> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/network-measurements/cvt.md).

# CVT

## Description

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-a529fd3dc61539c76ef01f8d5297831b16a08763%2Fimage%20(1639).png?alt=media" alt=""><figcaption></figcaption></figure>

The **Capacitive Divider Transformer** block, located in the **Network Measurements library**, is a voltage transformer with capacitive coupling.

## Mask parameters

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-fd3f55a19801dc20d5d2c4a4b2e69275d315ecc6%2F10.png?alt=media" alt=""><figcaption></figcaption></figure>

{% tabs %}
{% tab title="General" %}

<table><thead><tr><th width="185.77783203125">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>C1, C2</strong></td><td>Capacitances of the voltage divider (farad or pu)</td></tr><tr><td><strong>Rc</strong></td><td>Tuning circuit resistance (ohm or pu)</td></tr><tr><td><strong>Lc</strong></td><td>Tuning circuit inductance (henry or pu)</td></tr><tr><td><strong>Cc</strong></td><td>Tuning circuit capacitance (farad or pu)</td></tr><tr><td><strong>R, RL, LL</strong></td><td>Load resistances (ohm or pu) and load inductance (henry or pu)</td></tr><tr><td><strong>Np</strong></td><td>Number of turns (default: np = 18240)</td></tr><tr><td><strong>Rp</strong></td><td>Leakage resistance (ohm or pu)</td></tr><tr><td><strong>Lp</strong></td><td>Leakage inductance (henry or pu)</td></tr><tr><td><strong>Cp</strong></td><td>Stray capacitance (farad)</td></tr><tr><td><strong>Rm</strong></td><td>Resistance (ohm) representing magnetization losses</td></tr><tr><td><strong>Ns</strong></td><td>Number of turns (default: ns = 100)</td></tr><tr><td><strong>Rs</strong></td><td>Leakage resistance (ohm or pu)</td></tr><tr><td><strong>Ls</strong></td><td>Leakage inductance (henry or pu)</td></tr></tbody></table>
{% endtab %}

{% tab title="Saturation" %}

<table><thead><tr><th width="225.77783203125">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Number of points</strong></td><td>Number of segments of the current-flux saturation curve; only the positive part of the curve must be specified, the negative part being completed by symmetry</td></tr><tr><td><strong>Saturation current</strong></td><td>The peak value of the current (ampere or pu) for each segment of the saturation curve. The origin (0.0, 0.0) is implied. The number of segments must be equal to the parameter “Number of points”.</td></tr><tr><td><strong>Saturation flux</strong></td><td>The peak value of the flux (volt-second or pu) for each segment of the saturation curve. The origin (0.0, 0.0) is implied. The number of segments must be equal to the parameter “Number of points”.</td></tr></tbody></table>
{% endtab %}
{% endtabs %}

## Conserving ports

| Port       | Description                                                    |
| ---------- | -------------------------------------------------------------- |
| **Net\_1** | Primary winding connection (supports only 3-phase connections) |

## Inputs

This block has no inputs.

## Outputs

This bock has not outputs

## Signals available for monitoring and external I/O connections (via sensors form)

All block inputs and outputs are available as signals for monitoring and for external I/O connections.

Additional signals are also available and are listed below with their descriptions.

| Signal          | Description                          |
| --------------- | ------------------------------------ |
| **VOUT(a,b,c)** | Output voltage (V)                   |
| **VMAG(a,b,c)** | Voltage in magnetization branch (V)  |
| **IMAG(a,b,c)** | Magnetization current (A)            |
| **FLUX(a,b,c)** | Mutual flux in the transformer (V.s) |


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/network-measurements/cvt.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.