> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/network-transformers/3-winding-3-phase-saturable-transformer-with-tap-changer-and-decoupling-element.md).

# 3 Winding 3 Phase Saturable Transformer with Tap Changer and Decoupling Element

## Description

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-f8fdd250b68a44e4e88a018bc6c19f0668bd026a%2Fimage%20(351).png?alt=media" alt="" width="215"><figcaption></figcaption></figure>

The **3-Winding 3-Phase Saturable Transformer with Tap Changer and Decoupling Element** block, located in the **Network Transformers** library, is used when a regulated voltage is required, such as with electronic power converters. This 3‑winding saturable transformer models saturation and hysteresis with optional iteration to improve accuracy when the saturation segment changes. It also includes a decoupling element to split the network into two tasks that can run on separate cores for improved performance.

The saturation is a core characteristic (a winding property, not dependent on the 3‑phase connection type). It is applied to the magnetization branch and represented by line segments.

The main hysteresis cycle is characterized by four parameters and is measured in DC to exclude Foucault losses (accounted for by Rm). The initial trajectory is defined by the initial flux. Two special parameters limit the generation of internal nested loops saved in memory (very small loops are ignored and represented by a straight segment). The number of loops is limited to 100. Above the main cycle (±Is), the model enters saturation, defined either by a series of points or by an asymptotic inductance. In the latter case, the model automatically generates equal‑length segments (Is) in both saturation zones.

The tap changer effect is simulated by changing the transformer ratio.

## Mask parameters

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-1839b76864e7693c301b76bdbb6088ec9bcc456a%2F9.jpg?alt=media" alt=""><figcaption></figcaption></figure>

{% tabs %}
{% tab title="General" %}

<table><thead><tr><th width="240">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Description</strong></td><td>Use this field to add all kinds of information about the component.</td></tr><tr><td><strong>Flux-Current model</strong></td><td>Model saturation only, or saturation with hysteresis.</td></tr><tr><td><strong>Iteration in saturation model</strong></td><td>Enable or disable iteration to achieve more accurate results when the saturation segment changes (increases computation time).</td></tr><tr><td><strong>Base primary/secondary/tertiary winding voltage (rmsLL)</strong></td><td>Base value for PU conversion (kV). Voltage expressed in kV rms LL. This base voltage and nominal voltage change if the corresponding winding connection switches between delta and Y.</td></tr><tr><td><strong>Base power (total)</strong></td><td>Base value for PU conversion (MVA).</td></tr><tr><td><strong>Base frequency</strong></td><td>Base value for PU conversion (Hz).</td></tr><tr><td><strong>Rm</strong></td><td>Equivalent resistance of iron losses of the magnetic circuit (Ω).</td></tr><tr><td><strong>Voltage (rmsLL)</strong></td><td><p>Rated voltage of the winding (kV).</p><ul><li>Y connections: Voltage expressed in kV rms LL</li><li>Delta connections: Voltage expressed in kV rms LL</li></ul></td></tr><tr><td><strong>R1, R2, R3</strong></td><td>Leakage resistance of the winding (Ω).</td></tr><tr><td><strong>L1, L2, L3</strong></td><td>Leakage inductance of the winding (H).</td></tr></tbody></table>
{% endtab %}

{% tab title="Neutral impedance" %}

<table><thead><tr><th width="200">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>R1</strong></td><td>Neutral resistance of the primary winding; only applies to Y ground (Ω).</td></tr><tr><td><strong>L1</strong></td><td>Neutral inductance of the primary winding; only applies to Y ground (H).</td></tr><tr><td><strong>C1</strong></td><td>Neutral capacitance of the primary winding; only applies to Y ground (F).</td></tr></tbody></table>
{% endtab %}

{% tab title="Saturation" %}

<table><thead><tr><th width="220">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Number of data points</strong></td><td>Number of segments of the current‑flux saturation curve; specify only the positive part, the negative part is completed by symmetry.</td></tr><tr><td><strong>Saturation current</strong></td><td>Current for each segment of the saturation curve; the origin (0,0) is implied (A).</td></tr><tr><td><strong>Saturation flux</strong></td><td>Flux for each segment of the saturation curve; the origin (0.0, 0.0) is implied (V·s).</td></tr></tbody></table>
{% endtab %}

{% tab title="Hysteresis" %}

<table><thead><tr><th width="222">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Saturation data type</strong></td><td>Determines if the saturation curve is calculated by the model or defined by a series of segments (Equation, Curve).</td></tr><tr><td><strong>Air core inductance</strong></td><td>Value of the saturation inductance that the curve approaches asymptotically (H).</td></tr><tr><td><strong>Slope at Ic</strong></td><td>Flux slope at coercive current (H).</td></tr><tr><td><strong>Coercitive current - Ic</strong></td><td>Positive coercive current at null flux (A).</td></tr><tr><td><strong>Saturation current - Is</strong></td><td>Current value of the first point in the saturation zone (A).</td></tr><tr><td><strong>Current tolerance</strong></td><td>Limits generation of minor nested loops. When the magnetizing current values at the last and preceding inversion points are closer than the specified tolerance (in % of Ic), displacement is represented by a straight segment.</td></tr><tr><td><strong>Remnant flux - Φr</strong></td><td>Positive remnant flux at null current (V·s).</td></tr><tr><td><strong>Saturation flux - Φs</strong></td><td>Flux value of the first point in the saturation zone (V·s).</td></tr><tr><td><strong>Flux tolerance</strong></td><td>Limits generation of minor nested loops. When the flux values at the last and preceding inversion points are closer than the specified tolerance (in % of Φs), displacement is assumed on the current loop.</td></tr><tr><td><strong>Initial flux (peak)</strong></td><td>Initial flux determining the initial trajectory, calculated assuming an inversion point on the main cycle (V·s).</td></tr><tr><td><strong>Number of points</strong></td><td>Number of segments of the current‑flux saturation curve; specify only the positive part, the negative part is completed by symmetry.</td></tr><tr><td><strong>Saturation current</strong></td><td>Current for each segment of the saturation curve; the first value must be equal to Is (A).</td></tr><tr><td><strong>Saturation flux</strong></td><td>Flux for each segment of the saturation curve; the first value must be equal to Φs (V·s).</td></tr></tbody></table>
{% endtab %}

