> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-protection-relays/50-51-67-directional-oc.md).

# 50/51/67 - Directional OC

## Description

The **50/51/67 - Directional OC** block, located in the **Control Protection Relays** library, trips only when the current magnitude exceeds the configured threshold (50-51) and the current is in the specified direction (67). Direction can be forward or reverse, depending on the fault type and the directional element in service.

This page focuses on the 67 element (directional function) of the 50-51-67 model (for details on the 50-51 see [50/51 - Overcurrent Relay ](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-protection-relays/50-51-overcurrent.md)documentation).

The 67 element determines fault direction using phase-angle comparison between an operating quantity and a polarizing quantity. The operating quantity is the fault current. The polarizing quantity depends on the element:

* 67P (Phase directional): operating quantity is phase current; polarizing quantity is line-to-line voltage.
* 67N (Neutral directional): operating quantity is zero-sequence current; polarizing quantity is zero-sequence voltage (voltage polarization), ground current (current polarization), or both (dual polarization).

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-3e669b76b59bf91e1c4fa0d5b6d4a5df2cd4977c%2Fimage%20(569).png?alt=media" alt=""><figcaption><p>Concept of how the 50/51/67 relay operates</p></figcaption></figure>

The direction discrimination principle is based on phase angle comparison between a set of phasors, one of which is used as a reference. The model applies an **Element Characteristic Angle** (ECA), also known as **Relay Characteristic Angle** (RCA), to shift phasors and define forward and reverse operating regions. The directional element can issue a trip or provide a blocking signal to the overcurrent function.

### Directional elements 67P

The operating quantity is phase current and the polarizing quantity is line-to-line voltage. During faults, phase-to-neutral voltages may collapse, so line-to-line voltages are used as the reference and shifted by the user-defined ECA.

The phase-angle difference between operating and polarizing quantities is compared to 90 degrees to determine forward (trip) or reverse (block) direction. If a phase-to-phase voltage falls below 0.1 pu, the relay uses memorized voltage from three cycles earlier for direction determination.

The “Block after voltage memory expiration” setting controls whether 67P blocks phase overcurrent operation when voltage memory expires. If the phase current exceeds 0.05 pu, the 67P output is 1 for forward and 0 for reverse. Forward is used for tripping and reverse for blocking \[1].

### Directional elements 67N

The operating quantity is the zero-sequence current $$I\_0 = \frac{1}{3} \times I\_N = \frac{1}{3} \times (I\_A+ I\_B+ I\_C)$$.\
A positive-sequence restraint is applied: $$I\_{op} = 3 \times(I\_0 − K\times I\_1)$$, with K recommended as 1/16 but configurable \[2]. Based on the polarizing quantity, polarization modes are:

* Voltage polarization: polarizing quantity $$V\_{pol}=V\_0 =\frac{ 1}{3} \times V\_N =\frac{ 1}{3} \times (V\_A + V\_B + V\_C).$$
* Current polarization: polarizing quantity is ground current $$I\_{pol}=I\_G$$ (from a ground CT).
* Dual polarization: both quantities are used.

ECA is used with voltage polarization. The user sets pickup currents and forward/reverse limit angles for direction discrimination. The phase-angle difference between operating and polarizing quantities is compared with the configured Forward Limit Angle and Reverse Limit Angle to determine direction. The 67N element provides two direction outputs (forward and reverse), each 0 or 1; non-operation zones exist where both are 0.

In dual polarization, forward has priority if both forward and reverse evaluate to true. The neutral directional output is a tripping signal for the neutral overcurrent element; the user chooses whether trip control uses the forward or reverse direction. The overcurrent relay trips when the neutral fault current exceeds its threshold (50-51N) and the selected direction is met \[3].

The relay therefore operates (trips) whenever the monitored current exceeds the set threshold and is in the desired direction, for both phase and neutral faults.

