> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/model-and-simulation/optimize-the-model/use-parameter-generators/line-parameters.md).

# Line Parameters

## Overview

The **Line Generator** tool calculates the resistance (**R**), inductance (**L**), and capacitance (**C**) matrices for overhead transmission lines with arbitrary conductor configurations. It is available directly from the mask parameters of selected line blocks. Alternatively, the [Line Data block](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/network-lines-and-cables/line-data.md) can be used to generate a **.pun** file, which can then be imported directly into the parameters of a Line block.

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-20d4d170ed58ae3662a73eea242584e7a176ebf6%2Fimage%20(1656).png?alt=media" alt="" width="563"><figcaption></figcaption></figure>

HYPERSIM uses a dedicated calculation engine to generate the phase-domain **R**, **L**, and **C** matrices. It then applies CLAPACK library routines to derive the corresponding **sequence parameters**, **mode parameters**, and the **Ti transformation matrix** used by HYPERSIM line models.

* For a system containing **N conductors**, the tool computes three **N × N** matrices: the series resistance matrix **\[R]**, the series inductance matrix **\[L]**, and the shunt capacitance matrix **\[C]**. It also calculates the associated **Ti transformation matrix**, as well as the sequence and modal parameters.
* The self and mutual terms of the **R**, **L**, and **C** matrices are computed for each conductor pair using the image-conductor method illustrated in the following picture. This approach accounts for the electrical coupling between conductors and the influence of the ground.

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-39175a77856ced057cff3ea4482559b24dfa210d%2Fimage%20(1659).png?alt=media" alt=""><figcaption><p>Conductor representation</p></figcaption></figure>

### Equations

**Self and mutual resistance terms:**

$$
R\_{ii}=R\_{int}+ \Delta R\_{ii} ; \Omega /km \\\[8pt]
R\_{ik}=\Delta R\_{ik} ; \Omega /km
$$

**Self and mutual inductance terms:**

$$
L\_{ii}=L\_{int}+\frac{\mu\_0}{2\pi}.log \frac{2h\_i}{r\_i}+ \Delta L\_{ii} ; H/km \\\[8pt]
L\_{ik}=\frac{\mu\_0}{2\pi}.log \frac{D\_{ik}}{d\_{ik}}+\Delta L\_{ik} ; H/km
$$

**Self and mutual potential coefficient terms:**

$$
P\_{ii}=\frac{1}{2\pi \varepsilon\_0}.log \frac{2h\_i}{r\_i} ; km/F \\\[8pt]
P\_{ik}=\frac{1}{2\pi \varepsilon\_0}.log \frac{D\_{ik}}{d\_{ik}} ; km/F \\\[8pt]
\[C]=\[P]^{-1} ; F/km
$$

Where:

|                |                                                     |
| -------------- | --------------------------------------------------- |
| **µ₀**         | permeability of free space = 4.10⁻⁴ H/km            |
| **ε₀**         | permittivity of free space = 8.8542.10⁻⁹ F/km       |
| **rᵢ**         | radius of conductor i                               |
| **dᵢₖ**        | distance between conductors i and k                 |
| **Dᵢₖ**        | distance between conductor i and image of k         |
| **hᵢ**         | average height of conductor i above ground          |
| **Rᵢₙₜ, Lᵢₙₜ** | internal resistance and inductance of conductor     |
| **ΔRᵢᵢ, ΔRᵢₖ** | Carson R correction terms due to ground resistivity |
| **ΔLᵢᵢ, ΔLᵢₖ** | Carson L correction terms due to ground resistivity |

**Conductor self-inductance** is determined from the magnetic flux produced by the current flowing in the conductor and circulating both inside and outside the conductor. The flux circulating within the conducting material contributes to the **internal inductance** (*L*<sub>*int*</sub>), which depends on the conductor geometry. For both solid and hollow conductors, the internal inductance is calculated from the **T/D ratio**, where *D* is the conductor diameter and *T* is the thickness of the conducting material.

The conductor self-inductance can be calculated using **modified Bessel functions**, based on the conductor diameter, the T/D ratio, the electrical resistivity and relative permeability of the conducting material, and the specified frequency \[1].

