> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-protection-relays/27-undervoltage.md).

# 27 - Undervoltage

## Description

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-a69ebcc2cd4dbc39e8dbb958443f1040f0d25b80%2Fimage%20(949).png?alt=media" alt="" width="150"><figcaption></figcaption></figure>

The **27 - Undervoltage** block, located in the **Control protection Relays** library, operates when the monitored voltage drops below configured thresholds. The relay provides five levels, each with a predefined under-voltage pickup and a tripping delay. It can use the minimum Phase–Neutral voltage or the minimum Phase–Phase voltage among the three phases and supports 50 Hz and 60 Hz systems.

When the line or phase voltage falls below a selected level, the relay picks up and starts its timer. If the voltage remains below the threshold longer than the associated delay, the relay asserts. If the voltage recovers before the delay expires, the timer resets and restarts only when the voltage again falls below the threshold.

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-3534285646aa496c2faf282430d05aa91c3162a5%2Fimage%20(951).png?alt=media" alt="" width="305"><figcaption></figcaption></figure>

For example, with the default settings, Level 1 is 0.8 pu with a 1 s delay. If the input voltage stays below 0.8 pu for more than 1 s, the relay asserts; if it is below 0.8 pu for less than 1 s, the timer resets. All voltage levels and delay times are tunable.

## Mask parameters

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-8df26be52a1e41acd9a28f2c409383f191e6d01b%2Fimage%20(950).png?alt=media" alt="" width="563"><figcaption></figcaption></figure>

<table><thead><tr><th width="239.60003662109375">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Frequency</strong></td><td>Frequency of the measured current signals. Supported values: 50 Hz or 60 Hz. Sample value: 60.</td></tr><tr><td><strong>Ubase</strong></td><td>Base voltage (L–L) at the measurement location (V). Sample value: 500000.</td></tr><tr><td><strong>Operating Quantity</strong></td><td>Operating quantity selection: minimum Phase–Neutral Voltage or minimum Phase–Phase Voltage among the three phases. Sample value: Phase–Neutral Voltage.</td></tr><tr><td><strong>Level 1</strong></td><td>Under-voltage level 1 (pu). Sample value: 0.8.</td></tr><tr><td><strong>Level 2</strong></td><td>Under-voltage level 2 (pu). Sample value: 0.7.</td></tr><tr><td><strong>Level 3</strong></td><td>Under-voltage level 3 (pu). Sample value: 0.6.</td></tr><tr><td><strong>Level 4</strong></td><td>Under-voltage level 4 (pu). Sample value: 0.5.</td></tr><tr><td><strong>Level 5</strong></td><td>Under-voltage level 5 (pu). Sample value: 0.4.</td></tr><tr><td><strong>Time 1</strong></td><td>Time delay associated with Level 1 (s). Sample value: 1.0.</td></tr><tr><td><strong>Time 2</strong></td><td>Time delay associated with Level 2 (s). Sample value: 0.5.</td></tr><tr><td><strong>Time 3</strong></td><td>Time delay associated with Level 3 (s). Sample value: 0.4.</td></tr><tr><td><strong>Time 4</strong></td><td>Time delay associated with Level 4 (s). Sample value: 0.3.</td></tr><tr><td><strong>Time 5</strong></td><td>Time delay associated with Level 5 (s). Sample value: 0.2.</td></tr></tbody></table>

## Inputs

<table><thead><tr><th width="241.20001220703125">Input</th><th>Description</th></tr></thead><tbody><tr><td><strong>Vabc</strong></td><td>Three-phase voltage input [Va, Vb, Vc]. Unit: V.</td></tr><tr><td><strong>Reset</strong></td><td>Binary reset input. Resets the relay when set to 1.</td></tr></tbody></table>

## Outputs

<table><thead><tr><th width="240.39996337890625">Output</th><th>Description</th></tr></thead><tbody><tr><td><strong>Q</strong></td><td>Binary output. Default is 0; becomes 1 when an under-voltage condition is detected.</td></tr><tr><td><strong>Q_n</strong></td><td>Complementary value of Q.</td></tr></tbody></table>


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-protection-relays/27-undervoltage.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.