<details>

<summary>The different directional elements in 67</summary>

**Relay 67P**

| Polarization mode | Operating Quantity | Polarizing Quantity  |
| ----------------- | ------------------ | -------------------- |
| Voltage           | I<sub>A</sub>      | V<sub>BC</sub> ∠ ECA |
| Voltage           | I<sub>B</sub>      | V<sub>CA</sub> ∠ ECA |
| Voltage           | I<sub>C</sub>      | V<sub>BA</sub> ∠ ECA |

One output 1: FWD 0: REV

**Relay 67N**

| Polarization mode | Operating Quantity                   | Polarizing Quantity             |
| ----------------- | ------------------------------------ | ------------------------------- |
| Voltage           | I<sub>0</sub> \<ECA                  | -V<sub>0</sub>                  |
| Current           | I<sub>0</sub>                        | I<sub>G</sub>                   |
| Dual              | I<sub>0</sub> ∠ ECA or I<sub>0</sub> | -V<sub>0</sub> or I<sub>G</sub> |

Two outputs: 0 or 1: FWD ; 0 or 1: REV

</details>

## Mask parameters

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-6536eb006e600f006e0f95fde2601fe2a7aa474c%2F505167.jpg?alt=media" alt=""><figcaption></figcaption></figure>

{% tabs %}
{% tab title="General parameters" %}

| Parameter        | Description                                                                                |
| ---------------- | ------------------------------------------------------------------------------------------ |
| **Frequency**    | The frequency of the measured current signals. Unit: Hz. Variable: Freq\_param = {50, 60}. |
| **Base current** | Base value for current. Unit: A. Variable: Ibase\_param = \[1, 1e5].                       |
| **Base voltage** | Base value for voltage. Unit: V. Variable: Vbase\_param = \[1, 1e8].                       |
| {% endtab %}     |                                                                                            |

{% tab title="Phase overcurent" %}

<table><thead><tr><th width="220.199951171875">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Pickup current 50P</strong></td><td>50P pickup current (pu) pickup50P_param = [0, 30].</td></tr><tr><td><strong>Time delay 50P</strong></td><td>50P time delay (s) delay50P_param = [0, 600].</td></tr><tr><td><strong>Pickup current 51P</strong></td><td>51P pickup current (pu) Ipck_51P_param = [0, 30].</td></tr><tr><td><strong>Time Dial</strong></td><td>Time dial multiplier for 51P TD51P_param = [0, 600].</td></tr><tr><td><strong>Curve types (51P)</strong></td><td>IEC or US inverse-time curve selection.<br>U1: U.S. Moderately Inverse; U2: U.S. Inverse ; U3: U.S. Very Inverse ; U4: U.S. Extremely Inverse ; U5: U.S. Short-time Inverse<br>C1: IEC Class A Standard Inverse ; C2: IEC Class B Very Inverse ; C3: IEC Class C Extremely Inverse ; C4: IEC Long-time Inverse ; C5: IEC Short-time Inverse</td></tr><tr><td><strong>Use custom curves 51P</strong></td><td>Enable custom curve instead of standardized curve for 51P. cust51P_param = {0, 1}.</td></tr><tr><td><strong>Level 1, 51P</strong></td><td>51P Level 1 pickup current (pu) level1_51_param = [0, 30].</td></tr><tr><td><strong>Level 2, 51P</strong></td><td>51P Level 2 pickup current (pu) level2_51_param = [0, 30].</td></tr><tr><td><strong>Level 3, 51P</strong></td><td>51P Level 3 pickup current (pu) level3_51_param = [0, 30].</td></tr><tr><td><strong>Level 4, 51P</strong></td><td>51P Level 4 pickup current (pu) level4_51_param = [0, 30].</td></tr><tr><td><strong>Level 5, 51P</strong></td><td>51P Level 5 pickup current (pu) level5_51_param = [0, 30].</td></tr><tr><td><strong>Time for level 1, 51P</strong></td><td>51P Level 1 time delay (s) time1_51_param = [0, 600].</td></tr><tr><td><strong>Time for level 2, 51P</strong></td><td>51P Level 2 time delay (s) time2_51_param = [0, 600].</td></tr><tr><td><strong>Time for level 3, 51P</strong></td><td>51P Level 3 time delay (s) time3_51_param = [0, 600].</td></tr><tr><td><strong>Time for level 4, 51P</strong></td><td>51P Level 4 time delay (s) time4_51_param = [0, 600].</td></tr><tr><td><strong>Time for level 5, 51P</strong></td><td>51P Level 5 time delay (s) time5_51_param = [0, 600].</td></tr></tbody></table>
{% endtab %}

