> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-protection-relays/27-undervoltage-1-ph.md).

# 27 - Undervoltage 1-ph

## Description

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-a69ebcc2cd4dbc39e8dbb958443f1040f0d25b80%2Fimage%20(949).png?alt=media" alt="" width="150"><figcaption></figcaption></figure>

The **27 - Undervoltage 1-ph** block, located in the **Control Protection Relays** library, operates when the monitored voltage falls below configured thresholds. It provides five threshold levels, each with an associated trip delay. The operating quantity can be the RMS phase voltage or the positive, negative, or zero sequence of a three-phase voltage signal, expressed in per unit or volts. If the voltage remains below a level longer than its delay, the relay trips; if the voltage recovers before the delay expires, the timer resets.

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-3534285646aa496c2faf282430d05aa91c3162a5%2Fimage%20(951).png?alt=media" alt="" width="305"><figcaption></figcaption></figure>

All voltage levels and delay times are configurable.

## Mask parameters

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-8df26be52a1e41acd9a28f2c409383f191e6d01b%2Fimage%20(950).png?alt=media" alt="" width="563"><figcaption></figcaption></figure>

<table><thead><tr><th width="219.60003662109375">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Level 1</strong></td><td>Undervoltage level 1 (pu or V). Sample value: 0.8.</td></tr><tr><td><strong>Level 2</strong></td><td>Undervoltage level 2 (pu or V). Sample value: 0.7.</td></tr><tr><td><strong>Level 3</strong></td><td>Undervoltage level 3 (pu or V). Sample value: 0.6.</td></tr><tr><td><strong>Level 4</strong></td><td>Undervoltage level 4 (pu or V). Sample value: 0.5.</td></tr><tr><td><strong>Level 5</strong></td><td>Undervoltage level 5 (pu or V). Sample value: 0.4.</td></tr><tr><td><strong>Time 1</strong></td><td>Time delay associated with level 1 (s). Sample value: 1.0.</td></tr><tr><td><strong>Time 2</strong></td><td>Time delay associated with level 2 (s). Sample value: 0.5.</td></tr><tr><td><strong>Time 3</strong></td><td>Time delay associated with level 3 (s). Sample value: 0.4.</td></tr><tr><td><strong>Time 4</strong></td><td>Time delay associated with level 4 (s). Sample value: 0.3.</td></tr><tr><td><strong>Time 5</strong></td><td>Time delay associated with level 5 (s). Sample value: 0.2.</td></tr></tbody></table>

## Inputs

<table><thead><tr><th width="239.5999755859375">Input</th><th>Description</th></tr></thead><tbody><tr><td><strong>V</strong></td><td>A single dimensional signal, it should be the RMS value of phase voltage, or the positive, negative or zero sequence of a three-phase voltage signals (pu or V).</td></tr></tbody></table>

## Outputs

<table><thead><tr><th width="240.4000244140625">Output</th><th>Description</th></tr></thead><tbody><tr><td><strong>Trip</strong></td><td>The output of under-voltage relay (binary). By default it is 0, if an under-voltage scenario is detected, it becomes 1</td></tr></tbody></table>


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-protection-relays/27-undervoltage-1-ph.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.