> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-protection-relays/51-inverse-overcurrent-1-ph.md).

# 51 - Inverse Overcurrent 1-ph

## Description

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-d07f77e8b63b58917ebac6e628fe6c6339c9db6f%2Fimage%20(568).png?alt=media" alt="" width="278"><figcaption></figcaption></figure>

The **51 - Inverse Overcurrent 1-ph** block, located in the **Control Protection Relays** library, implements inverse-time overcurrent protection which operating quantity can be the RMS of phase current, ground current, or symmetrical components. The element trips when current exceeds the pickup level for the corresponding time delay and resets when current drops below the pickup. Reset can be instantaneous or timed.

Trip time can be determined in two ways:

* Inverse-time curves using IEC or US standards, or user-defined curve coefficients.
* A custom curve defined by five pickup/time data points with linear interpolation between points.

If the input current is above the pickup level and custom curves are not used, the relay's tripping time is calculated based on the following equation:

$$
T\_{Trip} = TD \left( \frac{A}{M^{P} - 1} + B \right) + K
$$

The reset time of the relay can be calculated based on this equation in an inverse curve:

$$
T\_{Reset}= TD \left( \frac{T\_r}{1 - M^{Q}} \right),
M = \frac{I}{I\_{pickup}}
$$

where TD is the time dial multiplier. A, B, P, K, Tr, and Q define the curve.

US coefficients follow IEEE C37.112-2018 (values based on SEL relays) and IEC coefficients follow IEC 60255 for inverse-time overcurrent relays

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-c03316cff19c4ef65a18b7e61e5593f91f752978%2Fimage%20(571).png?alt=media" alt="" width="563"><figcaption></figcaption></figure>

<details>

<summary>US coefficients follow IEEE C37.112-2018 (values based on SEL relays) and IEC coefficients follow IEC 60255 for inverse-time overcurrent relays</summary>

<table data-header-hidden><thead><tr><th>Curve Name</th><th>Curve Shape</th><th width="90.39996337890625">A</th><th width="88.800048828125">B</th><th width="68">P</th><th width="61.5999755859375">K</th><th width="83.199951171875">Tr</th><th>Q</th></tr></thead><tbody><tr><td>US (U1)</td><td>Moderately Inverse</td><td>0.0226</td><td>0.0104</td><td>0.02</td><td>0</td><td>1.08</td><td>2</td></tr><tr><td>US (U2)</td><td>Inverse</td><td>0.180</td><td>5.95</td><td>2</td><td>0</td><td>5.95</td><td>2</td></tr><tr><td>US (U3)</td><td>Very Inverse</td><td>0.0963</td><td>3.88</td><td>2</td><td>0</td><td>3.88</td><td>2</td></tr><tr><td>US (U4)</td><td>Extremely Inverse</td><td>0.0352</td><td>5.67</td><td>2</td><td>0</td><td>5.67</td><td>2</td></tr><tr><td>US (U5)</td><td>Short-time Inverse</td><td>0.00262</td><td>0.00342</td><td>0.02</td><td>0</td><td>0.323</td><td>2</td></tr><tr><td>IEC (C1)</td><td>Standard Inverse</td><td>0</td><td>0.14</td><td>0.02</td><td>0</td><td>13.5</td><td>2</td></tr><tr><td>IEC (C2)</td><td>Very Inverse</td><td>0</td><td>13.5</td><td>1</td><td>0</td><td>47.3</td><td>2</td></tr><tr><td>IEC (C3)</td><td>Extremely Inverse</td><td>0</td><td>80</td><td>2</td><td>0</td><td>80</td><td>2</td></tr><tr><td>IEC (C4)</td><td>Long-time Inverse</td><td>0</td><td>120</td><td>1</td><td>0</td><td>120</td><td>1</td></tr><tr><td>IEC (C5)</td><td>Short-time Inverse</td><td>0</td><td>0.05</td><td>0.04</td><td>0</td><td>4.85</td><td>2</td></tr></tbody></table>

</details>

Custom curve operation uses five tunable pickup levels and five associated delays. The trip delay for any current between two levels is linearly interpolated between their corresponding times. Note: the custom curve affects trip time only; timed reset still follows the inverse reset curve and its parameters.

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-2d53e8f079d0296000ebc0359b8ae18cea623730%2Fimage%20(572).png?alt=media" alt="" width="303"><figcaption></figcaption></figure>

## Mask parameters <a href="#mask-parameters" id="mask-parameters"></a>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-132f5c79fa74cdd2ff422d98002f54913426a621%2F510C.jpg?alt=media" alt=""><figcaption></figcaption></figure>

{% tabs %}
{% tab title="General" %}

<table><thead><tr><th width="217">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Pickup current</strong></td><td>Pickup current for 51OC (pu or A). Ipck_51P_param = [0, 30]</td></tr><tr><td><strong>Time Dial</strong></td><td>Time dial multiplier (TD) TD51P_param = [0, 600]</td></tr><tr><td><strong>Reset type</strong></td><td>Type of relay reset. Options:<br>Timed (inverse reset),<br>Instant (instantaneous reset)<br>Reset_set_param = [0, 1]</td></tr></tbody></table>
{% endtab %}

