> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/network-facts-and-hvdc/thyristor-controlled-reactor-and-thyristor-switched-capacitor.md).

# Thyristor Controlled Reactor & Thyristor Switched Capacitor

## Description

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-a2bf30aac00544fea46c3385a3446aa5a20c8be4%2Fimage%20(1092).png?alt=media" alt="" width="367"><figcaption></figcaption></figure>

The **Thyristor Controlled Reactor** & **Thyristor Switched Capacitor** blocks, located in the **Network Switches and Breakers** library, models a thyristor-controlled reactor (TCR) and a thyristor-switched capacitor (TSC). The TCR branch is a specific case of the TSC branch. Resistances R and r represent ohmic losses in the capacitor and the reactor, respectively. You can ignore either element by setting its value to zero in the mask.

The two resistances, the capacitor, and the reactor form an internal black box. As a result, voltages across the resistances and the reactor are not directly measurable. The capacitor voltage and the thyristor voltages are computed and available as signals.

## Mask parameters

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-3fb54fe3025b12a2b1c1fb4d092b15d334ae2a03%2Fimage%20(444).png?alt=media" alt="" width="552"><figcaption></figcaption></figure>

<table><thead><tr><th width="201.20001220703125">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Control Type</strong></td><td>Select the control source for the block (external inputs or sensors).</td></tr><tr><td><strong>Precision Valve</strong></td><td>Enable to correct digitization errors; disable to turn off this feature. Possible values: {Enable, Disable}.</td></tr><tr><td><strong>Connections</strong></td><td>Connection type. Options: Y ground; Y floating; Delta.</td></tr><tr><td><strong>r</strong></td><td>Resistance in parallel with the branch reactor (ohm) [0, 1e12].</td></tr><tr><td><strong>L</strong></td><td>Series inductance (H) [0, 1e12].</td></tr><tr><td><strong>R</strong></td><td>Branch resistance (ohm) [0, 1e12].</td></tr><tr><td><strong>C</strong></td><td>Branch capacitance. Range: (0, 1e12].</td></tr><tr><td><strong>Rsnubber</strong></td><td>Snubber resistance (ohm) [0, 1e12].</td></tr><tr><td><strong>Csnubber</strong></td><td>Snubber capacitance (F) [0, 1e12].</td></tr><tr><td><strong>Ropen</strong></td><td>Valve resistance when open (ohm) [0, 1e12].</td></tr><tr><td><strong>Rclose</strong></td><td>Valve resistance when closed (ohm) [0, 1e12].</td></tr><tr><td><strong>Imin</strong></td><td>Chopping current (A)[0, 1e12].</td></tr><tr><td><strong>Fbov</strong></td><td>Forward break overvoltage (V) [0, 1e12].</td></tr><tr><td><strong>Rbov</strong></td><td>Reverse break overvoltage (V)[0, 1e12].</td></tr><tr><td><strong>Tq</strong></td><td>Time for the valve to stop conducting (s) [0, 1e12].</td></tr><tr><td><strong>Vmin</strong></td><td>Minimum forward voltage across the valve to conduct (V) [0, 1e12].</td></tr></tbody></table>

## Conserving ports

<table><thead><tr><th width="205.20001220703125">Port</th><th>Description</th></tr></thead><tbody><tr><td><strong>Net_1</strong></td><td>Network connection (supports 3-phase connections only).</td></tr></tbody></table>

## Inputs

<table><thead><tr><th width="200.39996337890625">Input</th><th>Description</th></tr></thead><tbody><tr><td><strong>D</strong></td><td>Delay used for the precision valve, measured from the switching instant to the current time step.</td></tr><tr><td><strong>P</strong></td><td>Binary-coded firing pulses.</td></tr></tbody></table>

## Outputs

This block has no outputs.

## Signals available for monitoring and external I/O connections (via sensors form)

All block inputs and outputs are available as signals for monitoring and for external I/O connections.

Additional signals are also available and are listed below with their descriptions.

<table><thead><tr><th width="200.4000244140625">Signal</th><th>Description</th></tr></thead><tbody><tr><td><strong>CMD12_x</strong> (x = a, b, c)</td><td>Firing pulse of the positive valve in phase x.</td></tr><tr><td><strong>CMD21_x</strong> (x = a, b, c)</td><td>Firing pulse of the negative valve in phase x.</td></tr><tr><td><strong>I_x (A)</strong> (x = a, b, c)</td><td>Branch current in phase x.</td></tr><tr><td><strong>STATE12_x</strong> (x = a, b, c)</td><td>State of the positive valve in phase x.</td></tr><tr><td><strong>STATE21_x</strong> (x = a, b, c)</td><td>State of the negative valve in phase x.</td></tr><tr><td><strong>DelayImpInt</strong></td><td>Firing delay (fraction of the calculation step) calculated by the internal command (s)</td></tr><tr><td><strong>DelayImpExt</strong></td><td>Firing delay (fraction of the calculation step) calculated by an external command (s)</td></tr><tr><td><strong>DelayImp</strong></td><td>Firing delay (fraction of the calculation step) (s)</td></tr><tr><td><strong>DelayImpUsed</strong></td><td>Firing delay (fraction of the calculation step) actually used (s)</td></tr></tbody></table>


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/network-facts-and-hvdc/thyristor-controlled-reactor-and-thyristor-switched-capacitor.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.