> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/network-machines/synchronous-machine-pu-standard.md).

# Synchronous Machine (pu Standard)

## Description

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-8d5cd52b4a650a244549ebd5bf0268908218755b%2Fimage%20(347).png?alt=media" alt=""><figcaption></figcaption></figure>

The **Synchronous Machine (SM)** block, located in the **Network Machines** library, implements a Norton equivalent (non-iterative) model of a synchronous machine. Electrical parameters must be specified as per-unit values. The machine is externally controlled through the mechanical power or mechanical torque and the excitation input.

Key features include:

* **Dampers:** up to three damper windings (one on the d-axis and two on the q-axis)
* **Magnetic saturation:** total, independent, or d-axis only
* **Stator connection:** wye with neutral, wye grounded, or delta
* **Shaft:** up to six masses including the exciter mass

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-f7136accb0ff986e3df117bbb4dcf03933de78f9%2Fimage%20(1177).png?alt=media" alt=""><figcaption></figcaption></figure>

The synchronous machine participates in the load flow as a source behind an impedance and can be configured as a swing (reference) bus, PV bus, or PQ bus.

{% hint style="info" %}
**This model does not take into account hysteresis.** Under certain conditions some models of the machine may differ since the model of the synchronized machine-implemented is non-iterative.
{% endhint %}

### Base values for per-unit conversion

| Base value                                                               | Description                                     |
| ------------------------------------------------------------------------ | ----------------------------------------------- |
| $$S\_{base} = S\_{rated}$$                                               | Base power                                      |
| $$V\_{base\_stator} = \sqrt{\frac{2}{3}},V\_{LL}$$                       | Base stator voltage (peak) for wye connection   |
| $$V\_{base\_stator} = \sqrt{2}, V\_{LL}$$                                | Base stator voltage (peak) for delta connection |
| $$I\_{base\_stator} = \frac{S\_{base}}{3, V\_{base\_stator}}$$           | Base stator current (peak)                      |
| $$T\_{base} = \frac{3}{2}, \frac{p}{2}, \frac{S\_{base}}{\omega\_{sm}}$$ | Base mechanical torque                          |
| $$\Psi\_{base} = \frac{V\_{base\_stator}}{\omega\_{s}}$$                 | Base flux (peak)                                |

### Model equations

The Park transform is defined as follows:

$$
T = \frac{2}{3} \begin{bmatrix} \cos \theta\_{s} & \cos \left(\theta\_{s}-\frac{2 \pi}{3}\right) & \cos \left(\theta\_{s}+\frac{2 \pi}{3}\right) \\\[6pt] -\sin \theta\_{s} & -\sin \left(\theta\_{s}-\frac{2 \pi}{3}\right) & -\sin \left(\theta\_{s}+\frac{2 \pi}{3}\right) \\\[6pt]\ \frac{1}{2} & \frac{1}{2} & \frac{1}{2} \end{bmatrix}
$$

where $$\theta\_s$$ is the angle between phase a and the d-axis.

## Electrical system (p.u. and generating convention) equations

$$
v\_{q} = -r\_{s} i\_{q} + \frac{\omega\_{r}}{\omega\_{s}} \psi\_{d} + \frac{1}{\omega\_{s}} \frac{d \psi\_{q}}{dt} \\\[8pt] v\_{d} = -r\_{s} i\_{d} - \frac{\omega\_{r}}{\omega\_{s}} \psi\_{q} + \frac{1}{\omega\_{s}} \frac{d \psi\_{d}}{dt}  \\\[8pt] v\_{0} = -r\_{s} i\_{0} + \frac{1}{\omega\_{s}} \frac{d \psi\_{0}}{dt}  \\\[8pt] 0 = r\_{D1} i\_{D1} + \frac{1}{\omega\_{s}} \frac{d \psi\_{D1}}{dt}  \\\[8pt]
0 = r\_{D2} i\_{D2} + \frac{1}{\omega\_{s}} \frac{d \psi\_{D2}}{dt}  \\\[8pt]
0 = r\_{Q1} i\_{Q1} + \frac{1}{\omega\_{s}} \frac{d \psi\_{Q1}}{dt}  \\\[8pt]
0 = r\_{Q2} i\_{Q2} + \frac{1}{\omega\_{s}} \frac{d \psi\_{Q2}}{dt}
$$

