> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/network-facts-and-hvdc/lcc-6-12-pulse-rectifier-inverter-oriented.md).

# LCC - 6/12 Pulse Rectifier/Inverter Oriented

## Description

The **HVDC Converter** blocks, located in the **Network FACTS & HVDC** library, model 6-pulse and 12-pulse rectifiers and inverters with a common control system. The internal architecture is identical across 6-pulse/12-pulse and rectifier/inverter variants.

The thyristor bridge can be fired by: 1) the internal generic control system, 2) an external physical source, or 3) the HYPERSIM control module (control block). The models support valve short-circuits and DC faults, and allow step responses to tune regulator parameters.

A converter station includes a 6- or 12-pulse converter, a converter transformer, and the generic control system. For a 6‑pulse converter, the bridge connects to either the star or delta secondary winding of the transformer. A GTO-based two-level voltage-source converter (VSC) can be modeled using the GTO+diode switch in the six‑pulse inverter; the implementation ensures correct, simultaneous diode/GTO switching.

The control system comprises regulation, synchronization, protection, and tap changer subsystems. The rectifier regulates direct current to its reference and may reach its minimum delay angle (αmin) in abnormal conditions (αmin mode). The inverter regulates the DC voltage at the line input and can operate in voltage regulation, current-compensated, or current regulation modes, depending on current and margin settings. If the DC current increases excessively, the inverter extinction angle γ may reach its minimum, causing operation in γmin mode.

The alpha-angle regulation and limiting system adjusts the firing angle α to regulate DC current or voltage and limits the inverter extinction angle to a minimum. Two PI controllers with limiters determine α from the lowest of their outputs. For rectifier operation, the current loop is active (voltage loop is biased high). For inverter operation, the voltage loop is active and uses the current margin ΔI computed from the current reference and measured current. Gain linearization keeps the PI response speed consistent versus angle by multiplying the proportional gain with a factor G(α) (for the inverter, G(β) with β defined below).

$$\beta = 180^\circ - \alpha$$

Angle limits: the rectifier α is limited between adjustable bounds. For the inverter, the lower limit is an adjustable constant; the upper limit varies based on γmin, a commutation-failure reduction γcf, and the overlap angle μ. A rate limiter on Δα reduces commutation failure risk and improves stability during large disturbances; typical Δα breakpoints are provided for rectifier and inverter cases.

VDCOL (voltage-dependent current order limiter) improves recovery following AC-side faults and reduces commutation-failure risk. It filters Vd with a time constant T that depends on the Vd direction (decrease: Td = 0; increase: Tm = 80 ms), then computes a current reference that falls quickly and rises more slowly. Typical adjustable values are provided for Idrefmin, Vdfmin, Vdf1pu, and Idrefmina.

The firing/synchronization system uses a lag-angle reference (α) from the regulation system. Six-pulse converters use equiangular synchronization; 12-pulse converters can use equiangular or equidistant synchronization. In equidistant mode, an oscillator at 12× grid frequency is phase-controlled by the regulation system; the oscillator gain governs synchronization speed and immunity to harmonics (default gain: 32). A valve fires only when its terminal voltage exceeds a user-adjustable threshold.

Band-pass filters (with adjustable tuning frequency, bandwidth, and min/max frequency) preprocess synchronization voltages. Low AC voltage detection holds the measured period T and inhibits DC fault detection when voltage is below a threshold for a specified duration (with a falling-edge hold).

Protection includes DC fault protection on the rectifier and commutation-failure protection on the inverter. DC faults force α to a value greater than 90° for a set time and can repeat until the fault clears or the converter is blocked. Commutation-failure protection reduces the inverter α upper limit by γcf, which rises rapidly on detection and decays slowly to avoid successive failures. Commutation failures can be simulated by withholding firing of a given valve for a specified duration.

Converters can be unblocked manually or automatically (after protection actions). Manual unblocking requires Id below a threshold and typically starts with Idref = 0, an enable command, and then applying the desired reference with rate limiters. Automatic disabling is immediate and driven by DC fault protection.

