> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-protection-relays/79-autorecloser.md).

# 79 - AutoRecloser

## Description

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-cc2b766209ff9f4f32c386f4a22a3f16d8509d0d%2Fimage%20(536).png?alt=media" alt="" width="283"><figcaption></figcaption></figure>

The **79 - AutoRecloser** block, located in the **Control Protection Relays** library, implements automatic reclosing for circuit breakers to restore service after transient line faults \[1]. When a fault is detected and the breaker trips, the relay waits a configured open-interval (dead) time, then issues a close command. If the fault has cleared, operation ends. If the fault persists, the breaker trips again and the relay may attempt additional recloses up to the configured number of shots. After the final attempt, if the fault remains, the breaker trips and the relay issues a LockOut command.

The open-interval time allows arc de-ionization on a de-energized line to improve the probability of a successful reclose \[1].

The reclaim time is the time from issuing a close command until the relay can issue the next reclose attempt; it starts when the circuit breaker closing command is given \[2]. The CB closing command (output CB\_Close) is a pulse whose duration is set by the CB\_Close pulse width parameter.

## Mask parameters

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-5d0ab08c5c95afff28ed644ad3e1d8dfbfa25217%2Fimage%20(537).png?alt=media" alt="" width="449"><figcaption></figcaption></figure>

| Parameter                     | Description                                        |
| ----------------------------- | -------------------------------------------------- |
| **Operation**                 | Enable or disable the 79 recloser function.        |
| **Number of reclosure shots** | Number of reclosure attempts (maximum 3).          |
| **79OI1 Open Interval**       | Open-interval time for shot 1 (s).                 |
| **79OI2 Open Interval**       | Open-interval time for shot 2 (s).                 |
| **79OI3 Open Interval**       | Open-interval time for shot 3 (s).                 |
| **Reclaim time**              | Duration of the reclaim time (s).                  |
| **CB\_Close pulse width**     | Duration of the circuit breaker closing pulse (s). |

## Inputs

| Input                 | Description                                                              |
| --------------------- | ------------------------------------------------------------------------ |
| **AR\_Start**         | Triggers the reclosing function.                                         |
| **CB\_Close\_status** | <p>Circuit breaker contact position:<br>1 = Closed; 0 = Open.</p>        |
| **CB\_Ready\_status** | <p>Circuit breaker ready for reclosing:<br>1 = Ready; 0 = Not ready.</p> |
| **SyncCheck**         | Synchronism-check condition is fulfilled.                                |
| **Reset**             | Resets to initial conditions on the rising edge of the signal.           |

## Outputs

| Output        | Description                              |
| ------------- | ---------------------------------------- |
| **CB\_Close** | Closing command for the circuit breaker. |
| **LockOut**   | LockOut command for the circuit breaker. |

## References

\[1] REL-670 Application Manual - ABB

\[2] REL-670 Technical Manual - ABB

\[3] SEL-651 Recloser Control, Instruction Manual - SEL


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-protection-relays/79-autorecloser.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.