## Flux current (pu)

$$
\psi\_{q} = -x\_{q} i\_{q} + x\_{mq} i\_{Q1} + x\_{mq} i\_{Q2}\\\[8pt]
\psi\_{d} = -x\_{d} i\_{d} + x\_{md} i\_{D1} + x\_{md} i\_{D2} + \psi\_{f}\\\[8pt] \psi\_{0} = -x\_{0} i\_{0}\\\[8pt]
\psi\_{D1} = -x\_{md} i\_{d} + x\_{D1} i\_{D1} + x\_{md} i\_{D2} + \psi\_{f}\\\[8pt]
\psi\_{D2} = -x\_{md} i\_{d} + x\_{D2} i\_{D2} + x\_{md} i\_{D1} + \psi\_{f}\\\[8pt]
\psi\_{Q1} = -x\_{mq} i\_{q} + x\_{Q1} i\_{Q1} + x\_{mq} i\_{Q2}\\\[8pt]
\psi\_{Q2} = -x\_{mq} i\_{q} + x\_{Q2} i\_{Q2} + x\_{mq} i\_{Q1}
$$

\
where $$\omega\_r$$ is the electric speed (rad / s) and $$\psi\_f$$ the flux produced by the permanent magnets (pu).

## Reactance relationships (pu)

Since the flux equations are in per-unit, any reactance can be equivalently specified as an inductance.

$$
x\_{d} = x\_{md} + x\_{l} \\\[8pt]
x\_{q} = x\_{mq} + x\_{l} \\\[8pt]
x\_{D1} = x\_{md} + x\_{lD1} \\\[8pt]
x\_{D2} = x\_{md} + x\_{lD2}\\\[8pt]
x\_{Q1} = x\_{mq} + x\_{lQ1} \\\[8pt]
x\_{Q2} = x\_{mq} + x\_{lQ2}
$$

## Electromagnetic torque (pu)

$$
t\_{em} = \psi\_{d} i\_{q} - \psi\_{q} i\_{d}
$$

## Mechanical equations (mass i)

$$
2 H\_{i} \frac{d \omega\_{im}}{dt} = \\\[8pt]
T\_{im} - T\_{em} - K\_{di} \omega\_{im} - D\_{i}(\omega\_{im} - \omega\_{sm}) - D\_{i,i-1}(\omega\_{im} - \omega\_{(i-1)m}) - D\_{i,i+1}(\omega\_{im} - \omega\_{(i+1)m})\\\[8pt] - K\_{i,i-1}(\delta\_{im} - \delta\_{(i-1)m}) - K\_{i,i+1}(\delta\_{im} - \delta\_{(i+1)m})\\\[10pt]
\frac{d \delta\_{im}}{dt} = \omega\_{im} - \omega\_{sm}
$$

Where: $$T\_{im}$$ is the mechanical torque developed on the i-th mass (Nm); $$T\_{em}$$ is the electromagnetic torque developed by the PMSM (Nm); $$\omega\_{im}$$ is the mechanical speed of mass i (rad/s); $$\omega\_{sm}$$ is the mechanical synchronous speed (rad/s); $$\delta\_{im}$$ is the mechanical angle of mass i; $$K\_{di}$$ is the absolute damping coefficient (Nm/rad/s); $$D\_{i}$$ is the self damping coefficient (Nm/rad/s); $$D\_{i,j}$$ is the mutual damping coefficient (Nm/rad/s); $$K\_{i,j}$$ is the angular stiffness (Nm/rad); $$H\_{i}$$ is the inertia constant (s).

## No-load rotor voltage (pu), seen from the stator

$$
E\_{fd} = \varpi\_{r},L^{uns}*{md},\frac{v{f}}{r*{f}}
$$

## Field voltage independent of speed deviation

$$
V\_{fd} = L^{uns}*{md},\frac{v{f}}{r*{f}}
$$

## Field voltage dependent on speed deviation

$$
E\_{fd} = \varpi\_{r},V\_{fd}
$$

## At steady state and fundamental frequency (ωr = 1):

$$
E\_{fd} = V\_{fd}
$$

{% hint style="info" %}
When the machine operates as a motor, the mechanical torque is negative; it is positive in generator mode.
{% endhint %}

