> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/network-transformers/4-winding-1-phase-saturable-transformer.md).

# 4 Winding 1 Phase Saturable Transformer

## Description

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-88dde5dbfc09760b94da9d1f21c93f00243a109b%2Fimage%20(1174).png?alt=media" alt=""><figcaption></figcaption></figure>

The **4-Winding 1-phase Saturable Transformer** block, located in the **Network Transformers** library, adds modeling of core saturation and hysteresis to a linear 4‑winding transformer at the expense of additional computation time.

## Mask parameters

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-6edef8614b1cddec6119e52f42c909ff5b3039fe%2F10.jpg?alt=media" alt=""><figcaption></figcaption></figure>

{% tabs %}
{% tab title="General" %}

<table><thead><tr><th width="240">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Description</strong></td><td>Use this field to add all kinds of information about the component</td></tr><tr><td><strong>Flux-current model</strong></td><td>Model saturation only or saturation with hysteresis</td></tr><tr><td><strong>Iteration in saturation model</strong></td><td>Enable or disable iteration to achieve more accurate results at the expense of computation time when the saturation segment changes</td></tr><tr><td><strong>Base primary/secondary/tertiary/quaternary winding voltage (rmsLN)</strong></td><td>Base value for PU conversion (kV)</td></tr><tr><td><strong>Base power (total)</strong></td><td>Base value for PU conversion (MVA)</td></tr><tr><td><strong>Base frequency</strong></td><td>Base value for PU conversion (Hz)</td></tr><tr><td><strong>Rm</strong></td><td>Equivalent resistance of iron losses of the magnetic circuit (Ω)</td></tr><tr><td><strong>Voltage (rms)</strong></td><td>Rated voltage of the winding (kV)</td></tr><tr><td><strong>R1, R2, R3, R4</strong></td><td>Leakage resistance of the winding (Ω)</td></tr><tr><td><strong>L1, L2, L3, L4</strong></td><td>Leakage inductance of the winding (H)</td></tr></tbody></table>
{% endtab %}

{% tab title="Saturation" %}

| Parameter                 | Description                                                                                                                                                   |
| ------------------------- | ------------------------------------------------------------------------------------------------------------------------------------------------------------- |
| **Number of data points** | Number of segments of the current–flux saturation curve; only the positive part of the curve must be specified, the negative part being completed by symmetry |
| **Saturation current**    | Current for each segment of the saturation curve; the origin (0,0) is implied (A)                                                                             |
| **Saturation flux**       | Flux for each segment of the saturation curve; the origin (0.0,0.0) is implied (V.s)                                                                          |
| {% endtab %}              |                                                                                                                                                               |

{% tab title="Hysteresis" %}

<table><thead><tr><th width="220">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Saturation data type</strong></td><td>Determines if the saturation curve is calculated by the model or defined by a series of segments (Equation, Curve)</td></tr><tr><td><strong>Air core inductance</strong></td><td>Value of the saturation inductance that the curve approaches asymptotically (H)</td></tr><tr><td><strong>Slope at Ic</strong></td><td>Flux slope at coercive current (H)</td></tr><tr><td><strong>Coercitive current - Ic</strong></td><td>Positive coercive current at null flux (A)</td></tr><tr><td><strong>Saturation current - Is</strong></td><td>Current value of the first point in the saturation zone (A)</td></tr><tr><td><strong>Current tolerance</strong></td><td>Parameter limiting the generation of minor nested loops. When the magnetizing current values at the last inversion point and the preceding inversion point are closer than the specified tolerance (in % of Ic), the displacement is represented by a straight line segment.</td></tr><tr><td><strong>Remanent flux - Φr</strong></td><td>Positive remanent flux at null current (V.s)</td></tr><tr><td><strong>Saturation flux - Φs</strong></td><td>Flux value of the first point in the saturation zone (V.s)</td></tr><tr><td><strong>Flux tolerance</strong></td><td>Parameter limiting the generation of minor nested loops. When the flux values at the last inversion point and the preceding inversion point are closer than the specified tolerance (in % of Φs), it is assumed that there is a displacement on the current loop.</td></tr><tr><td><strong>Initial flux (peak)</strong></td><td>Initial flux determining the initial trajectory, calculated by assuming it has an inversion point on the main cycle (V.s)</td></tr><tr><td><strong>Number of points</strong></td><td>Number of segments of the current–flux saturation curve; only the positive part of the curve must be specified, the negative part being completed by symmetry</td></tr><tr><td><strong>Saturation current</strong></td><td>Current for each segment of the saturation curve; the first value must be equal to Is (A)</td></tr><tr><td><strong>Saturation flux</strong></td><td>Flux for each segment of the saturation curve; the first value must be equal to Φs (V.s)</td></tr></tbody></table>
{% endtab %}
{% endtabs %}

## Conserving ports

<table><thead><tr><th width="200">Port</th><th>Description</th></tr></thead><tbody><tr><td><strong>Net_1+</strong></td><td>Positive primary winding connection (supports 1‑phase connections only)</td></tr><tr><td><strong>Net_1-</strong></td><td>Negative primary winding connection (supports 1‑phase connections only)</td></tr><tr><td><strong>Net_2+</strong></td><td>Positive secondary winding connection (supports 1‑phase connections only)</td></tr><tr><td><strong>Net_2-</strong></td><td>Negative secondary winding connection (supports 1‑phase connections only)</td></tr><tr><td><strong>Net_3+</strong></td><td>Positive tertiary winding connection (supports 1‑phase connections only)</td></tr><tr><td><strong>Net_3-</strong></td><td>Negative tertiary winding connection (supports 1‑phase connections only)</td></tr><tr><td><strong>Net_4+</strong></td><td>Positive quaternary winding connection (supports 1‑phase connections only)</td></tr><tr><td><strong>Net_4-</strong></td><td>Negative quaternary winding connection (supports 1‑phase connections only)</td></tr></tbody></table>

## Input

This block has no inputs

## Outputs

This block has no outputs

## Signals available for monitoring and external I/O connections (via sensors form)

All block inputs and outputs are available as signals for monitoring and for external I/O connections.

Additional signals are also available and are listed below with their descriptions.

<table><thead><tr><th width="198">Signal</th><th>Description</th></tr></thead><tbody><tr><td><strong>FLUX</strong></td><td>Magnetization flux (V.s)</td></tr><tr><td><strong>IMAG</strong></td><td>Magnetization current (A)</td></tr><tr><td><strong>IPRIM</strong></td><td>Primary current (A)</td></tr><tr><td><strong>ISEC2</strong></td><td>Secondary current (A)</td></tr><tr><td><strong>ISEC3</strong></td><td>Tertiary current (A)</td></tr><tr><td><strong>ISEC4</strong></td><td>Quaternary current (A)</td></tr><tr><td><strong>SEG</strong></td><td>Segment number of the saturation curve.<br>In the <strong>saturation</strong> model, numbering is always positive starting at 1 for the last segment in the negative saturation zone.<br>In the <strong>hysteresis</strong> model, numbering is positive/negative starting at 1/−1 in the positive/negative saturation zone; it is zero in the hysteresis zone.</td></tr></tbody></table>

## References <a href="#id-4-winding1-phasesaturabletransformer-references" id="id-4-winding1-phasesaturabletransformer-references"></a>

«Hysteresis Modeling in the Matlab/Power System Blockset», Silvano Casoria, Patrice Brunelle, Gilbert Sybille, Mathematics and Computers in Simulation, Volume 63, Issues 3-5, Pages 237-248


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/library-blocks-reference/network-transformers/4-winding-1-phase-saturable-transformer.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.