> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/network-transformers/2-winding-3-phase-saturable-autotransformer-with-internal-tertiary.md).

# 2 Winding 3 Phase Saturable Autotransformer with Internal Tertiary

## Description

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-53cb3ea24534aa6d63338acf97346e8833214529%2Fimage%20(368).png?alt=media" alt="" width="189"><figcaption></figcaption></figure>

The **2-Winding 3-Phase Saturable Autotransformer with Internal Tertiary** block, located in the **Network Transformers** library, implements an autotransformer with one tapping point. It is suitable for applications such as induction motor starting, transmission line voltage regulation, and voltage transformation when the primary-to-secondary ratio is close to unity.

### Internal Connection and Parameters <a href="#id-2-winding3-phasesaturableautotransformerwithinternaltertiary-internalconnectionandparameters" id="id-2-winding3-phasesaturableautotransformerwithinternaltertiary-internalconnectionandparameters"></a>

The internal connection of the autotransformer is shown below. Note that it is the phase C's terminal of tertiary which is grounded. The neutral point of the autotransformer is accessible via the single-phase "N" terminal.

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-bbf65a1fe7af84059fd7a549745d2c2d6871d62d%2Fimage%20(369).png?alt=media" alt=""><figcaption></figcaption></figure>

The main parameters (R<sub>12</sub>, X<sub>12</sub>, X<sub>13</sub>, X<sub>23</sub> and R<sub>3</sub>) are entered in "per unit" only. They are then used to determine the parameters by winding (R<sub>1</sub>, R<sub>2</sub>, R<sub>3</sub>, X<sub>1</sub>, X<sub>2</sub> and X<sub>3</sub>) as a function of the nominal voltages of the windings (N<sub>1</sub> and N<sub>2</sub>) according to the expressions below, N<sub>1</sub> and N<sub>2</sub> corresponds to the series winding and common winding.

$$
k = \frac{N\_2}{N\_1 + N\_2}\\\[8pt]

X\_1 = \frac{\frac{1+k}{1-k} X\_{12} + X\_{13} - X\_{23}}{2(1-k)}\\\[8pt]

X\_2 = \frac{X\_{12} - X\_{13} + X\_{23}}{2(1-k)}\\\[8pt]

X\_3 = \frac{-X\_{12} + X\_{13} + (1 - 2k)X\_{23}}{2(1-k)}
$$

* If **"Parameter calculation method" = Equal R1 R2**

$$
R\_1 = R\_2 = \frac{R\_{12}}{2(1-k)^2} \\\[8pt]

R\_3 = R\_{13} - R\_1(1-k)^2 - R\_2(k)^2
$$

* If **"Parameter calculation method" = Classic**

$$
R\_1 = \frac{\frac{1+k}{1-k} R\_{12} + R\_{13} - R\_{23}}{2(1-k)}\\\[8pt]
R\_2 = \frac{R\_{12} - R\_{13} + R\_{23}}{2(1-k)} \\\[8pt]
R\_3 = \frac{-R\_{12} + R\_{13} + (1 - 2k)R\_{23}}{2(1-k)}
$$

The values obtained are referenced to the primary nominal voltages (VbasePrimary = VnomSeries + VnomCommon), secondary (VbaseSecondary = VnomCommon) and tertiary (VbaseTertiary = VnomTertiary).

{% hint style="info" %}
For the moment, no protection against negative winding values has been implemented. The calculated winding values are visible from the netlist.
{% endhint %}

All other parameters are entered in the same way as for other HYPERSIM transformer models. The saturation is placed at the series winding and uses the nominal voltage of this winding for the "per unit" conversion.

### Load Flow and Initialization <a href="#id-2-winding3-phasesaturableautotransformerwithinternaltertiary-loadflowandinitialization" id="id-2-winding3-phasesaturableautotransformerwithinternaltertiary-loadflowandinitialization"></a>

The autotransformer sends the parameters of a standard equivalent transformer to the power flow algorithm.

$$
R\_1 = R\_2 = \frac{R\_{12}}{2} \\\[8pt]
X\_1 = \frac{X\_{12} + X\_{13} - X\_{23}}{2} \\\[8pt]
X\_2 = \frac{X\_{12} - X\_{13} + X\_{23}}{2}
$$

Tertiary winding is now considered for power flow.