## Mask parameters

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-99d0f4f3cb2f01d9d64e748e4a6792b471adff1f%2Fe.jpg?alt=media" alt=""><figcaption></figcaption></figure>

{% tabs %}
{% tab title="Electrical parameters" %}

<table><thead><tr><th width="209">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Base power</strong></td><td>Nominal power (MVA)</td></tr><tr><td><strong>Base voltage</strong></td><td>Nominal line-to-line voltage (kV)</td></tr><tr><td><strong>Frequency</strong></td><td>Nominal frequency (Hz)</td></tr><tr><td><strong>Number of poles</strong></td><td>Number of poles (-)</td></tr><tr><td><strong>d-axis damper</strong></td><td>Number of dampers on d-axis (-)</td></tr><tr><td><strong>q-axis damper</strong></td><td>Number of dampers on q-axis (-)</td></tr><tr><td><strong>Stator connection</strong></td><td>Stator winding connection (wye or delta)</td></tr><tr><td><strong>Field current</strong></td><td>Field current that produces 1 pu air-gap voltage, used to compute pu values of current inputs to the saturation table (A) (not available in the current version)</td></tr><tr><td><strong>Rs</strong></td><td>Stator resistance (pu)</td></tr><tr><td><strong>Xl</strong></td><td>Stator leakage reactance (pu)</td></tr><tr><td><strong>X0</strong></td><td>Zero-sequence reactance (pu)</td></tr><tr><td><strong>Xc</strong></td><td>Canay reactance (pu)</td></tr><tr><td><strong>Xd</strong></td><td>d-axis synchronous reactance (pu)</td></tr><tr><td><strong>Xq</strong></td><td>q-axis synchronous reactance (pu)</td></tr><tr><td><strong>Xpd</strong></td><td>q-axis transient reactance (pu) (must be defined when including any number of d-axis dampers; ignored otherwise)</td></tr><tr><td><strong>Xpq</strong></td><td>q-axis transient reactance (pu) (must be defined when including any number of q-axis dampers; ignored otherwise)</td></tr><tr><td><strong>Xppd</strong></td><td>d-axis subtransient reactance (pu) (must be defined when including one d-axis damper; ignored otherwise)</td></tr><tr><td><strong>Xppq</strong></td><td>q-axis subtransient reactance (pu) (must be defined when including two q-axis dampers; ignored otherwise)</td></tr><tr><td><strong>Tpd0</strong></td><td>d-axis open-circuit transient time constant (s) (must be defined when including any number of d-axis dampers; ignored otherwise)</td></tr><tr><td><strong>Tpq0</strong></td><td>q-axis open-circuit transient time constant (s) (must be defined when including any number of q-axis dampers; ignored otherwise)</td></tr><tr><td><strong>Tppd0</strong></td><td>d-axis open-circuit subtransient time constant (s) (must be defined when including one d-axis damper; ignored otherwise)</td></tr><tr><td><strong>Tppq0</strong></td><td>d-axis open-circuit subtransient time constant (s) (must be defined when including two q-axis dampers; ignored otherwise)</td></tr></tbody></table>
{% endtab %}

