> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/network-transformers/2-winding-3-phase-saturable-autotransformer-with-internal-tertiary-3-limb.md).

# 2 Winding 3 Phase Saturable Autotransformer with Internal Tertiary 3 Limb

## Description

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-48505cf10f4b90030156ed31a6a0f5f8157b097e%2Fimage%20(365).png?alt=media" alt="" width="200"><figcaption></figcaption></figure>

The **2-Winding 3-Phase Saturable Autotransformer with Internal Tertiary 3-Limb** block, located in the **Network Transformers** library, models an autotransformer that accounts for the magnetic behavior of three-limb cores under geomagnetic induced currents (GICs). In three-limb transformers, quasi-DC GIC flux returns through the transformer tank and air, which have high reluctance. As a result, three-limb transformers are less sensitive to GICs. To represent this effect, the model adds a fictitious delta-grounded winding to the basic autotransformer.

### Internal Connection and Parameters <a href="#id-2-winding3-phasesaturableautotransformerwithinternaltertiary3-limb-internalconnectionandparameter" id="id-2-winding3-phasesaturableautotransformerwithinternaltertiary3-limb-internalconnectionandparameter"></a>

The internal connection of the autotransformer is shown below. Note that it is the phase C's terminal of tertiary and fictitious windings which are grounded. The neutral point of the autotransformer is accessible via the single-phase "N" terminal.

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-3a22739e9f6c289bbb972262b28e78c8fee747b4%2Fimage%20(366).png?alt=media" alt="" width="375"><figcaption></figcaption></figure>

The main parameters (R<sub>12</sub>, X<sub>12</sub>, X<sub>13</sub>, X<sub>23</sub> and R<sub>3</sub>) are entered in "per unit" only. They are then used to determine the parameters by winding (R<sub>1</sub>, R<sub>2</sub>, R<sub>3</sub>, X<sub>1</sub>, X<sub>2</sub> and X<sub>3</sub>) as a function of the nominal voltages of the windings (N<sub>1</sub> and N<sub>2</sub>) according to the expressions below, N<sub>1</sub> and N<sub>2</sub> corresponds to the series winding and common winding.

$$
k = \frac{N\_2}{N\_1 + N\_2}\\\[8pt]

X\_1 = \frac{\frac{1+k}{1-k} X\_{12} + X\_{13} - X\_{23}}{2(1-k)}\\\[8pt]

X\_2 = \frac{X\_{12} - X\_{13} + X\_{23}}{2(1-k)}\\\[8pt]

X\_3 = \frac{-X\_{12} + X\_{13} + (1 - 2k)X\_{23}}{2(1-k)}
$$

* If **"Parameter calculation method" = Equal R1 R2**

$$
R\_1 = R\_2 = \frac{R\_{12}}{2(1-k)^2} \\\[8pt]

R\_3 = R\_{13} - R\_1(1-k)^2 - R\_2(k)^2
$$

* If **"Parameter calculation method" = Classic**

$$
R\_1 = \frac{\frac{1+k}{1-k} R\_{12} + R\_{13} - R\_{23}}{2(1-k)}\\\[8pt]
R\_2 = \frac{R\_{12} - R\_{13} + R\_{23}}{2(1-k)} \\\[8pt]
R\_3 = \frac{-R\_{12} + R\_{13} + (1 - 2k)R\_{23}}{2(1-k)}
$$

The values obtained are referenced to the primary nominal voltages (VbasePrimary = VnomSeries + VnomCommon), secondary (VbaseSecondary = VnomCommon) and tertiary (VbaseTertiary = VnomTertiary).

All other parameters are entered in the same way as for other HYPERSIM transformer models. The saturation is placed at the series winding and uses the nominal voltage of this winding for the "per unit" conversion.

### Load Flow and Initialization <a href="#id-2-winding3-phasesaturableautotransformerwithinternaltertiary3-limb-loadflowandinitialization" id="id-2-winding3-phasesaturableautotransformerwithinternaltertiary3-limb-loadflowandinitialization"></a>

The autotransformer sends the parameters of a standard equivalent transformer to the power flow algorithm.

$$
R\_1 = R\_2 = \frac{R\_{12}}{2} \\\[8pt]
X\_1 = \frac{X\_{12} + X\_{13} - X\_{23}}{2} \\\[8pt]
X\_2 = \frac{X\_{12} - X\_{13} + X\_{23}}{2}
$$

Tertiary winding is considered for power flow whereas the fourth winding (if activated) does not participate in the power flow.