Once the power flow calculation is performed, the values obtained are used to calculate the internal voltages and currents of the autotransformer taking into account the true topology.

## Mask parameters

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-900a9aeab3af117712e22a5f9d9342986f80db49%2F3phSA.jpg?alt=media" alt=""><figcaption></figcaption></figure>

{% tabs %}
{% tab title="General" %}

<table><thead><tr><th width="221">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Tertiary connection</strong></td><td>Select whether the delta-connected winding voltage leads or lags the star-connected winding voltage, or grounds phase C.</td></tr><tr><td><strong>Flux-Current characteristic model</strong></td><td>Choose between saturation only or saturation with hysteresis.</td></tr><tr><td><strong>Iteration in saturation model</strong></td><td>Enable to improve accuracy when the saturation segment changes (increases computation time); disable to reduce computation time.</td></tr><tr><td><strong>Base serial/common/tertiary winding voltage (rmsLL)</strong></td><td>Base value for per-unit (pu) conversion (kV).</td></tr><tr><td><strong>Rm</strong></td><td>Equivalent resistance of magnetic circuit iron losses (Ω).</td></tr><tr><td><strong>Base primary/secondary winding voltage (rmsLL)</strong></td><td><p>Base value for per-unit (pu) conversion (kV).</p><ul><li>Voltage expressed in kV rms line-to-line.</li><li>This base voltage and nominal voltage change if the winding connection switches between delta and Y.</li></ul></td></tr><tr><td><strong>Base power (total)</strong></td><td>Base value for per-unit (pu) conversion (MVA).</td></tr><tr><td><strong>Base frequency</strong></td><td>Base value for per-unit (pu) conversion (Hz).</td></tr><tr><td><strong>Parameter calculation method</strong></td><td><p>Select how winding resistances are determined:</p><ul><li><strong>Equal R1 R2</strong>: The series winding resistance equals the common winding resistance.</li><li><strong>Classic</strong>: R1, R2, and R3 are computed from between-winding resistances R12, R13, and R23.</li></ul><p>The following expressions are used to determine winding parameters as a function of nominal winding voltages, where N1 corresponds to the series winding and N2 to the common winding; k = N2 / (N1 + N2).</p><p>If <strong>Equal R1 R2</strong>:</p><p>If <strong>Classic</strong>:</p><p>The values obtained are referenced to the base voltages:</p><ul><li>VbasePrimary = VnomSeries + VnomCommon</li><li>VbaseSecondary = VnomCommon</li><li>VbaseTertiary = VnomTertiary</li></ul></td></tr><tr><td><strong>R12</strong></td><td>Primary-to-secondary resistance (pu).</td></tr><tr><td><strong>R13</strong></td><td>Primary-to-tertiary resistance (pu).</td></tr><tr><td><strong>R23</strong></td><td>Secondary-to-tertiary resistance (pu).</td></tr><tr><td><strong>L12</strong></td><td>Primary-to-secondary inductance (pu).</td></tr><tr><td><strong>L13</strong></td><td>Primary-to-tertiary inductance (pu).</td></tr><tr><td><strong>L23</strong></td><td>Secondary-to-tertiary inductance (pu).</td></tr></tbody></table>
{% endtab %}

{% tab title="Neutral impedance" %}

<table><thead><tr><th width="220">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>R1, R2, R3, R4</strong></td><td>Neutral resistance of the winding; applies only when the winding is Y-grounded (Ω).</td></tr><tr><td><strong>L1, L2, L3, L4</strong></td><td>Neutral inductance of the winding; applies only when the winding is Y-grounded (H).</td></tr><tr><td><strong>C1, C2, C3, C4</strong></td><td>Neutral capacitance of the winding; applies only when the winding is Y-grounded (F).</td></tr></tbody></table>
{% endtab %}

{% tab title="Saturation" %}

<table><thead><tr><th width="228">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Number of data points</strong></td><td>Number of segments in the current–flux saturation curve; specify only the positive part. The negative part is inferred by symmetry.</td></tr><tr><td><strong>Saturation current</strong></td><td>Current for each segment of the saturation curve; the origin (0,0) is implied (A).</td></tr><tr><td><strong>Saturation flux</strong></td><td>Flux for each segment of the saturation curve; the origin (0.0, 0.0) is implied (V·s).</td></tr></tbody></table>
{% endtab %}