## Mask parameters

**Id and Vd References**

| Parameter                 | Description                                                        |
| ------------------------- | ------------------------------------------------------------------ |
| **Id Ref (pu)**           | Current reference. Possible values: \[0, 1]                        |
| **Id Ref + Slope (pu/s)** | Current reference rising rate. Possible values: \[0, 1e12]         |
| **Id Ref - Slope (pu/s)** | Current reference falling rate. Possible values: \[0, 1e12]        |
| **Id Ref min (pu)**       | Lower limit for the current reference. Possible values: \[0, 1]    |
| **Id Ref max (pu)**       | Upper limit for the current reference. Possible values: \[0, 1]    |
| **Vd Ref (pu)**           | Voltage reference. Possible values: \[0, 1]                        |
| **Vd Ref + Slope (pu/s)** | Voltage reference rising rate. Possible values: \[0, 1e12]         |
| **Vd Ref - Slope (pu/s)** | Voltage reference falling rate. Possible values: \[0, 1e12]        |
| **Vd Ref min (pu)**       | Lower limit for the voltage reference. Possible values: \[0, 1e12] |
| **Vd Ref max (pu)**       | Upper limit for the voltage reference. Possible values: \[0, 1e12] |

**Operating modes**

| Parameter                         | Description                                                                                    |
| --------------------------------- | ---------------------------------------------------------------------------------------------- |
| **Converter mode**                | Operating mode of the converter (rectifier = 0, inverter = 1). Possible values: {0, 1}         |
| **Blocking**                      | Converter enabled (1) or disabled (0). Possible values: {0, 1}                                 |
| **Regulator mode α constant**     | Controlled Alpha (0) or Constant Alpha (1). Possible values: {0, 1}                            |
| **α constant reference (degree)** | Delay angle α when operating in constant α mode. Possible values: \[0, 179]                    |
| **Firing**                        | Firing source: internal (0) or external (1). Possible values: {0, 1}                           |
| **Cathode connection**            | Location of the cathode connection: neutral side (0) or line side (1). Possible values: {0, 1} |

**General Parameters**

| Parameter                    | Description                                                              |
| ---------------------------- | ------------------------------------------------------------------------ |
| **Vd Base (kV)**             | Base for direct voltage. Possible values: (0, 1e12]                      |
| **Id Base (kA)**             | Base for direct current. Possible values: (0, 1e12]                      |
| **Vac Base (rms L-L) (kV)**  | Rated AC voltage on the transformer primary. Possible values: (0, 1e12]  |
| **Synchronization Bus**      | Name of the bus whose voltages are used to synchronize the firing system |
| **DC Line Bus (Vd Measure)** | Name of the bus connecting the converter and the DC line                 |

**Command**

| Parameter                      | Description                                                                                                          |
| ------------------------------ | -------------------------------------------------------------------------------------------------------------------- |
| **Control Type**               | Firing control source selection: internal generated; from external pins of the block; from external signals hardware |
| **UCC command (for 12 pulse)** | Disable (0) or enable (1) the command. Possible values: {0, 1}                                                       |

**Converter Transformer**

| Parameter                 | Description                                                                                                             |
| ------------------------- | ----------------------------------------------------------------------------------------------------------------------- |
| **Transfo name**          | Transformer name                                                                                                        |
| **Leakage (H)**           | Leakage inductance of the converter transformer for star or delta winding on the valve side. Possible values: (0, 1e12] |
| **Delta connection Type** | Delta winding phase shift: Lag; Lead                                                                                    |

**Rectifier**

| Parameter                           | Description                                                                      |
| ----------------------------------- | -------------------------------------------------------------------------------- |
| **Ki Id (degrees/pu/second)**       | Integral gain of the PI current regulator. Possible values: \[-1e12, 1e12]       |
| **Kp Id (degrees/pu/second)**       | Proportional gain of the PI current regulator. Possible values: \[-1e12, 1e12]   |
| **αmin (degree)**                   | Lower limit of the delay angle α. Possible values: \[0, 179]                     |
| **αmax (degree)**                   | Upper limit of the delay angle α. Possible values: \[0, 179]                     |
| **Δα1, Δα2 (degree, for 12 pulse)** | Limit values for positive variation of delay angle α. Possible values: \[0, 179] |
| **Δα3, Δα4 (degree, for 12 pulse)** | Limit values for negative variation of delay angle α. Possible values: \[0, 179] |

