit phase angle (degrees).                                   |

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-948be2f32c56b442c73929b6824f7e0690486556%2Fjfx8415751582273222310.png?alt=media" alt=""><figcaption><p>Exciter diagram</p></figcaption></figure>
{% endtab %}

{% tab title="Initial values" %}

| Parameter | Description                                           |
| --------- | ----------------------------------------------------- |
| **Ifd0**  | Synchronous machine field current initial value (pu). |
| **Efd0**  | Exciter output voltage initial value (pu).            |

{% hint style="info" %}
Ifd0 and Efd0 can be set manually by entering numerical values, or automatically from load flow by referencing synchronous machine variables. For example, if the synchronous machine name is "SM1":

* Thermal or hydraulic machine: set Ifd0 to "=SM1.IfdInit" multiplied by Xad = Xd – Xl, and set Efd0 to "=SM1.EfdInit".
* pu standard or pu fundamental machine: set Ifd0 to "=SM1.IF\_Init" and Efd0 to "=SM1.EFD\_Init".
  {% endhint %}
  {% endtab %}
  {% endtabs %}

## Inputs

<table><thead><tr><th width="201.20001220703125">Input</th><th>Description</th></tr></thead><tbody><tr><td><strong>Voel</strong></td><td>Over-excitation limiter output.</td></tr><tr><td><strong>Vc1</strong></td><td>Signal proportional to compensated terminal voltage (see Load Compensator block). If the Load Compensator block is not used upstream of the exciter block, Vc1 equals Vt (main alternator terminal voltage).</td></tr><tr><td><strong>Vuel</strong></td><td>Under-excitation limiter output.</td></tr><tr><td><strong>Vref</strong></td><td>Voltage regulator reference voltage.</td></tr><tr><td><strong>Vs</strong></td><td>Output voltage of a Power System Stabilizer (PSS) [1].</td></tr><tr><td><strong>Id</strong></td><td>d-axis component of generator terminal current.</td></tr><tr><td><strong>Iq</strong></td><td>q-axis component of generator terminal current.</td></tr><tr><td><strong>Vd</strong></td><td>d-axis component of generator terminal voltage.</td></tr><tr><td><strong>Vq</strong></td><td>q-axis component of generator terminal voltage.</td></tr><tr><td><strong>Ifd</strong></td><td>Synchronous machine field current.</td></tr></tbody></table>

{% hint style="danger" %}
**Vuel** and **Voel** are normally inputs for this excitation system. You can choose fixed constant values directly in the mask by selecting the “internal” option.
{% endhint %}

If a Synch. Machine (Hydraulic or Thermal) from the Network Machines and Generators library is used, multiply the machine observable Ifd by the synchronous machine parameter Xad = Xd – Xl before applying it to the exciter input. This multiplication is not needed if a Synchronous Machine (pu Standard) or (pu Fundamental) is used.

## Outputs

<table><thead><tr><th width="202.79998779296875">Output</th><th>Description</th></tr></thead><tbody><tr><td><strong>Efd</strong></td><td>Exciter output voltage (pu).</td></tr></tbody></table>

The terminal current calculation is performed from Id and Iq as: $$I\_t =\sqrt{ I\_{d^2} + I\_{q^2}}$$

Similarly, the terminal voltage calculation is performed from Vd and Vq as: $$V\_t =\sqrt{ V\_{d^2} + V\_{q^2}}$$

## References

1. I. C. Report, "Excitation System Models for Power System Stability Studies," in IEEE Transactions on Power Apparatus and Systems, vol. PAS-100, no. 2, pp. 494-509, Feb. 1981.
2. PSS<sup>®</sup>E 34.2.0 Model Library. NY, USA: Siemens Industry, Inc., 2017.


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-exciters/ieee-exst3.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.