> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/network-transformers/3-winding-1-phase-linear-transformer-with-tap-changer.md).

# 3 Winding 1 Phase Linear Transformer with Tap Changer

## Description

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-a109b740eed23c5992e66be9a12a7c51aaeb4fd8%2Fimage%20(355).png?alt=media" alt="" width="115"><figcaption></figcaption></figure>

The **Three-Winding 1-phase Linear Transformer with Tap Changer** block, located in the **Network Transformers** library, regulates voltage using a tap changer by adjusting the transformer ratio. It is recommended when simulating voltage control for electronic power converters. Use the linear model when core saturation is not required to reduce computation time.

## Mask parameters

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-ef5e110277f1b11bc7fb81cca0ddccd55aa5f5bd%2F33-phtap.jpg?alt=media" alt=""><figcaption></figcaption></figure>

{% tabs %}
{% tab title="General" %}

<table><thead><tr><th width="220">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Description</strong></td><td>Use this field to add all kinds of information about the block</td></tr><tr><td><strong>Base primary/secondary/tertiary winding voltage (rmsLN)</strong></td><td>Base value for pu conversion (kV)</td></tr><tr><td><strong>Base power (total)</strong></td><td>Base value for pu conversion (MVA)</td></tr><tr><td><strong>Base frequency</strong></td><td>Base value for pu conversion (Hz).</td></tr><tr><td><strong>Rm</strong></td><td>Equivalent resistance of iron losses of the magnetic circuit (Ω)</td></tr><tr><td><strong>Lm</strong></td><td>Magnetization inductance (H)</td></tr><tr><td><strong>Voltage (rmsLN)</strong></td><td>Rated voltage of the winding (kV)</td></tr><tr><td><strong>R1, R2, R3</strong></td><td>Leakage resistance of the winding (Ω)</td></tr><tr><td><strong>L1, L2, L3</strong></td><td>Leakage inductance of the winding (H)</td></tr></tbody></table>
{% endtab %}

{% tab title="Control" %}

<table><thead><tr><th width="205">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Control type</strong></td><td><p>Source of the command</p><ul><li>Internal (control model): The Manual position parameter defines the set point for the tap. It is reached after the temporization and operation times.</li><li>External (input pins): The Manual position parameter defines the initial tap value only. The temporization and operation times apply to the external control.</li></ul></td></tr><tr><td><strong>Manual position</strong></td><td>Manual position required; either a set point or initial value depending on the control type</td></tr><tr><td><strong>Number of taps</strong></td><td>Number of tap(s); maximum 50</td></tr><tr><td><strong>Nominal tap</strong></td><td>Tap position at which nominal values are set</td></tr><tr><td><strong>Tap size (% of base voltage)</strong></td><td>Tap voltage increment value in reference to the primary base voltage (%)</td></tr><tr><td><strong>Temporization time</strong></td><td>Minimum duration required for a signal order to start changing tap (s)</td></tr><tr><td><strong>Operation time</strong></td><td>Time between tap changes (s)</td></tr></tbody></table>
{% endtab %}
{% endtabs %}

## Conserving ports

<table><thead><tr><th width="200">Port</th><th>Description</th></tr></thead><tbody><tr><td><strong>Net_1+</strong></td><td>Positive primary winding connection (supports only 1-phase connections)</td></tr><tr><td><strong>Net_1-</strong></td><td>Negative primary winding connection (supports only 1-phase connections)</td></tr><tr><td><strong>Net_2+</strong></td><td>Positive secondary winding connection (supports only 1-phase connections)</td></tr><tr><td><strong>Net_2-</strong></td><td>Negative secondary winding connection (supports only 1-phase connections)</td></tr><tr><td><strong>Net_3+</strong></td><td>Positive tertiary winding connection (supports only 1-phase connections)</td></tr><tr><td><strong>Net_3-</strong></td><td>Negative tertiary winding connection (supports only 1-phase connections)</td></tr></tbody></table>

## Inputs

| Input | Description                                |
| ----- | ------------------------------------------ |
| **U** | "Up" control input; changes one position   |
| **D** | "Down" control input; changes one position |

## Outputs

| Output  | Description  |
| ------- | ------------ |
| **Tap** | Tap position |

## Signals available for monitoring and external I/O connections (via sensors form)

All block inputs and outputs are available as signals for monitoring and for external I/O connections.

Additional signals are also available and are listed below with their descriptions.

| Signal    | Description               |
| --------- | ------------------------- |
| **ILMAG** | Magnetization current (A) |
| **IPRIM** | Primary current (A)       |
| **ISEC2** | Secondary current (A)     |
| **ISEC3** | Tertiary current (A)      |


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/network-transformers/3-winding-1-phase-linear-transformer-with-tap-changer.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.