**Inverter**

| Parameter                     | Description                                                                      |
| ----------------------------- | -------------------------------------------------------------------------------- |
| **Ki Id (degrees/pu/second)** | Integral gain of the PI current regulator. Possible values: \[-1e12, 1e12]       |
| **Kp Id (degrees/pu/second)** | Proportional gain of the PI current regulator. Possible values: \[-1e12, 1e12]   |
| **αmin (degree)**             | Lower limit of the delay angle α. Possible values: \[0, 179]                     |
| **Ki Vd (degrees/pu/second)** | Integral gain of the PI voltage regulator. Possible values: \[-1e12, 1e12]       |
| **Kp Vd (degrees/pu/second)** | Proportional gain of the PI voltage regulator. Possible values: \[-1e12, 1e12]   |
| **γmin (degree)**             | Lower limit for the γ angle. Possible values: \[0, 179]                          |
| **Δα1, Δα2 (degree)**         | Limit values for positive variation of delay angle α. Possible values: \[0, 179] |
| **Δα3 (degree)**              | Limit value for negative variation of delay angle α. Possible values: \[0, 179]  |
| **Id margin (pu)**            | Current regulation tolerance. Possible values: (0, 1]                            |
| **Vd margin (pu)**            | Voltage regulation tolerance. Possible values: (0, 1]                            |

**Synchronization and Command (12-pulse only)**

| Parameter                          | Description                                                                                   |
| ---------------------------------- | --------------------------------------------------------------------------------------------- |
| **Synchronization mode**           | Equidistant or equiangular synchronization                                                    |
| **Status**                         | Used (1); Not used (0). Possible values: {0, 1}                                               |
| **Umin (pu)**                      | Minimum valve terminal voltage required to fire in equidistant mode. Possible values: \[0, 1] |
| **Kosc**                           | Oscillator gain. Possible values: \[-1e12, 1e12]                                              |
| **Transformer Decoupling element** | Tap changer transformer with decoupling element (Enabled or Disabled)                         |
| **Transformation ratio**           | Rated ratio Ns/Np. Possible values: \[0, 1e12]                                                |

**VDCOL**

| Parameter             | Description                                      |
| --------------------- | ------------------------------------------------ |
| **Vd min (pu)**       | Minimum DC voltage. Possible values: (0, 1]      |
| **Id min (pu)**       | Minimum DC current. Possible values: (0, 1]      |
| **Rise time (s)**     | DC voltage rise time. Possible values: (0, 1e12] |
| **Vd threshold (pu)** | Threshold voltage. Possible values: (0, 1]       |

**Tap changer control**

| Parameter                           | Description                                                                           |
| ----------------------------------- | ------------------------------------------------------------------------------------- |
| **αmin (rectifier mode) (degrees)** | Minimum delay angle range bound for tap changer logic. Possible values: (15, 18]      |
| **αmax (rectifier mode) (degrees)** | Maximum delay angle range bound for tap changer logic. Possible values: (15, 18]      |
| **γmin (inverter mode) (degrees)**  | Minimum extinction angle range bound for tap changer logic. Possible values: (17, 20] |
| **γmax (inverter mode) (degrees)**  | Maximum extinction angle range bound for tap changer logic. Possible values: (17, 20] |

**Id and Vd Measurement Filters**

| Parameter                 | Description                                                    |
| ------------------------- | -------------------------------------------------------------- |
| **First order (τ1) (s)**  | First-order filter time constant. Possible values: (0, 1e12]   |
| **Second order (τ2) (s)** | Second-order filter time constant. Possible values: (0, 1e12]  |
| **Freq base (Hz)**        | Frequency base. Possible values: (0, 1e12]                     |
| **Freq min (Hz)**         | Minimum band-pass filter frequency. Possible values: (0, 1e12] |
| **Freq max (Hz)**         | Maximum band-pass filter frequency. Possible values: (0, 1e12] |
| **Passband (Hz)**         | Filter bandwidth. Possible values: (0, 1e12]                   |

**General parameters**

| Parameter           | Description                                                                                            |
| ------------------- | ------------------------------------------------------------------------------------------------------ |
| **Ropen (Ohms)**    | Open-state resistance. Possible values: (0, 1e12]                                                      |
| **Rclosed (Ohms)**  | Closed-state resistance. Possible values: (0, 1e12]                                                    |
| **Rsnubber (Ohms)** | Snubber resistance. Possible values: (0, 1e12]                                                         |
| **Csnubber (F)**    | Snubber capacitance. Possible values: \[0, 1e12]                                                       |
| **Fbov (V)**        | Highest forward voltage across a blocked valve (diodes, thyristors, GTOs). Possible values: \[0, 1e12] |
| **Rbov (V)**        | Highest reverse voltage across a valve (diodes, thyristors, GTOs). Possible values: \[0, 1e12]         |
| **Tq (s)**          | Turn-off time. Possible values: \[0, 1e12]                                                             |
| **Ibreak (A)**      | GTO maximum breakable current. Possible values: \[0, 1e12]                                             |
| **Vf (V)**          | Forward voltage drop. Possible values: \[0, 1e12]                                                      |
| **Ihold (A)**       | Holding current. Possible values: \[0, 1e12]                                                           |