During power flow, the block sends parameters of a standard equivalent transformer to the algorithm. After the solution, internal voltages and currents are recalculated using the true topology.

## Mask parameters

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-869933c6061743cecb456a986877387c54c01cc6%2F3phSA_.jpg?alt=media" alt=""><figcaption></figcaption></figure>

{% tabs %}
{% tab title="General" %}

| Parameter                                               | Description                                                                                                                                                                                                           |
| ------------------------------------------------------- | --------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- |
| **Tertiary connection**                                 | Select whether the delta-connected winding voltage will lead or lag the star-connected winding voltage, or ground C-phase.                                                                                            |
| **Flux-Current characteristic model**                   | Select saturation only, or saturation with hysteresis.                                                                                                                                                                |
| **Iteration in saturation model**                       | Enable or disable iteration to improve accuracy when the saturation segment changes, at the expense of computation time.                                                                                              |
| **Base serial/common/tertiary winding voltage (rmsLL)** | Base value for PU conversion (kV).                                                                                                                                                                                    |
| **Rm**                                                  | Equivalent resistance of iron losses of the magnetic circuit (Ω).                                                                                                                                                     |
| **Base primary/secondary winding voltage (rmsLL)**      | <p>Base value for PU conversion (kV).</p><ul><li>Voltage expressed in kV rms LL.</li><li>This base voltage and nominal voltage change if the corresponding winding connection switches between delta and Y.</li></ul> |
| **Base power (total)**                                  | Base value for PU conversion (MVA).                                                                                                                                                                                   |
| **Base frequency**                                      | Base value for PU conversion (Hz).                                                                                                                                                                                    |
| **R12**                                                 | Primary to secondary resistance (pu).                                                                                                                                                                                 |
| **R13**                                                 | Primary to tertiary resistance (pu).                                                                                                                                                                                  |
| **R23**                                                 | Secondary to tertiary resistance (pu).                                                                                                                                                                                |
| **L12**                                                 | Primary to secondary inductance (pu).                                                                                                                                                                                 |
| **L13**                                                 | Primary to tertiary inductance (pu).                                                                                                                                                                                  |
| **L23**                                                 | Secondary to tertiary inductance (pu).                                                                                                                                                                                |
| **Parameter calculation method**                        | <ul><li>Equal R1 R2: Resistance of the series winding is set equal to the common winding.</li><li>Classic: R1, R2, and R3 are calculated using between-winding resistances R12, R13, and R23.</li></ul>               |
| **3-limb magnetic circuit**                             | Enable or disable modeling of the three-legged magnetic circuit.                                                                                                                                                      |
| **Air and tank leakage inductance**                     | Inductance of the fictitious winding (pu) \[uses the same base as the tertiary winding].                                                                                                                              |
| **Air and tank leakage resistance**                     | Resistance of the fictitious winding (pu) \[uses the same base as the tertiary winding].                                                                                                                              |
| {% endtab %}                                            |                                                                                                                                                                                                                       |

{% tab title="Neutral Impedance" %}

| Parameter          | Description                                                       |
| ------------------ | ----------------------------------------------------------------- |
| **R1, R2, R3, R4** | Neutral resistance of the winding; only applies to Y ground (Ω).  |
| **L1, L2, L3, L4** | Neutral inductance of the winding; only applies to Y ground (H).  |
| **C1, C2, C3, C4** | Neutral capacitance of the winding; only applies to Y ground (F). |
| {% endtab %}       |                                                                   |

{% tab title="Saturation" %}

| Parameter                 | Description                                                                                                                                        |
| ------------------------- | -------------------------------------------------------------------------------------------------------------------------------------------------- |
| **Number of data points** | Number of segments of the current-flux saturation curve; specify only the positive part of the curve (the negative part is completed by symmetry). |
| **Saturation current**    | Current for each segment of the saturation curve; the origin (0,0) is implied (A).                                                                 |
| **Saturation flux**       | Flux for each segment of the saturation curve; the origin (0.0, 0.0) is implied (V.s).                                                             |
| {% endtab %}              |                                                                                                                                                    |

