> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-exciters/ieee-t2.md).

# IEEE T2

## Description

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-f88896fbaaf308b5a55e6f007be94e62c89a4654%2Fimage%20(789).png?alt=media" alt="" width="200"><figcaption></figcaption></figure>

The **IEEET2** block, located in the **Control Exciters** library, implements the IEEE Std. 412.5 type IIET2 excitation system specified in the IEEE committee report "Computer representation of excitation systems" \[1]\[2]. In this model, the stabilizing feedback source is proportional to the control element output.

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-0e070f2da47a109013a41c9a627f8f5369eb4de1%2Fimage%20(790).png?alt=media" alt="" width="563"><figcaption><p>IEEET2 diagram</p></figcaption></figure>

{% hint style="info" %}
The HYPERSIM<sup>®</sup> simulation option Set Initial Conditions must be checked for the automatic initialization to work properly.
{% endhint %}

## Mask parameters

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-f51c8a13e04e34784926db61477076c68c9c8066%2FIEEET2.jpg?alt=media" alt=""><figcaption></figcaption></figure>

{% tabs %}
{% tab title="AVR" %}

<table><thead><tr><th width="201">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Tr</strong></td><td>Regulator input filter time constant (s).</td></tr><tr><td><strong>Ka</strong></td><td>Voltage regulator gain.</td></tr><tr><td><strong>Ta</strong></td><td>Regulator time constant.</td></tr><tr><td><strong>Kf</strong></td><td>Excitation control system stabilizer gain.</td></tr><tr><td><strong>Tf1</strong></td><td>Excitation control system stabilizer time constant 1 (s) ;<br>Range: Tf1 >= 0.001s.</td></tr><tr><td><strong>Tf2</strong></td><td>Excitation control system stabilizer time constant 2 (s).</td></tr><tr><td><strong>VRmax</strong></td><td>Maximum voltage regulator output (pu).</td></tr><tr><td><strong>VRmin</strong></td><td>Minimum voltage regulator output (pu).</td></tr></tbody></table>
{% endtab %}

{% tab title="Exciter" %}

<table><thead><tr><th width="201">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Te</strong></td><td>Exciter time constant (s); Range: Te >= 0.04.</td></tr><tr><td><strong>Ke</strong></td><td>Exciter constant related to self-excited field.</td></tr><tr><td><strong>Se1</strong></td><td>Exciter saturation factor at the corresponding Vex (pu).</td></tr><tr><td><strong>Se2</strong></td><td>Exciter saturation factor at the corresponding Vex ( pu).</td></tr><tr><td><strong>Efd1</strong></td><td>Exciter voltage for the exciter saturation function (pu).</td></tr><tr><td><strong>Efd2</strong></td><td>Exciter voltage for the exciter saturation function (pu).</td></tr></tbody></table>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-1b4db0f0626c30b0b358c5506b8508a56064628d%2Fimage%20(791).png?alt=media" alt="" width="375"><figcaption><p>Exciter diagram</p></figcaption></figure>
{% endtab %}

{% tab title="Initial values" %}

<table><thead><tr><th width="200.20001220703125">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Efd0</strong></td><td>Exciter output voltage initial value (pu).</td></tr></tbody></table>

{% hint style="info" %}
You can set Efd0 manually by entering a numeric value, or automatically from load flow results by referencing the synchronous machine variable.

For a machine named "SM1": use "=SM1.EfdInit" with a thermal or hydraulic machine, and "=SM1.EFD\_Init" with a pu standard or pu fundamental machine.
{% endhint %}
{% endtab %}
{% endtabs %}

## Inputs

<table><thead><tr><th width="200.4000244140625">Input</th><th>Description</th></tr></thead><tbody><tr><td><strong>Vc1</strong></td><td>Signal proportional to compensated terminal voltage (refer to the load compensator block documentation). If the load compensator block is not used upstream from the exciter block, Vc1 equals Vt (pu).</td></tr><tr><td><strong>Vref</strong></td><td>Voltage regulator reference voltage (pu).</td></tr><tr><td><strong>Vs</strong></td><td>Combined PSS and possibly discontinuous control output after any limits or switching, summed with terminal voltage and reference signals. For example, Voel and Vuel should be added to this signal before connecting to the input (pu).</td></tr></tbody></table>

## Outputs

<table><thead><tr><th width="199.60003662109375">output</th><th>Description</th></tr></thead><tbody><tr><td><strong>Efd</strong></td><td>Exciter output voltage (pu).</td></tr></tbody></table>

## References

1. C. Report, "Computer representation of excitation systems," IEEE Transactions on Power Apparatus and Systems,\_pp. 1460-1464, June 1968
2. PSS<sup>®</sup>E 34.2.0 Model Library. NY, USA: Siemens Industry, Inc., 2017.


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-exciters/ieee-t2.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.