> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-exciters/ieee-st1a.md).

# IEEE ST1A

Description

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-26f17909273fb29f02568eaeab17ae5bba0e411b%2Fimage%20(852).png?alt=media" alt=""><figcaption></figcaption></figure>

The **ST1A** block, located in the **Control Exciters** library, is based on the IEEE Std. 412.5 type ST1A excitation system model. It represents a static excitation system where a controlled rectifier performs regulation and a transformer provides excitation.

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-37a11e6c4bf8e627b37d90cee94f24eed5714ae2%2Fimage%20(854).png?alt=media" alt=""><figcaption><p>ST1A diagram</p></figcaption></figure>

{% hint style="info" %}
The HYPERSIM<sup>®</sup> simulation option Set Initial Conditions must be checked for the automatic initialization to work properly.
{% endhint %}

## Mask parameters

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-7e1b79775a146601ba01f3e9546c9f97db99e8bd%2FST1A.jpg?alt=media" alt=""><figcaption></figcaption></figure>

{% tabs %}
{% tab title="AVR" %}

<table><thead><tr><th width="200">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Tr</strong></td><td>Regulator input filter time constant (s). This input filter is not part of the standard and no typical values are recommended; it was added for flexibility. This parameter can be set to 0 if the filter is not used.</td></tr><tr><td><strong>Tb, Tb1</strong></td><td>AVR lead-lag denominator time constants (s).</td></tr><tr><td><strong>Tc, Tc1</strong></td><td>AVR lead-lag numerator time constants (s).</td></tr><tr><td><strong>PSS input location</strong></td><td><p>Two options :</p><ul><li>Summation point at voltage error calculation</li><li>Summation point at voltage regulator output</li></ul></td></tr><tr><td><strong>Ka</strong></td><td>AVR filter gain.</td></tr><tr><td><strong>Ta</strong></td><td>AVR filter time constant (s).</td></tr><tr><td><strong>Kf</strong></td><td>Excitation control system stabilizer gain.</td></tr><tr><td><strong>Tf</strong></td><td>Excitation control system stabilizer time constant (s).</td></tr><tr><td><strong>Vamax</strong></td><td>Maximum regulator internal voltage (pu).</td></tr><tr><td><strong>Vamin</strong></td><td>Minimum regulator internal voltage (pu).</td></tr><tr><td><strong>Vrmax</strong></td><td>Maximum voltage regulator output (pu).</td></tr><tr><td><strong>Vrmin</strong></td><td>Minimum voltage regulator output (pu).</td></tr><tr><td><strong>VImax</strong></td><td>Maximum regulator input voltage (pu).</td></tr><tr><td><strong>VImin</strong></td><td>Minimum regulator input voltage (pu).</td></tr><tr><td><strong>UEL input location</strong></td><td><p>Three options :</p><ul><li>Summation point UEL (at voltage error)</li><li>HV gate 1</li><li>HV gate 2</li></ul></td></tr></tbody></table>
{% endtab %}

{% tab title="Exciter" %}

| Parameter | Description                                                     |
| --------- | --------------------------------------------------------------- |
| **KLR**   | Exciter output current limiter gain.                            |
| **Kc**    | Rectifier loading factor proportional to commutating reactance. |
| **ILR**   | Exciter output current limit reference (pu).                    |

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-8597e2af50352ff5af1db4ff67d4d9d6b851ff90%2Fimage%20(853).png?alt=media" alt=""><figcaption><p>Exciter diagram</p></figcaption></figure>
{% endtab %}

{% tab title="Initial values" %}

<table><thead><tr><th width="200">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Ifd0</strong></td><td>Synchronous machine field current initial value (pu).</td></tr><tr><td><strong>Efd0</strong></td><td>Exciter output voltage initial value (pu).</td></tr></tbody></table>

{% hint style="info" %}
The parameters Ifd0 and Efd0 can be set manually by entering a numerical value, or automatically based on load flow by referencing the synchronous machine variable. For instance, if the name of the synchronous machine is “SM1”:

* If a thermal machine or a hydraulic machine is used, Ifd0 shall be set as “=SM1.IfdInit” multiplied by the synchronous machine parameter Xad = Xd – Xl, and Efd0 shall be set as “=SM1.EfdInit”.
* If a pu standard or pu fundamental machine is used, Ifd0 shall be set as “=SM1.IF\_Init” and Efd0 shall be set as “=SM1.EFD\_Init”.
  {% endhint %}
  {% endtab %}
  {% endtabs %}

## Inputs

<table><thead><tr><th width="200">Input</th><th>Description</th></tr></thead><tbody><tr><td><strong>Voel</strong></td><td>Overexcitation limiter output (pu).</td></tr><tr><td><strong>Vc1</strong></td><td>Signal proportional to compensated terminal voltage (pu). If the Load Compensator block is not used upstream from the exciter block, connect Vc1 to Vt.</td></tr><tr><td><strong>Vt</strong></td><td>Machine terminal voltage (pu).</td></tr><tr><td><strong>Vuel</strong></td><td>Under-excitation limiter output (pu).</td></tr><tr><td><strong>Vref</strong></td><td>Voltage regulator reference voltage (pu).</td></tr><tr><td><strong>Vs</strong></td><td>Output voltage of a power system stabilizer (PSS) [(pu).</td></tr><tr><td><strong>Ifd</strong></td><td>Synchronous machine field current (pu).</td></tr></tbody></table>

{% hint style="danger" %}
**Vuel** and **Voel** are normally inputs for this excitation system. You can choose fixed constant values directly in the mask by selecting the “internal” option.
{% endhint %}

If a Synch. Machine (Hydraulic or Thermal) from the Network Machines and Generators library is used, the machine observable Ifd must be multiplied by the synchronous machine parameter Xad = Xd – Xl prior to its input to the exciter. This multiplication is not needed if a Synchronous Machine (pu Standard) or (pu Fundamental) is used.

## Outputs

<table><thead><tr><th width="200">Output</th><th>Description</th></tr></thead><tbody><tr><td><strong>Efd</strong></td><td>Exciter output voltage (pu).</td></tr></tbody></table>

## References

“IEEE Recommended Practice for Excitation System Models for Power System Models for Power System Stability Studies,” IEEE Standard 421.5-2005.


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-exciters/ieee-st1a.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.