> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/network-lines-and-cables/pi-section-6-ph.md).

# PI Section, 6-ph

## Description

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-bd236392b25f8351b9141f9ea62bf466d089e67b%2Fimage%20(1131).png?alt=media" alt="" width="323"><figcaption></figcaption></figure>

The **PI section 6-phase** block, located in the **Network Lines and Cables** library, is mainly used for short transmission lines.

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-430ecdaa94b73a9ab119033c6e7ae63db3f65732%2Fimage%20(1125).png?alt=media" alt="" width="393"><figcaption><p>Equivalent circuit</p></figcaption></figure>

It assumes identical capacitances on both sides and coupled RL branches.

For 6-phase PI lines, the parameters are the same as for 3-phase PI lines, except that the R, L, and C matrices have dimensions 6x6 (instead of 3x3) to represent six conductors. A 6-phase PI model can represent a double-circuit transmission line. The neutral coupling between both circuits (mutual impedance) is represented only in zero sequences.

## Mask parameters

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-a0aa4c7f20b5b7f8b6d2f76ac000cfd5bbcaf720%2FPI6.jpg?alt=media" alt=""><figcaption></figcaption></figure>

{% tabs %}
{% tab title="General" %}

| Parameter                                            | Description                                                                                                                                                                                                                                                  |
| ---------------------------------------------------- | ------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------ |
| **Description**                                      | Use this field to add information about the component.                                                                                                                                                                                                       |
| **EMTP (.pun) file for line parameters calculation** | Path to the EMTP file (pun file) containing the line parameters. the EMTP “.pun” format is **not allowed with this model**.                                                                                                                                  |
| **Type**                                             | <p>The line data can be taken using Matrix or Sequence parameters.<br><strong>Matrix (0)</strong>: Untransposed line. The data is filled in the matrices tab.<br><strong>Sequence (1)</strong>: Transposed line. The data is filled in the sequences tab</p> |
| **Line Length**                                      | The length of the line (km), length \[0, 1e64]                                                                                                                                                                                                               |
| **Base power (perPhase)**                            | Base value for PU conversion (MVA) per phase, pBase \[1, 1e64]                                                                                                                                                                                               |
| **Base voltage (rmsLN)**                             | Base value for PU conversion (kV) rms LN, vBase \[1, 1e64]                                                                                                                                                                                                   |
| **Base frequency**                                   | Base value for PU conversion (Hz), fBase \[1, 1e64]                                                                                                                                                                                                          |
| {% endtab %}                                         |                                                                                                                                                                                                                                                              |

{% tab title="Matrix" %}

| Parameter           | Description                                |
| ------------------- | ------------------------------------------ |
| **Resistance - R**  | Resistance matrix (Ω/km) R \[-1e64, 1e64]  |
| **Inductance - L**  | Inductance matrix (H/km), L \[-1e64, 1e64] |
| **Capacitance - C** | Capacitance matrix (F/km, C \[-1e64, 1e64] |
| {% endtab %}        |                                            |

{% tab title="Sequence" %}
**Self impedance - Line 1**

| Parameter | Description                                                                     |
| --------- | ------------------------------------------------------------------------------- |
| **R**     | Resistance value for Zero and Positive sequences ( Ω/km), Rself1 \[-1e64, 1e64] |
| **L**     | Inductance value for Zero and Positive sequences (H/km), Lself1 \[-1e64, 1e64]  |
| **C**     | Capacitance value for Zero and Positive sequences (F/km), Cself1 \[-1e64, 1e64] |

**Self impedance - Line 2**

| Parameter | Description                                                                     |
| --------- | ------------------------------------------------------------------------------- |
| **R**     | Resistance value for Zero and Positive sequences ( Ω/km), Rself2 \[-1e64, 1e64] |
| **L**     | Inductance value for Zero and Positive sequences (H/km), Lself2 \[-1e64, 1e64]  |
| **C**     | Capacitance value for Zero and Positive sequences (F/km), Cself2 \[-1e64, 1e64] |

**Self impedance - Line 3**

| Parameter    | Description                                                                     |
| ------------ | ------------------------------------------------------------------------------- |
| **R**        | Resistance value for Zero and Positive sequences ( Ω/km), Rself3 \[-1e64, 1e64] |
| **L**        | Inductance value for Zero and Positive sequences (H/km), Lself3 \[-1e64, 1e64]  |
| **C**        | Capacitance value for Zero and Positive sequences (F/km), Cself3 \[-1e64, 1e64] |
| {% endtab %} |                                                                                 |

{% tab title="Line Generator" %}
The EMTP “.pun” format is not allowed with this model. However, the electrical parameters of PI lines can be calculated using the Line Generator.\
For more information see [Line Parameter Generator](https://github.com/Opal-RT-Technologies/product-docs-hypersim/tree/release-2026.4/model-and-simulation/use-parameter-generators/line-parameters/README.md)
{% endtab %}
{% endtabs %}

## Conserving ports

| Port                 | Description                                                             |
| -------------------- | ----------------------------------------------------------------------- |
| **net\_1\_1(a,b,c)** | Network connection of phases (a,b,c) of the **left (+)** side of line 1 |
| **net\_1\_2(a,b,c)** | Network connection of phases (a,b,c) of the **right** side of line 1    |
| **net\_2\_1(a,b,c)** | Network connection of phases (a,b,c) of the **left (+)** side of line 2 |
| **net\_2\_2(a,b,c)** | Network connection of phases (a,b,c) of the **right** side of line 2    |

## Inputs

This block has no inputs.

## Outputs

This block has no outputs.

## Signals available for monitoring and external I/O connections (via sensors form)

All block inputs and outputs are available as signals for monitoring and for external I/O connections.

Additional signals are also available and are listed below with their descriptions.

| Signal          | Description                                             |
| --------------- | ------------------------------------------------------- |
| **I1.1(a,b,c)** | Current (A) in each phase at **left (+)** end of line 1 |
| **I1.2(a,b,c)** | Current (A) in each phase at **right** end of line 1    |
| **I1.1(a,b,c)** | Current (A) in each phase at **left (+)** end of line 2 |
| **I2.2(a,b,c)** | Current (A) in each phase at **right** end of line 2    |


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/network-lines-and-cables/pi-section-6-ph.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.