{% tab title="Inverse curve" %}

<table><thead><tr><th width="219.4000244140625">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Inverse curve options</strong></td><td>Select standard curve parameters or user-defined parameters for inverse curves. Options: Use standard parameters for inverse curve; Use custom parameters for inverse curve User_coef_param = [0, 1]</td></tr><tr><td><strong>Standard IEC and US curve types</strong></td><td>Select a standard curve type. U1 (U.S. Moderately Inverse), U2 (U.S. Inverse), U3 (U.S. Very Inverse), U4 (U.S. Extremely Inverse), U5 (U.S. Short-time Inverse),<br>C1 (IEC Class A Standard Inverse), C2 (IEC Class B Very Inverse), C3 (IEC Class C Extremely Inverse), C4 (IEC Long-time Inverse), C5 (IEC Short-time Inverse). curve_type_51P_param = [0, 10]</td></tr><tr><td><strong>Trip parameter A</strong></td><td>'A' coefficient for user-defined inverse curve A_param = [0, 200]</td></tr><tr><td><strong>Trip parameter B</strong></td><td>'B' coefficient for user-defined inverse curve B_param = [0, 200]</td></tr><tr><td><strong>Trip parameter P</strong></td><td>'P' exponent for user-defined inverse curve P_param = [eps, 2]<br>if set to 0 by the user, epsilon is used internally to avoid division by zero</td></tr><tr><td><strong>Trip parameter K</strong></td><td>'K' offset for user-defined inverse curve K_param = [0, 50]</td></tr><tr><td><strong>Reset parameter Tr</strong></td><td>'Tr' reset coefficient for user-defined inverse curve Tr_param = [0, 50]</td></tr><tr><td><strong>Reset parameter Q</strong></td><td>'Q' reset exponent for user-defined inverse curve. Variable: Q_param = [eps, 50]<br>if set to 0 by the user, epsilon is used internally to avoid division by zero</td></tr></tbody></table>
{% endtab %}

{% tab title="Custom curve" %}

<table><thead><tr><th width="218.60003662109375">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Use custom curves 51P</strong></td><td>Enable custom five-point trip curve instead of standard time curves cust51P_param = {0, 1}<br>Note: applies to trip time only; timed reset still follows inverse reset parameters</td></tr><tr><td><strong>Level 1, 51P</strong></td><td>Pickup current at Level 1 (pu or A) level1_51_param = [0, 30]</td></tr><tr><td><strong>Level 2, 51P</strong></td><td>Pickup current at Level 2 (pu or A) level2_51_param = [0, 30]</td></tr><tr><td><strong>Level 3, 51P</strong></td><td>Pickup current at Level 3 (pu or A) level3_51_param = [0, 30]</td></tr><tr><td><strong>Level 4, 51P</strong></td><td>Pickup current at Level 4 (pu or A) level4_51_param = [0, 30]</td></tr><tr><td><strong>Level 5, 51P</strong></td><td>Pickup current at Level 5 (pu or A) level5_51_param = [0, 30]</td></tr><tr><td><strong>Time for level 1, 51P</strong></td><td>Time delay at Level 1 (s) time1_51_param = [0, 600]</td></tr><tr><td><strong>Time for level 2, 51P</strong></td><td>Time delay at Level 2 (s) time2_51_param = [0, 600]</td></tr><tr><td><strong>Time for level 3, 51P</strong></td><td>Time delay at Level 3 (s) time3_51_param = [0, 600]</td></tr><tr><td><strong>Time for level 4, 51P</strong></td><td>Time delay at Level 4 (s) time4_51_param = [0, 600]</td></tr><tr><td><strong>Time for level 5, 51P</strong></td><td>Time delay at Level 5 (s) time5_51_param = [0, 600]</td></tr></tbody></table>
{% endtab %}
{% endtabs %}

## Inputs <a href="#inputs" id="inputs"></a>

<table><thead><tr><th width="220.39996337890625">Input</th><th>Description</th></tr></thead><tbody><tr><td><strong>I</strong></td><td>Per-unit or RMS value (A) of the actuating current</td></tr></tbody></table>

## Outputs <a href="#outputs" id="outputs"></a>

<table><thead><tr><th width="219.60003662109375">Output</th><th>Description</th></tr></thead><tbody><tr><td><strong>Trip</strong></td><td>Binary trip output of the 51OC relay.<br>Defaults to 0; becomes 1 when overcurrent is detected; resets when the input drops below the pickup value</td></tr></tbody></table>

## References <a href="#references" id="references"></a>

1. SEL-751 Relay Feeder Protection Relay Instruction Manual, Schweitzer Engineering Laboratories Inc., 2017


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-protection-relays/51-inverse-overcurrent-1-ph.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.