{% tab title="Neutral overcurrent" %}

<table><thead><tr><th width="240.20001220703125">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Enable neutral overcurrent</strong></td><td>Enable 50N/51N elements</td></tr><tr><td><strong>Pickup current 50N</strong></td><td>50N pickup current (pu) pickup50N_param = [0, 30].</td></tr><tr><td><strong>Time delay 50N</strong></td><td>50N time delay (s) delay50N_param = [0, 600].</td></tr><tr><td><strong>Pickup current 51N</strong></td><td>51N pickup current (pu) Ipck_51N_param = [0, 30].</td></tr><tr><td><strong>Time Dial</strong></td><td>Time dial multiplier for 51N TD51N_param = [0, 600].</td></tr><tr><td><strong>Curve types (51N)</strong></td><td><p>IEC or US inverse-time curve selection.<br>U1: U.S. Moderately Inverse ; U2: U.S. Inverse - U3: U.S. Very Inverse ; U4: U.S. Extremely Inverse ; U5: U.S. Short-time Inverse</p><p>C1: IEC Class A Standard Inverse ; C2: IEC Class B Very Inverse ; C3: IEC Class C Extremely Inverse ; C4: IEC Long-time Inverse ; C5: IEC Short-time Inverse</p></td></tr><tr><td><strong>Use custom curves 51N</strong></td><td>Enable custom curve instead of standardized curve for 51N</td></tr><tr><td><strong>Level 1, 51N</strong></td><td>51N Level 1 pickup current (pu) level1_neutral_param = [0, 30].</td></tr><tr><td><strong>Level 2, 51N</strong></td><td>51N Level 2 pickup current (pu) level2_neutral_param = [0, 30].</td></tr><tr><td><strong>Level 3, 51N</strong></td><td>51N Level 3 pickup current (pu) level3_neutral_param = [0, 30].</td></tr><tr><td><strong>Level 4, 51N</strong></td><td>51N Level 4 pickup current (pu) llevel4_neutral_param = [0, 30].</td></tr><tr><td><strong>Level 5, 51N</strong></td><td>51N Level 5 pickup current (pu) level5_neutral_param = [0, 30].</td></tr><tr><td><strong>Time for level 1, 51N</strong></td><td>51N Level 1 time delay (s) time1_neutral_param = [0, 600].</td></tr><tr><td><strong>Time for level 2, 51N</strong></td><td>51N Level 2 time delay (s) time2_neutral_param = [0, 600].</td></tr><tr><td><strong>Time for level 3, 51N</strong></td><td>51N Level 3 time delay (s) time3_neutral_param = [0, 600].</td></tr><tr><td><strong>Time for level 4, 51N</strong></td><td>51N Level 4 time delay (s) time4_neutral_param = [0, 600].</td></tr><tr><td><strong>Time for level 5, 51N</strong></td><td>51N Level 5 time delay (s) time5_neutral_param = [0, 600].</td></tr></tbody></table>
{% endtab %}

