> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-governors/ieee-ieesgo.md).

# IEEE IEESGO

## Description

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-0ca417f8d109e45158ddea43dd038cfd8b988ebd%2Fimage%20(767).png?alt=media" alt="" width="173"><figcaption></figcaption></figure>

The **IEESGO** block, located in the **Control Governors** library, is a steam turbine governor model, improved in 1973 from the IEEE TGOV1 model. It implements governor droop with lead–lag compensation (K1, T1, T2, T3), main steam control valve dynamics and limits (T4, P<sub>MAX</sub>, P<sub>MIN</sub>), reheater control (K2, T5), and the IP–LP power contribution (K3, T6). Two turbine fractions (K2 and K3) represent different turbine stages.

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-1326f08013e46023f4fee2a1f16f49fdf14805c1%2Fimage%20(768).png?alt=media" alt=""><figcaption><p>IEESGO governor-turbine model</p></figcaption></figure>

{% hint style="info" %}
The HYPERSIM<sup>®</sup> simulation option Set Initial Conditions must be checked for the automatic initialization to work properly.
{% endhint %}

## Mask parameters

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-bde44e624c3d4361e4aec230282df11061dc6eed%2FIEEESGO.jpg?alt=media" alt=""><figcaption></figcaption></figure>

{% tabs %}
{% tab title="IEESGO" %}

<table><thead><tr><th width="200.4000244140625">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>K1</strong></td><td>Per-unit regulation. Default: 20.</td></tr><tr><td><strong>T1</strong></td><td>Controller lag (s) Default: 0.15.</td></tr><tr><td><strong>T2</strong></td><td>Controller lead compensation (s) Default: 0.</td></tr><tr><td><strong>T3</strong></td><td>Governor lag (s) Default: 0.13.</td></tr><tr><td><strong>P</strong><sub><strong>MAX</strong></sub></td><td>Upper power limit (pu) Default: 0.982.</td></tr><tr><td><strong>P</strong><sub><strong>MIN</strong></sub></td><td>Lower power limit (pu) Default: 0.</td></tr><tr><td><strong>T4</strong></td><td>Delay due to steam inlet volumes associated with the steam chest and inlet piping (s) Default: 0.22.</td></tr><tr><td><strong>K2</strong></td><td>Fraction Default: 0.747.</td></tr><tr><td><strong>T5</strong></td><td>Reheater delay including hot and cold leads (s) Default: 4.97.</td></tr><tr><td><strong>K3</strong></td><td>Fraction Default: 0.631.</td></tr><tr><td><strong>T6</strong></td><td>Delay due to IP–LP turbine, crossover pipes, and LP end hoods (s) Default: 0.2.</td></tr></tbody></table>
{% endtab %}

{% tab title="Initial values" %}

<table><thead><tr><th width="197.79998779296875">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Pm0</strong></td><td>Initial mechanical power output (pu).</td></tr></tbody></table>

{% hint style="info" %}
Can be set manually (numeric value) or automatically from load flow by referencing the connected synchronous machine variables.\
For a **machine defined as PV type** named SM1 :

* PmO = SM1.lfP/1e6/SM1.sBase+3\*SM1.Rs\*((sqrt(SM1.lfP^2+SM1.lfQ^2)/1e6/SM1.sBase)/sqrt(3)/SM1.lfVolt)^2

For a **machine defined as swing type** named SM1 :

* PmO = *BusName*.LF\_Pbus/SM1.sBase+3\*SM1.Rs\*((sqrt(SM1.lfP^2+SM1.lfQ^2)/1e6/SM1.sBase)/sqrt(3)/SM1.lfVolt)^2
  {% endhint %}
  {% endtab %}
  {% endtabs %}

## Inputs

| Input  | Description                      |
| ------ | -------------------------------- |
| **P0** | External control reference (pu). |
| **w**  | Machine actual speed (pu).       |

## Outputs

| Output | Description                   |
| ------ | ----------------------------- |
| **Pm** | Mechanical power output (pu). |

## References

\[1] P. Kundur, “Power System Stability and Control”, McGraw-Hill 1994

\[2] Standard Dynamic Turbine-Governor Systems in NEPLAN Power System Analysis Tool

\[3] PSSE Explore 34 Siemens software


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-governors/ieee-ieesgo.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.