**Switch parameters**

| Parameter                 | Description                                                                               |
| ------------------------- | ----------------------------------------------------------------------------------------- |
| **Switch type**           | Valve type used in the converter                                                          |
| **Fail reset**            | Reset for breakdown/false firing signal: Disable (0); Enable (1). Possible values: {0, 1} |
| **Precision valve model** | Precision valve model active or not (Active = Enable; Deactivated = Disable)              |

\*\*DC fault protection (rectifier)\*\*

| Parameter                 | Description                                                                             |
| ------------------------- | --------------------------------------------------------------------------------------- |
| **Detection delay (s)**   | Detection delay of DC fault. Possible values: \[0, 1e12]                                |
| **Vd threshold (pu)**     | DC voltage threshold used for DC fault detection. Possible values: \[0, 1]              |
| **α retard (degree)**     | Constant α angle imposed after fault detection. Possible values: \[0, 1e12]             |
| **α retard duration (s)** | Duration during which forced α is imposed by DC protection. Possible values: \[0, 1e12] |
| **α retard number**       | Number of forced-α attempts before automatic blocking. Possible values: \[0, 1e12]      |

**Switching misfiring protection (inverter)**

| Parameter            | Description                                                                                             |
| -------------------- | ------------------------------------------------------------------------------------------------------- |
| **Protection**       | Enabled (1) or disabled (0). Possible values: {0, 1}                                                    |
| **Delta γ (degree)** | Value added to the lower γ limit by the protection for commutation failures. Possible values: \[0, 360] |
| **Rise time (s)**    | First-order time constant for increase of minimum γ. Possible values: \[0, 1e12]                        |
| **Fall time (s)**    | First-order time constant for decrease of minimum γ. Possible values: \[0, 1e12]                        |

**Protective Block (12-pulse only)**

| Parameter                           | Description                                                         |
| ----------------------------------- | ------------------------------------------------------------------- |
| **Protective Block**                | Protective block enable (1) or disable (0). Possible values: {0, 1} |
| **Protective Block start time (s)** | Time to start the protective block. Possible values: (0, 1e12]      |

**Low AC Voltage Detection**

| Parameter               | Description                                                                                        |
| ----------------------- | -------------------------------------------------------------------------------------------------- |
| **Vac threshold (pu)**  | Voltage threshold used for low AC voltage detection. Possible values: {0, 1)                       |
| **Detection delay (s)** | Detection delay for low AC voltage. Possible values: {0, 1e12}                                     |
| **Fall delay (s)**      | Minimum flag duration (voltage lower than Vac threshold) before action. Possible values: {0, 1e12} |

### Protection — Disturbances

| Parameter                     | Description                                                                                                                          |
| ----------------------------- | ------------------------------------------------------------------------------------------------------------------------------------ |
| **Valve number for fault**    | Valve index to apply fault/misfiring (1–12 corresponds to: 1Y, 2Y, 3Y, 4Y, 5Y, 6Y, 1D, 2D, 3D, 4D, 5D, 6D). Possible values: {1, 12} |
| **Faults/misfiring**          | Disturbance type: None = 0; Valve = 1; DC = 2; Misfiring = 3; DCY = 4; DCD = 5                                                       |
| **DC fault resistance (Ohm)** | Fault resistance at converter terminals. Possible values: {0, 1e12}                                                                  |
| **Reference step**            | Reference step selection: None; 1 for ΔIref step; 2 for ΔVref step                                                                   |
| **ΔIref or ΔVref (pu)**       | Step size for current or voltage reference                                                                                           |
| **Start time (s)**            | Disturbance start time                                                                                                               |
| **End time (s)**              | Disturbance end time                                                                                                                 |

## Conserving ports

| Port  | Description                                             |
| ----- | ------------------------------------------------------- |
| **+** | DC positive terminal                                    |
| **-** | DC negative terminal                                    |
| **Y** | AC connection to internal transformer secondary (star)  |
| **Δ** | AC connection to internal transformer secondary (delta) |