{% tab title="hysteresis" %}

| Parameter                   | Description                                                                                                                                                                                                                            |
| --------------------------- | -------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- |
| **Saturation data type**    | Determines if the saturation curve is calculated by the model or defined by a series of segments (Equation, Curve).                                                                                                                    |
| **Air core inductance**     | Value of the saturation inductance that the curve approaches asymptotically (H).                                                                                                                                                       |
| **Slope at Ic**             | Flux slope at coercive current (H).                                                                                                                                                                                                    |
| **Coercive current - Ic**   | Positive coercive current at null flux (A).                                                                                                                                                                                            |
| **Saturation current - Is** | Current value of the first point in the saturation zone (A).                                                                                                                                                                           |
| **Current tolerance**       | Limits generation of minor nested loops. When magnetizing current values at the last and preceding inversion points are closer than the specified tolerance (in % of Ic), the trajectory is assumed to follow a straight line segment. |
| **Remanent flux - Φr**      | Positive remanent flux at null current (V.s).                                                                                                                                                                                          |
| **Saturation flux - Φs**    | Flux value of the first point in the saturation zone (V.s).                                                                                                                                                                            |
| **Flux tolerance**          | Limits generation of minor nested loops. When flux values at the last and preceding inversion points are closer than the specified tolerance (in % of Φs), the displacement is assumed to follow the current loop.                     |
| **Initial flux (peak)**     | Initial flux determining the initial trajectory, calculated by assuming an inversion point on the main cycle (V.s).                                                                                                                    |
| **Number of data points**   | Number of segments of the current-flux saturation curve; specify only the positive part of the curve (the negative part is completed by symmetry).                                                                                     |
| **Saturation current**      | The current for each segment of the saturation curve; the first value must be equal to Is (A).                                                                                                                                         |
| **Saturation flux**         | The flux for each segment of the saturation curve; the first value must be equal to Φs (V.s).                                                                                                                                          |
| {% endtab %}                |                                                                                                                                                                                                                                        |
| {% endtabs %}               |                                                                                                                                                                                                                                        |

## Conserving ports

<table><thead><tr><th width="200">Port</th><th>Description</th></tr></thead><tbody><tr><td><strong>Net_1</strong></td><td>Primary winding connection (supports only 3-phase connections).</td></tr><tr><td><strong>Net_2</strong></td><td>Secondary winding connection (supports only 3-phase connections).</td></tr><tr><td><strong>Net_N1</strong></td><td>Neutral connection for the primary winding (supports only 1-phase connections).</td></tr><tr><td><strong>Net_3</strong></td><td>Tertiary winding connection (supports only 3-phase connections)</td></tr></tbody></table>

## Inputs

This block has no inputs.

## Outputs

This block has no outputs.

## Signals available for monitoring and external I/O connections (via sensors form)

All block inputs and outputs are available as signals for monitoring and for external I/O connections.

Additional signals are also available and are listed below with their descriptions.

<table><thead><tr><th width="220">Signal</th><th>Description</th></tr></thead><tbody><tr><td><strong>FLUX(a,b,c)</strong></td><td>Magnetization flux for each phase (V·s).</td></tr><tr><td><strong>ILMAG(a,b,c)</strong></td><td>Magnetization current for each phase (A)</td></tr><tr><td><strong>IPRIM(a,b,c)</strong></td><td>Primary current for each phase (A)</td></tr><tr><td><strong>ISEC2(a,b,c)</strong></td><td>Secondary current (A)</td></tr><tr><td><strong>ISEC3(a,b,c)</strong></td><td>Tertiary current for each phase (A).</td></tr><tr><td><strong>ISEC3(a,b,c)</strong></td><td>Fictitious winding current for each phase (A); available only when “3-limb magnetic circuit” is enabled.</td></tr><tr><td><strong>SEG(a,b,c)</strong></td><td><p>Segment number of the saturation curve.</p><ul><li><strong>Saturation</strong> model: numbering is positive, starting at 1 for the last segment in the negative saturation zone.</li><li><strong>Hysteresis</strong> model: numbering is positive/negative starting at 1/−1 in the positive/negative saturation zone; it is zero in the hysteresis zone.</li></ul></td></tr></tbody></table>


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/network-transformers/2-winding-3-phase-saturable-autotransformer-with-internal-tertiary-3-limb.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.