> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-protection-relays/49m-thermal-overload-protection.md).

# 49M - Thermal Overload Protection

## Description

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-c3e54e136143df69b52cfba239bc1e15c0d2325d%2Fimage%20(954).png?alt=media" alt="" width="194"><figcaption></figcaption></figure>

The **49M - Thermal Overload Protection** block, located in the **Control Protection Relays** library, models a thermal overload protection function for motors. It protects motors from overheating by modeling thermal behavior based on the measured load current, and it disconnects the motor when the thermal content reaches the configured pickup thermal loading value \[1].

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-32ef0b7b44e62d9dda7696765905f3756a0efe69%2Fimage%20(955).png?alt=media" alt="" width="563"><figcaption><p>the block diagram of the 49M relay</p></figcaption></figure>

**Max Current Calculator** selects the highest measured true RMS phase current and reports it to Thermal level calculator.

The **motor’s full-load current (FLC)** is specified by the manufacturer based on an ambient temperature of 40 °C. If the motor operates in a higher ambient temperature, its windings may experience excessive heating—even when operating at or below the rated load—similar to the effects of overload at normal ambient conditions. Therefore, the motor’s rating must be derated for operation in elevated ambient temperatures. Conversely, when the ambient temperature is significantly lower than the standard 40 °C, the motor can tolerate a slight overload.\
For thermal analysis, FLC values should be scaled to account for different ambient temperatures. These adjusted values are called the internal FLC.

<details>

<summary>Internal FLC is calculated based on the ambient temperature table</summary>

| Ambient temperature Tamb                   | Internal/calculated FLC              |
| ------------------------------------------ | ------------------------------------ |
| < 20 <sup>o</sup>C                         | FLC\*1.09                            |
| >= 20 <sup>o</sup>C and < 40 <sup>o</sup>C | FLC\*(1.18-T<sub>amb</sub>\*0.09/20) |
| = 40 <sup>o</sup>C                         | FLC                                  |
| > 40 <sup>o</sup>C and <= 65 <sup>o</sup>C | FLC\*(1-\[(T<sub>amb</sub>-40)/100]) |
| > 65 <sup>o</sup>C                         | FLC\*0.75                            |

</details>

The **thermal level calculator** module determines the motor’s thermal load using the maximum phase true RMS current and the negative-sequence current. Motor heating is primarily governed by the square of the load current; however, when the phase currents are unbalanced, the negative-sequence component contributes additional heating. By incorporating both current components into the protection logic, the system prevents abnormal motor heating.

$$
\theta\_B = \left\[ \left( \frac{I}{k \times I\_r} \right)^2 + K\_2 \times \left( \frac{I\_2}{k \times I\_r} \right)^2 \right] \times \left( 1 - e^{-\frac{t}{\tau}} \right) \times p%
$$

$$
\theta\_A = \left\[ \left( \frac{I}{k \times I\_r} \right)^2 + K\_2 \times \left( \frac{I\_2}{k \times I\_r} \right)^2 \right] \times \left( 1 - e^{-\frac{t}{\tau}} \right) \times 100%
$$

where,\
\&#xNAN;*I* = True RMS value of measured max of phase currents,

*I*<sub>*r*</sub> = FLC or Internal FLC,

*I*<sub>*2*</sub> = measured negative sequence current,

*k* = set value of Overload factor,

*K*<sub>*2*</sub> = set value of Negative seq factor,

*p* = set value of Weighting factor,

*τ* = time constant, in order to accurately calculate the motor thermal condition, different time constants are used depending on the motor running conditions (start, normal and stop).

<details>

<summary>Time constant in use</summary>

| Time constant in use (s) | Phase current (pu)                         |
| ------------------------ | ------------------------------------------ |
| **Time constant normal** | $$0.12 \times I\_r < I < 2.5 \times I\_r$$ |
| **Time constant start**  | $$I > 2.5 \times I\_r$$                    |
| **Time constant stop**   | $$I < 0.12 \times I\_r$$                   |

{% hint style="info" %}
Only one time constant is valid at a time.
{% endhint %}

</details>

{% hint style="info" %}
The equation θ<sub>B</sub> is used when the values of all the phase currents are below the overload limit $$k \times I\_r$$The equation θ<sub>A</sub> is used when the value of any one of the phase currents exceeds the overload limit.\
During overload, θ<sub>B</sub> is calculated in the background. When overload ends, the thermal level transitions linearly from θ<sub>A</sub> to θ<sub>B</sub> at 1.66% per second.
{% endhint %}

The **Alarm and Tripping Logic** module activates the TRIP output when the thermal level exceeds the set value of the thermal value pickup level setting. Similarly, when thermal level exceeds the set value of the Alarm thermal value setting, the ALARM output is activated.