## Inputs

| Input                          | Description                                                                                                                                              |
| ------------------------------ | -------------------------------------------------------------------------------------------------------------------------------------------------------- |
| **Vst\_UCC (Boolean)**         | Voltage Setting Terminal (1 = true). Inverter controlling the voltage                                                                                    |
| **Vref\_UCC (pu)**             | DC voltage reference to the voltage regulator                                                                                                            |
| **ThirdSt\_UCC (Boolean)**     | Third station present when deblock (1 = true, 0 = false)                                                                                                 |
| **Stop\_UCC**                  | Block the converter (0→1 pulse). Must be 0 to allow start; IdRef should be ≤ 0.1 pu                                                                      |
| **Start\_UCC**                 | Deblock the converter (0→1 pulse)                                                                                                                        |
| **Rect\_UCC (Boolean)**        | Rectifier mode (1 = Rectifier; 0 = Inverter). Operates in current control                                                                                |
| I**ref\_UCC (pu)**             | DC current reference to the current regulator. Note: Set Id Ref slopes to a large value (e.g., 10 pu/s) in the model to avoid interfering with Iref\_UCC |
| DefCCBloc\_UCC (Boolean)       | Def CC Bloc signal from local or master (1 = true, 0 = false)                                                                                            |
| **BVst\_UCC (Boolean)**        | Backup Voltage Setting Terminal (1 = true, 0 = false). Inverter controls current, but switches to voltage control if Vst is blocked                      |
| **AlphaRetard\_UCC (Boolean)** | Alpha retard activation from local or master (1 = true, 0 = false)                                                                                       |

## Outputs

This block has no outputs.

## Signals available for monitoring and external I/O connections (via sensors form)

All block inputs and outputs are available as signals for monitoring and for external I/O connections.

Additional signals are also available and are listed below with their descriptions.

