> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-stabilizers/ieee-pss2a.md).

# IEEE PSS2A

## Description

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-4938898341c2d6480c34b158aeadeb602200609b%2Fimage%20(966).png?alt=media" alt="" width="200"><figcaption></figcaption></figure>

The **IEEE** **PSS2A** block is a dual-input power system stabilizer based on references \[1] and \[2]. It represents stabilizers with inputs of power, speed, or frequency.

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-28c99e89aecf415b9040c68227ce30b4200a4ddf%2Fimage%20(968).png?alt=media" alt=""><figcaption></figcaption></figure>

{% hint style="danger" %}
The HYPERSIM<sup>®</sup> simulation option “Set Initial Conditions” must be checked for automatic initialization to work properly.
{% endhint %}

## Mask parameters

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-070a8cd66923e2f3cd923195474e957f85fd3f98%2Fimage%20(967).png?alt=media" alt="" width="563"><figcaption></figcaption></figure>

<table><thead><tr><th width="181.60003662109375">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>T1, T3</strong></td><td>PSS lead compensating time constant (s).</td></tr><tr><td><strong>T2, T4</strong></td><td>PSS lag compensating time constant (s).</td></tr><tr><td><strong>Tw1, Tw2, Tw3, Tw4</strong></td><td>PSS washout time constant (s).</td></tr><tr><td><strong>T6</strong></td><td>Transducer time constant (s).</td></tr><tr><td><strong>T7</strong></td><td>Transducer time constant (s).</td></tr><tr><td><strong>T8</strong></td><td>Lead time constant of ramp tracking filter (s).</td></tr><tr><td><strong>T9</strong></td><td>Lag time constant of ramp tracking filter (s).</td></tr><tr><td><strong>M, N</strong></td><td>Ramp tracking filter constant (-). Range: 0 ≤ M ≤ 5; 0 ≤ N ≤ 4. M and N are integers.</td></tr><tr><td><strong>Ks1, Ks2, Ks3</strong></td><td>PSS gains (-).</td></tr><tr><td><strong>VSTmax</strong></td><td>Maximum PSS output (pu).</td></tr><tr><td><strong>VSTmin</strong></td><td>Minimum PSS output (pu).</td></tr><tr><td><strong>W0</strong></td><td>Rotor speed/frequency reference (Wref in the diagram) (pu).</td></tr><tr><td><strong>Pe0</strong></td><td>Electrical active power reference (Pref in the diagram) (pu).</td></tr></tbody></table>

The parameters Pe0 and W0 can be set manually with numeric values or automatically from load flow results by referencing a synchronous machine variable. If the synchronous machine name is “SM1” in the genunit to which the stabilizer is connected:

* For a thermal or hydraulic machine: set Pe0 = “=SM1.Peo/SM1.BaseMVA” and W0 = “=SM1.wo”.
* For a pu standard or pu fundamental machine: set Pe0 = “=SM1.lfP/1e6/SM1.sBase” and W0 = “=SM1.Wm\_Init”.

{% hint style="info" %}
For all transfer functions, the degree of the numerator must be less than or equal to the degree of the denominator.
{% endhint %}

## Inputs

<table><thead><tr><th width="180.800048828125">Input</th><th>Description</th></tr></thead><tbody><tr><td><strong>VSI1</strong></td><td>Power system stabilizer input (speed or frequency), (pu).</td></tr><tr><td><strong>VSI2</strong></td><td>Power system stabilizer input (electrical power), (pu).</td></tr></tbody></table>

## Outputs

<table><thead><tr><th width="180">Output</th><th>Description</th></tr></thead><tbody><tr><td><strong>VST</strong></td><td>Power system stabilizer output, (pu).</td></tr></tbody></table>

## References

\[1] Siemens Industry, Inc. Siemens Power Technologies International, "PSS®E 34.2.0 MODEL LIBRARY," April 2017.

\[2] IEEE, , "IEEE Recommended Practice for Excitation System Models for Power System Stability Studies," \_IEEE Std 421.5-1992,\_pp. 1-56, 10 Aug. 1992.


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/control-stabilizers/ieee-pss2a.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.