> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-protection-relays/59-overvoltage-1-ph.md).

# 59 - Overvoltage 1-ph

## Description

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-8e906053159ab1a7cc22e652b45399f50428c9eb%2Fimage%20(960).png?alt=media" alt="" width="181"><figcaption></figcaption></figure>

The **59 - Overvoltage 1-ph** block, located in the **Control Protection Relays** library, operates when the monitored voltage exceeds configurable thresholds. It provides five over-voltage levels, each with an associated trip delay.

The relay trips when the input stays above a selected level longer than its delay. If the input falls below that threshold before the delay expires, the timer resets and restarts only when the threshold is exceeded again. All voltage levels and delay times are tunable.

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-a2d33458a49cdd1aa2142da25e817b6737b909f7%2Fimage%20(566).png?alt=media" alt="" width="316"><figcaption></figcaption></figure>

The operating quantity can be the RMS phase voltage, or the positive-, negative-, or zero-sequence of a three-phase voltage. Units can be per-unit (pu) or volts (V).

## Mask parameters

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-5a4e593c48b831843d8d56ffa72418a6246348e4%2Fimage%20(961).png?alt=media" alt="" width="512"><figcaption></figcaption></figure>

<table><thead><tr><th width="219.60003662109375">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Level 1</strong></td><td>Overvoltage level 1 (pu). Sample value: 1.05.</td></tr><tr><td><strong>Level 2</strong></td><td>Overvoltage level 2 (pu). Sample value: 1.1.</td></tr><tr><td><strong>Level 3</strong></td><td>Overvoltage level 3 (pu). Sample value: 1.15.</td></tr><tr><td><strong>Level 4</strong></td><td>Overvoltage level 4 (pu). Sample value: 1.2.</td></tr><tr><td><strong>Level 5</strong></td><td>Overvoltage level 5 (pu). Sample value: 1.25.</td></tr><tr><td><strong>Time 1</strong></td><td>Time delay associated with Level 1 (s). Sample value: 2.</td></tr><tr><td><strong>Time 2</strong></td><td>Time delay associated with Level 2 (s). Sample value: .5.</td></tr><tr><td><strong>Time 3</strong></td><td>Time delay associated with Level 3 (s). Sample value: .4.</td></tr><tr><td><strong>Time 4</strong></td><td>Time delay associated with Level 4 (s). Sample value: .3.</td></tr><tr><td><strong>Time 5</strong></td><td>Time delay associated with Level 5 (s). Sample value: .2.</td></tr></tbody></table>

## Inputs

<table><thead><tr><th width="220.4000244140625">Input</th><th>Description</th></tr></thead><tbody><tr><td><strong>V</strong></td><td>Single-dimensional signal: RMS phase voltage, or positive-, negative-, or zero-sequence of a three-phase voltage (pu or V).</td></tr></tbody></table>

## Outputs

<table><thead><tr><th width="219.60003662109375">Output</th><th>Description</th></tr></thead><tbody><tr><td><strong>Trip</strong></td><td>Binary output. 0 by default; set to 1 when an over-voltage condition is detected.</td></tr></tbody></table>


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-protection-relays/59-overvoltage-1-ph.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.