{% tab title="Mechanical data" %}

<table><thead><tr><th width="211">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Number of mass</strong></td><td>Number of masses</td></tr><tr><td><strong>H</strong></td><td>Inertia constants (s). Depending on the number of masses, provide values for: Generator, Low Pressure Turbine B (LPB), Low Pressure Turbine A (LPA), Intermediate Pressure (IP) Turbine, High Pressure (HP) Turbine.</td></tr><tr><td><strong>Kd</strong></td><td>Absolute damping coefficients (Nm/rad/s). Depending on the number of masses, provide values for: Generator, Turbine LPB, Turbine LPA, Turbine IP, Turbine HP.</td></tr><tr><td><strong>Kij</strong></td><td>Stiffness coefficients (Nm/rad). Depending on the number of masses, provide values for: Generator–Turbine LPB, LPB–Turbine LPA, Turbine LPA–Turbine IP, Turbine IP–Turbine HP.</td></tr><tr><td><strong>D</strong></td><td>Self damping coefficients (Nm/rad/s). Depending on the number of masses, provide values for: Generator, Turbine LPB, Turbine LPA, Turbine IP, Turbine HP.</td></tr><tr><td><strong>Dij</strong></td><td>Mutual speed deviation damping coefficients (Nm/rad/s). Depending on the number of masses, provide values for: Generator–Turbine LPB, LPB–Turbine LPA, Turbine LPA–Turbine IP, Turbine IP–Turbine HP.</td></tr><tr><td><strong>F</strong></td><td>Fractions of total external torque applied to each mass (-). Depending on the number of masses, provide fractions for LPB turbine, LPA turbine, IP turbine, HP turbine. The sum of all fractions must equal 1.</td></tr><tr><td><strong>Exciter Type</strong></td><td>Exciter type (rotating or static)</td></tr><tr><td><strong>H (Exciter)</strong></td><td>Exciter inertia constant (s)</td></tr><tr><td><strong>Kd (Exciter)</strong></td><td>Exciter absolute damping coefficient (Nm/rad/s)</td></tr><tr><td><strong>D (Exciter)</strong></td><td>Exciter self damping coefficient (Nm/rad/s)</td></tr><tr><td><strong>D (Generator–Exciter)</strong></td><td>Mutual deviation speed damping coefficient between generator and exciter (Nm/rad/s)</td></tr><tr><td><strong>K (Generator–Exciter)</strong></td><td>Stiffness coefficient between generator and exciter (Nm/rad)</td></tr></tbody></table>
{% endtab %}

{% tab title="Control" %}

<table><thead><tr><th width="210">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Excitation control</strong></td><td><p>Excitation control mode:</p><ul><li>Constant: constant field voltage from load flow</li><li>External: Field voltage (Efd) from exciter</li><li>External: Field voltage (Vfd) from exciter</li></ul></td></tr><tr><td><strong>Mechanical control</strong></td><td><p>Mechanical control mode:</p><ul><li>Constant: constant mechanical power from load flow</li><li>Mechanical power: mechanical power from prime mover</li><li>Mechanical torque: mechanical torque from prime mover</li></ul></td></tr></tbody></table>
{% endtab %}

{% tab title="Saturation" %}

<table><thead><tr><th width="209">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Saturation</strong></td><td>Enable or disable independent, total, or d-axis-only saturation</td></tr><tr><td><strong>d-axis saturation curve points</strong></td><td>Number of points on the d-axis saturation curve (-) (maximum 10)</td></tr><tr><td><strong>Imd</strong></td><td>d-axis magnetizing current points of the saturation curve (pu)</td></tr><tr><td><strong>Fluxmd</strong></td><td>d-axis magnetizing flux points of the saturation curve (pu)</td></tr><tr><td><strong>q-axis saturation curve points</strong></td><td>Number of points on the q-axis saturation curve (-) (maximum 10)</td></tr><tr><td><strong>Imq</strong></td><td>q-axis magnetizing current points of the saturation curve (pu)</td></tr><tr><td><strong>Fluxmq</strong></td><td>q-axis magnetizing flux points of the saturation curve (pu)</td></tr></tbody></table>

{% hint style="info" %}
The magnetizing current of the d- or q-axis is defined in pu of the exciter (i.e., based on the rotor current). For example, if a field current of 1000 A produces an air-gap flux of 1 pu, then this current is 1 pu. If a field current of 1500 A produces an air-gap flux of 1.5 pu, then the current in pu is $$\frac{1500\~\text{A}}{1000\~\text{A}} = 1.5\~\text{pu}$$
{% endhint %}
{% endtab %}

{% tab title="Load flow " %}

<table><thead><tr><th width="211">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Type of bus</strong></td><td>Bus type: Swing, PV, or PQ</td></tr><tr><td><strong>Voltage</strong></td><td>Desired terminal voltage (pu)</td></tr><tr><td><strong>Angle</strong></td><td>Desired terminal voltage angle (deg)</td></tr><tr><td><strong>Active power</strong></td><td>Desired active power at the terminals (MW)</td></tr><tr><td><strong>Reactive power</strong></td><td>Desired reactive power at the terminals (MVAr)</td></tr><tr><td><strong>Minimum reactive power</strong></td><td>Minimum allowed reactive power at the terminals (MVAr)</td></tr><tr><td><strong>Maximum reactive power</strong></td><td>Maximum allowed reactive power at the terminals (MVAr)</td></tr></tbody></table>
{% endtab %}
{% endtabs %}