| Signal                            | Description                                                                                                                  |
| --------------------------------- | ---------------------------------------------------------------------------------------------------------------------------- |
| **VSYNC (a,b,c) (V)**             | Primary phase voltages used by the firing synchronization system                                                             |
| **VSYNC (ba,cb,ac) (V)**          | Primary phase-to-phase voltages used by the firing synchronization system                                                    |
| **V\_LINE (V)**                   | DC voltage (to ground) at the DC line input                                                                                  |
| **V\_NEUTRAL (V)**                | DC neutral (to ground) at the DC line input                                                                                  |
| **IPrimXfo (a,b,c) (A)**          | AC currents in the transformer primary windings                                                                              |
| **Id (A)**                        | DC current on the bridge                                                                                                     |
| **IY (a,b,c) (A)**                | AC currents in the Y secondary windings of the transformer                                                                   |
| **V12\_xY (x = 1 to 6) (V)**      | Voltage across valve x of the bridge connected to the Y windings                                                             |
| I**12\_xY (x = 1 to 6) (A)**      | Current through valve x of the bridge connected to the Y windings                                                            |
| **CMD12INT\_xY (x = 1 to 6)**     | Internal firing command to component “1 to 2” of valve x (Y windings)                                                        |
| **CMD21INT\_xY (x = 1 to 6)**     | Internal firing command to component “2 to 1” of valve x (Y windings)                                                        |
| **CMD12EXT\_xY (x = 1 to 6)**     | External firing command to component “1 to 2” of valve x (Y windings)                                                        |
| **CMD21EXT\_xY (x = 1 to 6)**     | External firing command to component “2 to 1” of valve x (Y windings)                                                        |
| **CMDFLT**                        | Flag for a valve fault                                                                                                       |
| **PPattern**                      | Binary pattern indicating which thyristors receive firing pulses (e.g., 5 = thyristors 1 and 3)                              |
| **Up\_Tr**                        | Command to increase the tap position                                                                                         |
| **Down\_Tr**                      | Command to decrease the tap position                                                                                         |
| **STATE12\_xY (x = 1 to 6)**      | State of component “1 to 2” of valve x (Y windings)                                                                          |
| **STATE21\_xY (x = 1 to 6)**      | State of component “2 to 1” of valve x (Y windings)                                                                          |
| **FAILSIG\_xY (x = 1 to 6)**      | Valve alarm signal (e.g., Tq limit infringements, reverse/forward voltage > Rbov; reset behavior depends on Fail Reset)      |
| **DelayImpInt**                   | Internal pulse delay                                                                                                         |
| **DelayImpExt**                   | External pulse delay                                                                                                         |
| **DelayImp**                      | Pulse delay                                                                                                                  |
| **P\_label**                      | Same as Pattern\_label, originating from the control module                                                                  |
| **D\_label**                      | Delay from the control module                                                                                                |
| **ID (a,b,c) (A)**                | AC currents in the delta secondary windings of the transformer                                                               |
| **V12\_xD (x = 1 to 6) (V)**      | Voltage across valve x of the bridge connected to the delta windings                                                         |
| **I12\_xD (x = 1 to 6) (A)**      | Current through valve x of the bridge connected to the delta windings                                                        |
| **CMD12INT\_xD (x = 1 to 6)**     | Internal firing command to component “1 to 2” of valve x (delta). For GTO+Diode, value is -1 when diode is forced to conduct |
| **CMD21INT\_xD (x = 1 to 6)**     | Internal firing command to component “2 to 1” of valve x (delta)                                                             |
| **CMD12EXT\_xD (x = 1 to 6)**     | External firing command to component “1 to 2” of valve x (delta)                                                             |
| **CMD21EXT\_xD (x = 1 to 6)**     | External firing command to component “2 to 1” of valve x (delta). For GTO+Diode, value is -1 when diode is forced to conduct |
| **STATE12\_xD (x = 1 to 6)**      | State of component “1 to 2” of valve x (delta)                                                                               |
| **STATE21\_xD (x = 1 to 6)**      | State of component “2 to 1” of valve x (delta)                                                                               |
| **FAILSIG\_xD (x = 1 to 6)**      | Valve alarm signal (delta bridge)                                                                                            |
| **PeriodY\_label (s)**            | Period of AC voltage measured in the equiangular synchronization (Y bridge)                                                  |
| **PeriodD\_label (s)**            | Period of AC voltage measured in the equiangular synchronization (delta bridge)                                              |
| **IdRef (pu)**                    | DC current reference                                                                                                         |
| **VdRref (pu)**                   | DC voltage reference                                                                                                         |
| **Mu (degree)**                   | Commutation (overlap) angle                                                                                                  |
| **Gamma (degree)**                | Extinction angle                                                                                                             |
| **Alpha (degree)**                | Firing delay angle generated by the regulation system                                                                        |
| **Deblocked\_label**              | Unblocking status flag                                                                                                       |
| **CmdComFail**                    | Command to simulate a switching (commutation) failure                                                                        |
| **CmdInvMode**                    | Rectifier/inverter mode (0 = rectifier; 1 = inverter)                                                                        |
| **ComFail**                       | Detection signal for switching failure on Y or delta bridge                                                                  |
| **AlphaRet**                      | Signal specifying the forced retard mode                                                                                     |
| **RatioXfo\_label (pu)**          | Normalized transformer ratio (Ns/Np) of the converter transformer                                                            |
| **syn\_Vd0\_level (pu)**          | Mean of the maximum ideal DC voltage in equidistant synchronization                                                          |
| **syn\_Alpha\_Osc (degree)**      | Firing delay angle reflecting the oscillator phase (equidistant synchronization)                                             |
| **syn\_Alpha\_measured (degree)** | Measured firing delay angle (equidistant synchronization)                                                                    |
| **syn\_Delta\_alpha (degree)**    | Oscillator phase variation (positive = lag; negative = lead) in equidistant synchronization                                  |
| **syn\_Vac\_ZC\_number**          | Zero-crossing count of switching voltages \[0–11] (equidistant synchronization)                                              |
| **syn\_Firing\_pulse\_number**    | Firing count of valves \[0–11] (equidistant synchronization)                                                                 |
| **sys\_Frequency (Hz)**           | Measured AC voltage frequency (equidistant synchronization)                                                                  |

## Characteristics and limitations

| Characteristic        | Value                                                                      |
| --------------------- | -------------------------------------------------------------------------- |
| Pulse configurations  | 6-pulse and 12-pulse                                                       |
| Operating modes       | Rectifier and inverter                                                     |
| Synchronization modes | Equiangular (6- and 12-pulse) and equidistant (12-pulse option)            |
| Supported valve types | Thyristor; Diode; GTO+Diode (with coordinated switching)                   |
| Tap changer           | Supported on converter transformers (rectifier and inverter)               |
| Fault simulation      | Valve short circuit; resistive grounded DC fault; commutation failure      |
| Protections           | DC fault protection (rectifier); Commutation-failure protection (inverter) |


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/network-facts-and-hvdc/lcc-6-12-pulse-rectifier-inverter-oriented.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.