Alternatively, conductor self-inductance can be derived from parameters commonly provided in conductor manufacturer datasheets, such as the **Geometric Mean Radius (GMR)** or the **reactance at one-foot spacing**. The **GMR** represents the radius of an equivalent hollow conductor with zero wall thickness. Since such a conductor has no internal flux, it yields the same self-inductance as the actual conductor. The conductor self-inductance can therefore be calculated from the GMR using the following equation:

$$
L\_{ii}=\frac{\mu\_0}{2\pi}.log \frac{2h\_i}{GMR}+ \Delta L\_{ii} ; H/km  \tag{Eq1}
$$

For a T/D ratio=0.5, the GMR is given by:

$$
\tag{Eq2} GMR=r \times e^{-\mu\_{\tau}/4}
$$

$$
\tag{Eq3} r=\frac{d}{\sqrt{(2(1-cos(alpha \times \frac{\pi}{180})))}}
$$

where *d* is the spacing between conductors in the bundle.

The GMR obtained from the above equation assumes a **uniform current density** throughout the conductor cross-section. This assumption is strictly valid under **DC conditions**. Under AC conditions, the effective GMR is slightly higher due to skin effect. For example, for a solid aluminum conductor with a diameter of 3 cm (*R*<sub>dc</sub> = 0.040 Ω/km), the GMR increases from **1.1682 cm** at DC to **1.1784 cm** at **60 Hz**. Manufacturers typically specify GMR values at the system nominal frequency, usually **50 Hz** or **60 Hz**.

The **reactance at one-foot spacing** (*X*<sub>a</sub>) or **one-meter spacing** (in metric units) is defined as the positive-sequence reactance of a three-phase line with phase conductors spaced one foot (or one meter) apart and located at infinite height above ground. At a given frequency *f*, the reactance at one-foot (or one-meter) spacing is related to the GMR by the following equation:

$$
X\_a= \omega \times \frac{\mu\_0}{2\pi} \times log \frac{1}{GMR} ; \Omega/km \tag{Eq4}
$$

The **conductor resistance matrix** at a given frequency is derived from the conductor DC resistance, with corrections applied for both **skin effect** and **ground return effects**. As a result, both the **resistance matrix (R)** and the **inductance matrix (L)** vary with frequency and ground resistivity.

To accurately account for these dependencies, the Line Generator implements the correction terms developed by **J. R. Carson (1926)** \[2]. Carson's formulation models the influence of the earth-return path on line impedance, providing frequency-dependent corrections to both the resistance and inductance components of the impedance matrix.

## Use the Line Generator step-by-step

### Toolbox icons

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-ff78865266675227349d0eff705f1d681d109ab8%2FZ-based-transformer-data-menu.png?alt=media" alt=""><figcaption></figcaption></figure>

| Button              | Description                                                                                                   |
| ------------------- | ------------------------------------------------------------------------------------------------------------- |
| **Compute**         | Compute the transformer data. The results are shown in the Log tab.                                           |
| **Revert**          | Revert to default transformer data.                                                                           |
| **Open**            | Loads preparation data. The required format is `.hmd` for HYPERSIM Machine Data.                              |
| **Save**            | Saves the transformer data in a new `.htd` (hypertransfo data file) file that contains the model information. |
| **Load parameters** | Loads the computed parameters into the component.                                                             |

### Sub-tab parameters <a href="#how-to-generate-transformer-parameters" id="how-to-generate-transformer-parameters"></a>

| Sub-tab                                  | Description                                                                                                |
| ---------------------------------------- | ---------------------------------------------------------------------------------------------------------- |
| **Parameters**                           | The upper section where you enter general parameters (units, frequency, ground resistivity, and comments). |
| **Line Geometry**                        | The table of conductors specifying the line geometry and conductor types.                                  |
| **Conductor and bundle characteristics** | The table of conductor types defining the conductor characteristics for each type.                         |
| **Line Data Report**                     | Reports the electrical parameters of the line computed by the program.                                     |

{% stepper %}
{% step %}

### Enter the parameters

The default parameters are for a single-circuit three-phase line with two ground wires.