## Conserving ports

<table><thead><tr><th width="211">Port</th><th>Description</th></tr></thead><tbody><tr><td><strong>S</strong></td><td>AC stator connector (3-phase only)</td></tr><tr><td><strong>N</strong></td><td>AC neutral connector (single-phase only)</td></tr></tbody></table>

## Inputs

<table><thead><tr><th width="212">Input</th><th>Description</th></tr></thead><tbody><tr><td><strong>Vfd_i</strong></td><td>Speed-independent field voltage</td></tr><tr><td><strong>Tm_i</strong></td><td>Mechanical torque</td></tr><tr><td><strong>Pm_i</strong></td><td>Mechanical power</td></tr><tr><td><strong>Efd_i</strong></td><td>Speed-dependent field voltage</td></tr></tbody></table>

## Outputs

This block has no outputs.

## Signals available for monitoring and external I/O connections (via sensors form)

All block inputs and outputs are available as signals for monitoring and for external I/O connections.

Additional signals are also available and are listed below with their descriptions.

<table><thead><tr><th width="212">Signal</th><th>Description</th></tr></thead><tbody><tr><td><strong>Efd</strong></td><td>Speed-dependent field voltage (pu)</td></tr><tr><td><strong>Efd_ss</strong></td><td>Exciter field voltage calculated during load flow (pu); used to initialize exciter blocks (steady state)</td></tr><tr><td><strong>Flux0s</strong></td><td>Zero-sequence stator flux (pu)</td></tr><tr><td><strong>Fluxds</strong></td><td>d-axis stator flux (pu)</td></tr><tr><td><strong>Fluxm</strong></td><td>Mutual magnetization flux (pu)</td></tr><tr><td><strong>Fluxmd</strong></td><td>d-axis mutual magnetization flux (pu)</td></tr><tr><td><strong>Fluxmq</strong></td><td>q-axis mutual magnetization flux (pu)</td></tr><tr><td><strong>Fluxqs</strong></td><td>q-axis stator flux (pu)</td></tr><tr><td><strong>I0s</strong></td><td>Zero-sequence stator current (pu)</td></tr><tr><td><strong>ID</strong></td><td>d-axis damper current (pu)</td></tr><tr><td><strong>IQ1</strong></td><td>Q1-axis damper current (pu)</td></tr><tr><td><strong>IQ2</strong></td><td>Q2-axis damper current (pu)</td></tr><tr><td><strong>Ias</strong></td><td>Phase A stator current (A)</td></tr><tr><td><strong>Ibs</strong></td><td>Phase B stator current (A)</td></tr><tr><td><strong>Ics</strong></td><td>Phase C stator current (A)</td></tr><tr><td><strong>Ids</strong></td><td>d-axis stator current (pu)</td></tr><tr><td><strong>If</strong></td><td>Field current (pu)</td></tr><tr><td><strong>Im</strong></td><td>Magnetizing current (pu)</td></tr><tr><td><strong>Imd</strong></td><td>d-axis magnetizing current (pu)</td></tr><tr><td><strong>Imq</strong></td><td>q-axis magnetizing current (pu)</td></tr><tr><td><strong>Iqs</strong></td><td>q-axis stator current (pu)</td></tr><tr><td><strong>Pmec</strong></td><td>Mechanical power of the turbine (Nm)</td></tr><tr><td><strong>Pmec_pu</strong></td><td>Mechanical power of the turbine (pu)</td></tr><tr><td><strong>Pmec_ss</strong></td><td>Mechanical power of the turbine calculated during load flow (pu); used to initialize turbine blocks</td></tr><tr><td><strong>PowerAngle</strong></td><td>Machine load angle (rad)</td></tr><tr><td><strong>Ps</strong></td><td>Active power (W)</td></tr><tr><td><strong>Ps_pu</strong></td><td>Active power (pu)</td></tr><tr><td><strong>Qs</strong></td><td>Reactive power (VAr)</td></tr><tr><td><strong>RotorAngle</strong></td><td>Rotor angle of the synchronous machine, relative to the synchronous reference frame (rad)</td></tr><tr><td><strong>RotorAngle_EXC</strong></td><td>Rotor angle of the exciter mass, relative to the synchronous reference frame (rad)</td></tr><tr><td><strong>RotorAngle_HP</strong></td><td>Rotor