> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-governors/ieee-degov.md).

# IEEE DEGOV

## Description

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-b7cea54c1aa2fc5022b2f318208d003f92410ce8%2Fimage%20(776).png?alt=media" alt="" width="153"><figcaption></figcaption></figure>

The **IEEE DEGOV** block, located in the **Control Governors** library, is a Woodward diesel generator governor model that includes an electric actuator, a hydromechanical actuator, and the diesel engine. Its counterpart, DEGOV1, also includes a droop control for operation in droop mode. The DEGOV model follows the governor–turbine architecture described in references \[1–3].

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-e2d888360ac0ba83f180acc822c5cf8f3c6d77c6%2Fimage%20(777).png?alt=media" alt=""><figcaption><p>DEGOV block</p></figcaption></figure>

The input of the DEGOV block is the machine speed in pu (ω). The block internally computes the speed deviation Δω with a reference of 1 pu.

{% hint style="info" %}
The HYPERSIM<sup>®</sup> simulation option Set Initial Conditions must be checked for the automatic initialization to work properly.
{% endhint %}

## Mask parameters

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-c5b48cf137151d3850509cc857ed27147772ac66%2FDEGOV.jpg?alt=media" alt="" width="563"><figcaption></figcaption></figure>

{% tabs %}
{% tab title="DEGOV" %}

<table><thead><tr><th width="199.5999755859375">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>T1</strong></td><td>Electric control box time constant (s)</td></tr><tr><td><strong>T2</strong></td><td>Electric control box time constant (s)</td></tr><tr><td><strong>T3</strong></td><td>Electric control box time constant (s)</td></tr><tr><td><strong>T4</strong></td><td>Actuator time constant (s)</td></tr><tr><td><strong>T5</strong></td><td>Actuator time constant (s)</td></tr><tr><td><strong>T6</strong></td><td>Actuator time constant (s)</td></tr><tr><td><strong>K</strong></td><td>Actuator gain</td></tr><tr><td><strong>Tmax</strong></td><td>Actuator maximum limit (pu)</td></tr><tr><td><strong>Tmin</strong></td><td>Actuator minimum limit (pu)</td></tr><tr><td><strong>TD</strong></td><td>Engine time delay (s)</td></tr></tbody></table>
{% endtab %}

{% tab title="Initial value" %}

| Parameter | Description                          |
| --------- | ------------------------------------ |
| **Pm0**   | Initial mechanical power output (pu) |

{% hint style="info" %}
The initial power output can be set manually by entering a numerical value, or automatically from load-flow results by referencing a synchronous machine variable from the machine netlist.
{% endhint %}

For example, if the synchronous machine connected to the governor/turbine is named “SM1”, set Pm0 as “=SM1.Peo/SM1.BaseMVA” for a thermal or hydraulic machine, and as “=SM1.lfP/1e6/SM1.sBase” for a pu standard or a pu fundamental machine, where Peo and IfP are the initial power outputs of the machines, respectively.
{% endtab %}
{% endtabs %}

## Inputs

| input | Description        |
| ----- | ------------------ |
| **ω** | Machine speed (pu) |

## Outputs

| Output | Description                  |
| ------ | ---------------------------- |
| **Pm** | Mechanical power output (pu) |

## References

1. P. Kundur, Power System Stability and Control, New York:McGraw-Hill, 1994.
2. NEPLAN AG. Turbine-Governor Models, Standard Dynamic Turbine-Governor Systems in NEPLAN Power System Analysis Tool; NEPLAN: CH-8700 Küsnacht (ZH), Switzerland, 2013; p. 91.
3. PSS<sup>®</sup>E 34.2.0 Model Library. NY, USA: Siemens Industry, Inc., 2017.


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-governors/ieee-degov.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.