{% tab title="Control" %}

<table><thead><tr><th width="221">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Control type</strong></td><td><p>Source of the command:</p><ul><li>Internal (combined with LCC): The parameter "Manual tap position" defines the set point for the tap. It is reached after the temporization and operation times.</li><li>Internal (manual tap position): The parameter "Manual tap position" defines the set point for the tap. It is reached after the temporization and operation times.</li><li>External (input sensors): The parameter "Manual tap position" defines the initial value of the tap and is not used thereafter. The temporization and operation times apply to the external control.</li></ul></td></tr><tr><td><strong>Manual position</strong></td><td>Manual position required; either a set point or initial value depending on the control type.</td></tr><tr><td><strong>Number of taps</strong></td><td>Number of tap(s); maximum 50.</td></tr><tr><td><strong>Nominal voltage (rms LG)</strong></td><td>Primary voltage to generate the rated voltage on the secondary winding at the nominal tap (kV).</td></tr><tr><td><strong>Minimum voltage (rms LG)</strong></td><td>Primary voltage linked with position 1 to generate the rated voltage on the secondary winding (kV).</td></tr><tr><td><strong>Maximum voltage (rms LG)</strong></td><td>Primary voltage linked with the last position of the tap changer to generate the rated voltage on the secondary winding (kV).</td></tr><tr><td><strong>Temporization time</strong></td><td>Minimum duration required for a signal order to start changing tap (s).</td></tr><tr><td><strong>Operation time</strong></td><td>Time between tap changes (s).</td></tr></tbody></table>
{% endtab %}
{% endtabs %}

## Conserving ports

<table><thead><tr><th width="200">Port</th><th>Description</th></tr></thead><tbody><tr><td><strong>Net_1</strong></td><td>Primary winding connection (supports only 3-phase connections).</td></tr><tr><td><strong>Net_2</strong></td><td>Secondary winding connection (supports only 3-phase connections).</td></tr><tr><td><strong>Net_3</strong></td><td>Tertiary winding connection (supports only 3‑phase connections).</td></tr></tbody></table>

## Inputs

This block has no inputs.

## Outputs

This block has no outputs.

## Signals available for monitoring and external I/O connections (via sensors form)

All block inputs and outputs are available as signals for monitoring and for external I/O connections.

Additional signals are also available and are listed below with their descriptions.

<table><thead><tr><th width="220">Signal</th><th>Description</th></tr></thead><tbody><tr><td><strong>Down</strong></td><td>"Down one position" order from internal command.</td></tr><tr><td><strong>DownBuf</strong></td><td>Signal specifying the start of a change issued by a “Down” order.</td></tr><tr><td><strong>DownEXT</strong></td><td>"Down one position" order from an external command.</td></tr><tr><td><strong>FLUX(a,b,c)</strong></td><td>Magnetization flux for each phase (V·s).</td></tr><tr><td><strong>ILMAG(a,b,c)</strong></td><td>Magnetization current for each phase (A)</td></tr><tr><td><strong>IPRIM(a,b,c)</strong></td><td>Primary current for each phase (A)</td></tr><tr><td><strong>PosA.B%</strong></td><td>Secondary current for each phase (A)</td></tr><tr><td><strong>PosSign</strong></td><td>Specifies that the tap is above or below the rated position.</td></tr><tr><td><strong>RatioXfo</strong></td><td>Winding ratio</td></tr><tr><td><strong>SEG(a,b,c)</strong></td><td><p>Segment number of the saturation curve</p><p>In the <strong>saturation</strong> model, the numbering is always positive starting at 1 for the last segment in the negative saturation zone.</p><p>In the <strong>hysteresis</strong> model, the numbering is positive/negative starting at 1/-1 in the positive/negative saturation zone. In the hysteresis zone, it takes a null value.</p></td></tr><tr><td><strong>Tap</strong></td><td>Tap position.</td></tr><tr><td><strong>Up</strong></td><td>"Up one position" order from internal command.</td></tr><tr><td><strong>UpBuf</strong></td><td>Signal specifying the start of a change issued by an “Up” order.</td></tr><tr><td><strong>UpEXT</strong></td><td>"Up one position" order from an external command.</td></tr></tbody></table>

## References <a href="#id-3-winding3-phasesaturabletransformerwithtapchangeranddecouplingelement-references" id="id-3-winding3-phasesaturabletransformerwithtapchangeranddecouplingelement-references"></a>

«Hysteresis Modeling in the Matlab/Power System Blockset», Silvano Casoria, Patrice Brunelle, Gilbert Sybille, Mathematics and Computers in Simulation, Volume 63, Issues 3-5, Pages 237-248


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/network-transformers/3-winding-3-phase-saturable-transformer-with-tap-changer-and-decoupling-element.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.