angle of the HP turbine mass, relative to the synchronous reference frame (rad)</td></tr><tr><td><strong>RotorAngle_IP</strong></td><td>Rotor angle of the IP turbine mass, relative to the synchronous reference frame (rad)</td></tr><tr><td><strong>RotorAngle_LPA</strong></td><td>Rotor angle of the LPA turbine mass, relative to the synchronous reference frame (rad)</td></tr><tr><td><strong>RotorAngle_LPB</strong></td><td>Rotor angle of the LPB turbine mass, relative to the synchronous reference frame (rad)</td></tr><tr><td><strong>Tem</strong></td><td>Electromagnetic torque of the synchronous machine (Nm)</td></tr><tr><td><strong>Tem_pu</strong></td><td>Electromagnetic torque of the synchronous machine (pu)</td></tr><tr><td><strong>Texc</strong></td><td>Electromagnetic torque of the exciter (pu)</td></tr><tr><td><strong>ThetaS</strong></td><td>Electrical rotor angle (angle between phase A axis and d-axis) (rad)</td></tr><tr><td><strong>Tmec</strong></td><td>Mechanical torque of the turbine (Nm)</td></tr><tr><td><strong>Tmec_GEN_EXC</strong></td><td>Mechanical torque between the synchronous machine mass and the exciter (pu)</td></tr><tr><td><strong>Tmec_HP</strong></td><td>Mechanical torque applied to the HP turbine mass (pu)</td></tr><tr><td><strong>Tmec_HP_IP</strong></td><td>Mechanical torque between HP and IP turbine masses (pu)</td></tr><tr><td><strong>Tmec_IP</strong></td><td>Mechanical torque applied to the IP turbine mass (pu)</td></tr><tr><td><strong>Tmec_IP_LPA</strong></td><td>Mechanical torque between IP and LPA turbine masses (pu)</td></tr><tr><td><strong>Tmec_LPA</strong></td><td>Mechanical torque applied to the LPA turbine mass (pu)</td></tr><tr><td><strong>Tmec_LPA_LPB</strong></td><td>Mechanical torque between LPA and LPB turbine masses (pu)</td></tr><tr><td><strong>Tmec_LPB</strong></td><td>Mechanical torque applied to the LPB turbine mass (pu)</td></tr><tr><td><strong>Tmec_LPB_GEN</strong></td><td>Mechanical torque between LPB turbine mass and the synchronous machine (pu)</td></tr><tr><td><strong>Tmec_pu</strong></td><td>Mechanical torque of the turbine (pu)</td></tr><tr><td><strong>V0s</strong></td><td>Zero-sequence stator voltage (pu)</td></tr><tr><td><strong>Vds</strong></td><td>d-axis stator voltage (pu)</td></tr><tr><td><strong>Vqs</strong></td><td>q-axis stator voltage (pu)</td></tr><tr><td><strong>Vfd</strong></td><td>Speed-independent field voltage (pu)</td></tr><tr><td><strong>Vt</strong></td><td>Machine terminal voltage (pu)</td></tr><tr><td><strong>Wm</strong></td><td>Mechanical or electrical speed of the machine (pu)</td></tr><tr><td><strong>Wm_EXC</strong></td><td>Mechanical or electrical speed of the exciter (pu)</td></tr><tr><td><strong>Wm_HP</strong></td><td>Mechanical or electrical speed of the HP turbine (pu)</td></tr><tr><td><strong>Wm_IP</strong></td><td>Mechanical or electrical speed of the IP turbine (pu)</td></tr><tr><td><strong>Wm_LPA</strong></td><td>Mechanical or electrical speed of the LPA turbine (pu)</td></tr><tr><td><strong>Wm_LPB</strong></td><td>Mechanical or electrical speed of the LPB turbine (pu)</td></tr><tr><td><strong>Wrpm</strong></td><td>Mechanical speed of the machine (r/min)</td></tr></tbody></table>

## References

\[1] *Power System Stability and Control*, P. Kundur, McGraw-Hill 1994

\[2] G. Sybille, Tarik Zabaiou, *Emergency Diesel-Generator and Asynchronous Motor*, Mathworks demo example, version: 2017B

\[3] *Power System Control and Stability*, 2nd edition, P. Mr. Anderson, A.A. Fouad, IEEE Press 2003


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/network-machines/synchronous-machine-pu-standard.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.