{% tab title="Directional overcurrent" %}

<table><thead><tr><th width="220.199951171875">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Enable phase directional 67P</strong></td><td>Enable use of 67P for phase overcurrent control.</td></tr><tr><td><strong>ECA (67P)</strong></td><td>ECA angle for 67P (deg) ECA_67P_param = [0, 359].</td></tr><tr><td><strong>Blocking signal when voltage memory expires</strong></td><td>Enable sending a blocking signal when 67P voltage memory expires.</td></tr><tr><td><strong>Enable neutral directional 67N</strong></td><td>Enable use of 67N for neutral overcurrent control.</td></tr><tr><td><strong>Choose directional element for tripping</strong></td><td>Select the tripping direction for neutral overcurrent control.<br>1: Forward, 2: Reverse.</td></tr><tr><td><strong>Positive sequence restraint factor (K)</strong></td><td>Factor K used in I<sub>op</sub> = 3·(I<sub>0</sub> − K·I<sub>1</sub>) for 67N K_param = [0, 0.0625].</td></tr><tr><td><strong>ECA (67N)</strong></td><td>ECA angle for 67N (deg) ECA_67N_param = [-90, 90].</td></tr><tr><td><strong>Polarization mode</strong></td><td>67N polarization mode Pol_Mode_param = {1, 2, 3}<br>1 Current, 2: Dual, 3: Voltage.</td></tr><tr><td><strong>Enable ground calculation (current polarization)</strong></td><td>Enable ground current and voltage calculations used by current polarization EnableGround_param = {0, 1}.</td></tr><tr><td><strong>Forward direction pickup current</strong></td><td>Pickup current for forward directional discrimination (pu) I_FWD_PKP_param = [0.002, 3].</td></tr><tr><td><strong>Reverse direction pickup current</strong></td><td>Pickup current for reverse directional discrimination (pu) I_REV_PKP_param = [0.002, 3].</td></tr><tr><td><strong>Forward direction limit angle</strong></td><td>Limit angle for forward directional discrimination (deg) FWD_LIM_ANG_param = [40, 90].</td></tr><tr><td><strong>Reverse direction limit angle</strong></td><td>Limit angle for reverse directional discrimination (deg) REV_LIM_ANG_param = [40, 90].</td></tr></tbody></table>
{% endtab %}
{% endtabs %}

## Inputs

<table><thead><tr><th width="219.5999755859375">Input</th><th>Description</th></tr></thead><tbody><tr><td><strong>I</strong><sub><strong>abc</strong></sub></td><td>Three-phase currents.</td></tr><tr><td><strong>V</strong><sub><strong>abc</strong></sub></td><td>Three-phase voltages.</td></tr><tr><td><strong>I</strong><sub><strong>G</strong></sub></td><td>Ground current from the ground CT.</td></tr><tr><td><strong>V</strong><sub><strong>G</strong></sub></td><td>Ground voltage from the ground VT.</td></tr><tr><td><strong>Reset</strong></td><td>Relay reset signal (the relay resets when this signal becomes 1).</td></tr></tbody></table>

## Outputs

<table><thead><tr><th width="218.800048828125">Output</th><th>Description</th></tr></thead><tbody><tr><td><strong>Q</strong></td><td>Directional overcurrent relay output. Default 0; becomes 1 when an overcurrent condition is detected.</td></tr><tr><td><strong>Q_h</strong></td><td>Complementary value of Q.</td></tr><tr><td><strong>M</strong></td><td><p><strong>S_50P(A,B,C)</strong>: Output of three-phase overcurrent 50P.</p><p><strong>S_50N</strong>: Output of neutral overcurrent 50N.</p><p><strong>S_51P(A,B,C)</strong>: Output of three-phase inverse overcurrent 51P.</p><p><strong>S_51N</strong>: Output of neutral inverse overcurrent 51N.</p><p><strong>S_67P(A,B,C)</strong>: Output of three-phase directional overcurrent 67P.</p><p><strong>S_67N</strong>: Output of neutral directional overcurrent 67N.</p></td></tr></tbody></table>

## References

\[1] GE Industrial Systems, “D60 Line Distance Relay: UR Series Instruction Manual”, *Section 5.5.7.e: Phase Directional Overcurrent,*(2009 GE Multilin)

\[2] Bogdan Kasztenny, Dave Sharples, Bruce Campbell, Marzio Pozzuoli, “Fast Ground Directional Overcurrent Protection: Limitations and Solutions”, *Page 16,*(2000 GE Grid Solutions)

\[3] GE Industrial Systems, “D60 Line Distance Relay: UR Series Instruction Manual”, *Section 5.5.8.d: Neutral Directional Overcurrent,*(2009 GE Multilin)


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-protection-relays/50-51-67-directional-oc.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.