> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-protection-relays/59-overvoltage.md).

# 59 - Overvoltage

## Description

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-ecb89edd1efdb5aa9bf7f0d6c0580385aad91a1b%2Fimage%20(959).png?alt=media" alt="" width="155"><figcaption></figcaption></figure>

The **59 - Overvoltage** block, located in the **Control Protection Relays** library, operates when the monitored voltage exceeds configured thresholds. It provides five levels, each with an over-voltage threshold and an associated time delay. The relay can use either the maximum phase-neutral voltage or the maximum phase-phase voltage among the three phases. It supports 50 Hz and 60 Hz systems.

The relay trips protected equipment when the selected operating quantity remains above a level longer than its delay. If the voltage drops below the threshold before the delay expires, the timer resets and will not restart until the threshold is exceeded again. All voltage levels and delay times are tunable.<br>

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-a2d33458a49cdd1aa2142da25e817b6737b909f7%2Fimage%20(566).png?alt=media" alt="" width="316"><figcaption></figcaption></figure>

## Mask parameters

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-bc4e0dffa14bd8557698ac234d1709d8e577413c%2Fimage%20(567).png?alt=media" alt="" width="563"><figcaption></figcaption></figure>

<table><thead><tr><th width="219.60003662109375">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Frequency</strong></td><td>The frequency of the measured current signals (Hz); supports 50 and 60 Hz. Sample value: 60.</td></tr><tr><td><strong>Ubase</strong></td><td>The base voltage (L-L) at the measurement location (V). Sample value: 500000.</td></tr><tr><td><strong>Operating Quantity</strong></td><td>Two types: maximum Phase-Neutral Voltage or maximum Phase-Phase Voltage among three phases. Sample value: Phase-Neutral Voltage.</td></tr><tr><td><strong>Level 1</strong></td><td>Overvoltage level 1 (pu). Sample value: 1.05.</td></tr><tr><td><strong>Level 2</strong></td><td>Overvoltage level 2 (pu). Sample value: 1.1.</td></tr><tr><td><strong>Level 3</strong></td><td>Overvoltage level 3 (pu). Sample value: 1.15.</td></tr><tr><td><strong>Level 4</strong></td><td>Overvoltage level 4 (pu). Sample value: 1.2.</td></tr><tr><td><strong>Level 5</strong></td><td>Overvoltage level 5 (pu). Sample value: 1.25.</td></tr><tr><td><strong>Time 1</strong></td><td>Time delay associated with Level 1 (s). Sample value: 2.</td></tr><tr><td><strong>Time 2</strong></td><td>Time delay associated with Level 2 (s). Sample value: .5.</td></tr><tr><td><strong>Time 3</strong></td><td>Time delay associated with Level 3 (s). Sample value: .4.</td></tr><tr><td><strong>Time 4</strong></td><td>Time delay associated with Level 4 (s). Sample value: .3.</td></tr><tr><td><strong>Time 5</strong></td><td>Time delay associated with Level 5 (s). Sample value: .2.</td></tr></tbody></table>

## Inputs

<table><thead><tr><th width="220.39996337890625">Input</th><th>Description</th></tr></thead><tbody><tr><td><strong>Vabc</strong></td><td>A 3-dimension voltage input for three-phase voltages, in the order of Va, Vb, and Vc (V).</td></tr><tr><td><strong>Reset</strong></td><td>The reset signal for the relay (binary). The relay will be reset when this signal becomes 1.</td></tr></tbody></table>

## Outputs

<table><thead><tr><th width="220.39996337890625">Output</th><th>Description</th></tr></thead><tbody><tr><td><strong>Q</strong></td><td>The output of the over-voltage relay (binary).<br>By default it is 0; if an over-voltage scenario is detected, it becomes 1.</td></tr><tr><td><strong>Q_n</strong></td><td>The complementary value of Q (binary).</td></tr></tbody></table>


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-protection-relays/59-overvoltage.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.