> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-exciters/ieee-rexsys.md).

# IEEE REXSYS

## Description

The **REXSYS** block, located in the **Control Exciters** library, is based on the IEEE Std. 412.5 type REXSYS excitation system model. It is a general-purpose rotating excitation system model that, with appropriate parameters and tuning, can represent a variety of exciters. The REXSYS component was developed in line with reference \[1].

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-cec7a8034bea5b18d68c3a37012e6227b2c23ea5%2Fimage%20(848).png?alt=media" alt=""><figcaption><p>REXSYS AVR diagram</p></figcaption></figure>

{% hint style="info" %}
The HYPERSIM<sup>®</sup> simulation option Set Initial Conditions must be checked for the automatic initialization to work properly.
{% endhint %}

## Mask parameters

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-af5f6eb0d2f098a64c141cd16251756438d265b0%2FREXSYS.jpg?alt=media" alt=""><figcaption></figcaption></figure>

{% tabs %}
{% tab title="AVR" %}

<table><thead><tr><th width="200.20001220703125">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Tr</strong></td><td>Regulator input filter time constant (s).</td></tr><tr><td><strong>Kvp</strong></td><td>Voltage regulator proportional gain (Kvp ≠ 0).</td></tr><tr><td><strong>Kvi</strong></td><td>Voltage regulator integral gain.</td></tr><tr><td><strong>VImax</strong></td><td>Voltage regulator input limit (pu).</td></tr><tr><td><strong>Ta</strong></td><td>Voltage regulator time constant (s).</td></tr><tr><td><strong>Tc1</strong></td><td>First stage lead-lag numerator time constant (s).</td></tr><tr><td>Tb1</td><td>First stage lead-lag denominator time constant (s).</td></tr><tr><td><strong>Tc2</strong></td><td>Second stage lead-lag numerator time constant (s).</td></tr><tr><td><strong>Tb2</strong></td><td>Second stage lead-lag denominator time constant (s).</td></tr><tr><td><strong>VRmax</strong></td><td>Maximum voltage regulator output (pu).</td></tr><tr><td><strong>VRmin</strong></td><td>Minimum voltage regulator output (pu).</td></tr><tr><td><strong>Kf</strong></td><td>Rate feedback gain.</td></tr><tr><td><strong>Tf</strong></td><td>Rate feedback time constant (s). If Tf &#x3C; 0.2, then Tf = 0.2.</td></tr><tr><td><strong>Tf1</strong></td><td>Feedback lead-lag numerator time constant (s).</td></tr><tr><td><strong>Tf2</strong></td><td>Feedback lead-lag denominator time constant (s).</td></tr><tr><td><strong>Fbf</strong></td><td>Rate feedback signal selector. Allowed values: VR, IFE, EFD.</td></tr></tbody></table>
{% endtab %}

{% tab title="FCR and  Exciter" %}

<table><thead><tr><th width="200.20001220703125">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Kip</strong></td><td>Field current regulator proportional gain.</td></tr><tr><td><strong>Kii</strong></td><td>Field current regulator integral gain.</td></tr><tr><td><strong>Tp</strong></td><td>Field current bridge time constant (s).</td></tr><tr><td><strong>VFmax</strong></td><td>Maximum exciter field current (pu).</td></tr><tr><td><strong>VFmin</strong></td><td>Minimum exciter field current (pu).</td></tr><tr><td><strong>Kh</strong></td><td>Field voltage controller feedback gain.</td></tr><tr><td><strong>Ke</strong></td><td>Exciter constant related to self-excited field.</td></tr><tr><td><strong>Te</strong></td><td>Exciter time constant (s).</td></tr><tr><td><strong>Kc</strong></td><td>Rectifier loading factor proportional to commutating reactance.</td></tr><tr><td><strong>Kd</strong></td><td>Exciter demagnetizing factor.</td></tr><tr><td><strong>Se2, Se1</strong></td><td>Exciter saturation factor at the corresponding Vex (pu).</td></tr><tr><td><strong>Ve2, Ve1</strong></td><td>Exciter voltage for the exciter saturation function (pu).<br>Ve1 > Ve2 > 0.</td></tr><tr><td><strong>F1imf</strong></td><td>Power supply limit factor.</td></tr></tbody></table>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-d1bf0aa001a1b791642231b6068eb415cf387fb6%2Fimage%20(849).png?alt=media" alt=""><figcaption><p>Exciter diagram</p></figcaption></figure>
{% endtab %}

{% tab title="Initial values" %}

<table><thead><tr><th width="200.199951171875">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Ifd0</strong></td><td>Synchronous machine field current initial value (pu).</td></tr><tr><td><strong>Efd0</strong></td><td>Exciter output voltage initial value (pu).</td></tr></tbody></table>

{% hint style="info" %}
Ifd0 and Efd0 can be set manually by entering a numerical value, or automatically from load flow calculations by referencing synchronous machine variables. For example, if the synchronous machine connected to the excitation system is named “SM1”:

* If a thermal machine or a hydraulic machine is used, Ifd0 shall be set as “=SM1.IfdInit” multiplied by the synchronous machine parameter Xad = Xd – Xl, and Efd0 shall be set as “=SM1.EfdInit”.
* If a pu standard or pu fundamental machine is used, Ifd0 shall be set as “=SM1.IF\_Init” and Efd0 shall be set as “=SM1.EFD\_Init”.
  {% endhint %}
  {% endtab %}
  {% endtabs %}

## Inputs

<table><thead><tr><th width="200.4000244140625">Input</th><th>Description</th></tr></thead><tbody><tr><td><strong>Voel</strong></td><td>Over-excitation limiter output (pu).</td></tr><tr><td><strong>Vc1</strong></td><td>Signal proportional to compensated terminal voltage. If a load compensator block is not used upstream from the exciter block, Vc1 equals Vt (main alternator terminal voltage) (pu).</td></tr><tr><td><strong>Vuel</strong></td><td>Under-excitation limiter output (pu).</td></tr><tr><td><strong>Vref</strong></td><td>Voltage regulator reference voltage (pu).</td></tr><tr><td><strong>Vs</strong></td><td>Output voltage of a Power System Stabilizer (PSS) (pu).</td></tr><tr><td><strong>Ifd</strong></td><td>Synchronous machine field current (pu).</td></tr><tr><td><strong>Vd</strong></td><td>d-axis component of generator terminal voltage (pu).</td></tr><tr><td><strong>Vq</strong></td><td>q-axis component of generator terminal voltage (pu).</td></tr></tbody></table>

{% hint style="danger" %}
**Vuel** and **Voel** are normally inputs for this excitation system. You can choose fixed constant values directly in the mask by selecting the “internal” option.
{% endhint %}

The observable field current **Ifd** from the synchronous machine in HYPERSIM must be multiplied by the machine’s Xad = Xd − Xl before it is provided to the exciter input.

## Outputs

<table><thead><tr><th width="201.20001220703125">Output</th><th>Description</th></tr></thead><tbody><tr><td><strong>Efd</strong></td><td>Exciter output voltage (pu).</td></tr></tbody></table>

The terminal voltage calculation is performed from Vd and Vq as follows: $$V\_t =\sqrt{ V\_{d^2} + V\_{q^2}}$$

## References

1. PSS<sup>®</sup>E 34.2.0 Model Library. NY, USA: Siemens Industry, Inc., 2017.


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-exciters/ieee-rexsys.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.