{% tab title="Hysteresis" %}

<table><thead><tr><th width="220">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Saturation data type</strong></td><td>Compute the saturation curve from an equation or define it using segments (Equation, Curve).</td></tr><tr><td><strong>Air core inductance</strong></td><td>Saturation inductance that the curve approaches asymptotically (H).</td></tr><tr><td><strong>Slope at Ic</strong></td><td>Flux slope at coercive current (H).</td></tr><tr><td><strong>Coercive current - Ic</strong></td><td>Positive coercive current at zero flux (A).</td></tr><tr><td><strong>Saturation current - Is</strong></td><td>Current value of the first point in the saturation zone (A).</td></tr><tr><td><strong>Current tolerance</strong></td><td>Limits generation of minor nested loops. If magnetizing current values at the last and preceding inversion points are within the specified tolerance (percent of Ic), displacement is assumed along a straight segment.</td></tr><tr><td><strong>Remanent flux - Φr</strong></td><td>Positive remanent flux at zero current (V·s).</td></tr><tr><td><strong>Saturation flux - Φs</strong></td><td>Flux value of the first point in the saturation zone (V·s).</td></tr><tr><td><strong>Flux tolerance</strong></td><td>Limits generation of minor nested loops. If flux values at the last and preceding inversion points are within the specified tolerance (percent of Φs), displacement is assumed on the current loop.</td></tr><tr><td><strong>Initial flux (peak)</strong></td><td>Initial flux determining the initial trajectory, calculated by assuming an inversion point on the main cycle (V·s).</td></tr><tr><td><strong>Number of data points</strong></td><td>Number of segments in the current–flux saturation curve; specify only the positive part. The negative part is inferred by symmetry.</td></tr><tr><td><strong>Saturation current</strong></td><td>Current for each segment of the saturation curve; the first value must equal Is (A).</td></tr><tr><td><strong>Saturation flux</strong></td><td>Flux for each segment of the saturation curve; the first value must equal Φs (V·s).</td></tr></tbody></table>
{% endtab %}
{% endtabs %}

## Conserving ports

<table><thead><tr><th width="200">Port</th><th>Description</th></tr></thead><tbody><tr><td><strong>Net_1</strong></td><td>Primary winding connection (supports only 3-phase connections).</td></tr><tr><td><strong>Net_2</strong></td><td>Secondary winding connection (supports only 3-phase connections).</td></tr><tr><td><strong>Net_N1</strong></td><td>Neutral connection for the primary winding (supports only 1-phase connections).</td></tr><tr><td><strong>Net_N2</strong></td><td>Neutral connection for the secondary winding (supports only 1-phase connections).</td></tr></tbody></table>

## Inputs

This block has no inputs.

## Outputs

This block has no outputs.

## Signals available for monitoring and external I/O connections (via sensors form)

All block inputs and outputs are available as signals for monitoring and for external I/O connections.

Additional signals are also available and are listed below with their descriptions.

<table><thead><tr><th width="220">Signal</th><th>Description</th></tr></thead><tbody><tr><td><strong>FLUX(a,b,c)</strong></td><td>Magnetization flux for each phase (V·s).</td></tr><tr><td><strong>ILMAG(a,b,c)</strong></td><td>Magnetization current for each phase (A)</td></tr><tr><td><strong>IPRIM(a,b,c)</strong></td><td>Primary current for each phase (A)</td></tr><tr><td><strong>ISEC2(a,b,c)</strong></td><td>Secondary current (A)</td></tr><tr><td><strong>ISEC3(a,b,c)</strong></td><td>Tertiary current for each phase (A).</td></tr><tr><td><strong>SEG(a,b,c)</strong></td><td><p>Segment number of the saturation curve.</p><ul><li>Saturation model: numbering is positive, starting at 1 for the last segment in the negative saturation zone.</li><li>Hysteresis model: numbering is positive/negative starting at 1/−1 in the positive/negative saturation zone; it is zero in the hysteresis zone.</li></ul></td></tr></tbody></table>


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/network-transformers/2-winding-3-phase-saturable-autotransformer-with-internal-tertiary.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.