The TRIP and ALARM outputs reset when the value of the thermal content drops below set thermal pickup level and alarm pickup level respectively.

## Mask parameters

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-105154e52f07eb3a23b634be735d78c12415974b%2Fimage%20(956).png?alt=media" alt="" width="545"><figcaption></figcaption></figure>

<table><thead><tr><th width="217.20001220703125">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Enable</strong></td><td>Operation On/Off. Variable: operation_onoff_param = {0, 1}.</td></tr><tr><td><strong>Full load current</strong></td><td>Full load current at 40 °C (pu) full_load_current_param = [0, 100].</td></tr><tr><td><strong>Overload factor</strong></td><td>Overload factor overload_factor_param = [1, 10].</td></tr><tr><td><strong>Weighting factor</strong></td><td>Weighting factor p (%). weighting_factor_param = [10, 100].</td></tr><tr><td><strong>Negative Seq factor</strong></td><td>Heating effect factor for negative-sequence current negative_seq__factor_param = [0, 50].</td></tr><tr><td><strong>Env temperature mode</strong></td><td>Mode for ambient temperature:<br>FLC only — no internal FLC is calculated, FLC specified at 40<sup>o</sup>C is used<br>Use input — Calculates internal FLC using the input temperature</td></tr><tr><td><strong>Thermal pickup level</strong></td><td>Thermal level above which the function trips (%) thermal_pickup_level_param = [5, 100].</td></tr><tr><td><strong>Alarm level</strong></td><td>Thermal level above which the function asserts an alarm (%). thermal_alarm_level_param = [5, 100].</td></tr><tr><td><strong>Initial thermal level</strong></td><td>Initial thermal level of the motor (%) initial_thermal_level_param = [0, 100].</td></tr><tr><td><strong>Time constant start</strong></td><td>Motor time constant during motor start (s) tau_start_param = [0, 1e6].</td></tr><tr><td><strong>Time constant normal</strong></td><td>Motor time constant during normal operation (s) tau_normal_param = [0, 1e6].</td></tr><tr><td><strong>Time constant stop</strong></td><td>Motor time constant during motor standstill (s) tau_stop_param = [0, 1e6].</td></tr></tbody></table>

## Inputs

<table><thead><tr><th width="219.60003662109375">Input</th><th>Description</th></tr></thead><tbody><tr><td><strong>Iabc</strong></td><td>Three-element per-unit true RMS three-phase currents in the order Ia, Ib, Ic.</td></tr><tr><td><strong>I2</strong></td><td>Magnitude of per-unit negative-sequence current.</td></tr><tr><td><strong>Block</strong></td><td>High level blocks the Trip and Alarm outputs.</td></tr><tr><td><strong>Amb_Tmp</strong></td><td>Ambient temperature used for internal FLC calculation when Env temperature mode is set to Use input.</td></tr></tbody></table>

## Outputs

<table><thead><tr><th width="220.4000244140625">Output</th><th>Description</th></tr></thead><tbody><tr><td><strong>Trip</strong></td><td>Thermal trip.<br>1 when the thermal level exceeds the Thermal pickup level; otherwise 0.</td></tr><tr><td><strong>Alarm</strong></td><td>Thermal alarm.<br>1 when the thermal level exceeds the Alarm level; otherwise 0.</td></tr><tr><td><strong>m</strong></td><td>Calculated thermal loading of the motor (%).</td></tr></tbody></table>

## References

1. REM620 series IEC 2.0 FP1, Technical Manual - ABB
2. REM620 IEC 2.0 FP1, Motor Protection and Control, Product Guide - ABB


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-protection-relays/49m-thermal-overload-protection.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.