> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/network-transformers/2-winding-3-phase-linear-transformer.md).

# 2 Winding 3 Phase Linear Transformer

## Description

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-c3718faa2beae54d13608e49100363fc513f75e2%2Fimage%20(1159).png?alt=media" alt=""><figcaption></figcaption></figure>

The **2-winding 3-phase linear transformer** block, located in the **Network Transformers** library, models a simple three-phase transformer with two windings. It is best used when core saturation is not simulated to reduce computation time.

## Mask parameters

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-1082313b7fa4424ed93a52d20e626d0f8f626448%2F3PLT.jpg?alt=media" alt=""><figcaption></figcaption></figure>

{% tabs %}
{% tab title="General" %}

<table><thead><tr><th width="240">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Description</strong></td><td>Free-text field for component information.</td></tr><tr><td><strong>Primary/secondary connection</strong></td><td><p>Winding connection type:</p><ul><li>Y ground: Grounded Y connection (uses the neutral impedance defined in the Neutral Impedance Parameters tab).</li><li>Y floating: Floating Y connection.</li><li>Y neutral: Y connection with an external impedance connected at input pin N1 or N2.</li><li>Delta lead: Delta connection with 30° lead.</li><li>Delta ground: Grounded delta connection (phase C grounded).</li><li>Delta lag: Delta connection with 30° lag.</li></ul></td></tr><tr><td><strong>Rm</strong></td><td>Equivalent resistance of iron losses of the magnetic circuit (Ω).</td></tr><tr><td><strong>Lm</strong></td><td>Magnetization inductance (H).</td></tr><tr><td><strong>Base primary/secondary winding voltage (rmsLL)</strong></td><td>Per-unit base voltage in kV rms line-to-line. The base and nominal voltages change if the corresponding winding connection switches between delta and Y.</td></tr><tr><td><strong>Base power (total)</strong></td><td>Per-unit base power in MVA.</td></tr><tr><td><strong>Base frequency</strong></td><td>Per-unit base frequency in Hz.</td></tr><tr><td><strong>Primary/secondary winding - Voltage (rmsLL)</strong></td><td>Rated winding voltage in kV. Expressed as kV rms line-to-line. The base and nominal voltages change if the corresponding winding connection switches between delta and Y.</td></tr><tr><td><strong>Primary/secondary winding - R1 R2</strong></td><td>Leakage resistance of the winding (Ω).</td></tr><tr><td><strong>Primary/secondary winding - L1 L2</strong></td><td>Leakage inductance of the winding (H).</td></tr></tbody></table>
{% endtab %}

{% tab title="Neutral impedance" %}

<table><thead><tr><th width="240.259765625">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>R1, R2</strong></td><td>Neutral resistance of the winding (Ω); applies only to Y ground.</td></tr><tr><td><strong>L1, L2</strong></td><td>Neutral inductance of the winding (H); applies only to Y ground.</td></tr><tr><td><strong>C1, C2</strong></td><td>Neutral capacitance of the winding (F); applies only to Y ground.</td></tr></tbody></table>
{% endtab %}
{% endtabs %}

## Conserving ports

<table><thead><tr><th width="200">Port</th><th>Description</th></tr></thead><tbody><tr><td><strong>Net_1</strong></td><td>Primary winding connection (supports only 3-phase connections).</td></tr><tr><td><strong>Net_2</strong></td><td>Secondary winding connection (supports only 3-phase connections).</td></tr><tr><td><strong>Net_N1</strong></td><td>Neutral connection for the primary winding (supports only 1-phase connections).</td></tr><tr><td><strong>Net_N2</strong></td><td>Neutral connection for the secondary winding (supports only 1-phase connections).</td></tr></tbody></table>

## Inputs

This block has no inputs.

## Outputs

This block has no outputs.

## Signals available for monitoring and external I/O connections (via sensors form)

All block inputs and outputs are available as signals for monitoring and for external I/O connections.

Additional signals are also available and are listed below with their descriptions.

<table><thead><tr><th width="201">Signal</th><th>Description</th></tr></thead><tbody><tr><td><strong>ILMAG(a,b,c)</strong></td><td>Magnetization current (A)</td></tr><tr><td><strong>IPRIM(a,b,c)</strong></td><td>Primary current (A)</td></tr><tr><td><strong>ISEC2(a,b,c</strong></td><td>Secondary current (A)</td></tr></tbody></table>


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/network-transformers/2-winding-3-phase-linear-transformer.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.