<table data-header-hidden><thead><tr><th width="200"></th><th></th></tr></thead><tbody><tr><td><strong>Frequency</strong></td><td>Specify the frequency in hertz to be used to evaluate RLC parameters.</td></tr><tr><td><strong>Ground Resistivity</strong></td><td>Specify the ground resistivity in ohm.meters. A zero value (perfectly conducting ground) is allowed.</td></tr><tr><td><strong>Comment</strong></td><td>Use this window to type comments that you want to save with the line parameters, for example, voltage level, conductor types and characteristics, etc.</td></tr></tbody></table>
{% endstep %}

{% step %}

### Enter line geometry parameters

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-c0e3acb46a97f7b706b1eef903c11cfcd9330875%2Fline-paramter-definition.png?alt=media" alt="" width="480"><figcaption></figcaption></figure>

The average height of the conductor is given by:

$$
Y\_{average}=Y\_{min}+\frac{sag}{3}=\frac{2Y\_{min}+Y\_{tower}}{3}
$$

Where:

* Y<sub>tower</sub>: height of conductor at tower
* Y<sub>min</sub>: height of conductor at mid span
* sag=Y<sub>tower</sub>-Y<sub>min</sub>

Instead of specifying two different values for Y<sub>tower</sub> and Y<sub>min</sub>, you may specify the same Y<sub>average</sub> value.

<table data-search="false"><thead><tr><th width="180" valign="top">Parameter</th><th>Description</th></tr></thead><tbody><tr><td valign="top"><strong>Number of phase conductors (bundles)</strong></td><td>Specify the number of phase conductors (single conductors or bundles of sub conductors) to be used. This parameter, together with the Number of ground wires (bundles) parameter, will determine the number of rows of the table of conductors.</td></tr><tr><td valign="top"><strong>Number of ground wires (bundles)</strong></td><td><p>Specify the number of ground wires (single conductors or bundles of sub conductors) to be used. Ground wires are usually not bundled. This parameter, together with the Number of phase conductors (bundles) parameter, will determine the number of rows of the table of conductors.</p><p>In the table of conductors, five rows are visible at a time. If more than five conductors (phase conductors plus ground wires) are specified, a scroll bar appears at the right side of the table to give you access to the different rows of the table.</p></td></tr><tr><td valign="top"><strong>Conductor (bundle)</strong></td><td>Number of conductor defined by the number of phase plus the number or ground wires.</td></tr><tr><td valign="top"><strong>Phase Number</strong></td><td><p>Specify the phase number to which the conductor belongs. Several conductors may have the same phase number. All conductors having the same phase number are lumped together and will be considered as a single equivalent conductor in the R L C matrices.</p><p>For example, if you want to compute the line parameters of a three-phase line equivalent to a double-circuit line, you specify phase numbers 1, 2, 3 for conductors p1, p2, p3 (circuit 1) and phase numbers 3, 2, 1 for conductors p4, p5, p6 (circuit 2), respectively.</p><p>If you prefer to simulate this line as two individual circuits and have access to the six-phase conductors, you would rather specify phase numbers 1, 2, 3, 6, 5, 4 respectively for conductors p1, p2, p3, p4, p5, and p6.<br>In three-phase systems, the three phases are usually labeled A, B, C. The correspondence with the phase number is 1, 2, 3, 4, 5, 6, 7, 8, 9,. = A, B, C, A, B, C A, B, C.<br>You can also use the phase number to lump conductors of an asymmetrical bundle. For ground wires, the phase number is forced to zero. All ground wires are lumped with the ground and they do not contribute to the R L C matrix dimensions.</p></td></tr><tr><td valign="top"><strong>X (meters)</strong></td><td>Specify the horizontal position of the conductor in meters or feet. The location of the zero reference position is arbitrary. For a symmetrical line you normally choose X = 0 at the center of the line.</td></tr><tr><td valign="top"><strong>Y tower (meters)</strong></td><td>Specify the vertical position of the conductor (at the tower) with respect to ground, in meters.</td></tr><tr><td valign="top"><strong>Y min (meters)</strong></td><td><p>Specify the vertical position of the conductor with respect to ground at mid-span, in meters.</p><div data-gb-custom-block data-tag="hint" data-style="info" class="hint hint-info"><p>If you need to access the ground wire connections in your model, you must specify these ground wires as normal phase conductors and connect them to the ground by yourself.</p></div></td></tr><tr><td valign="top"><strong>Conductor type</strong></td><td>Specify one of the conductor or bundle type numbers listed in the first column of the <strong>table of conductor characteristics</strong>.</td></tr></tbody></table>
{% endstep %}

{% step %}

### Define the conductor & bundle characteristics

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-7919e4ecd38409ec3f1fa95cb455b72d6506ca76%2Fcable-conductor-parameter-definition.png?alt=media" alt=""><figcaption></figcaption></figure>

<table data-header-hidden data-search="false"><thead><tr><th width="200" valign="top"></th><th></th></tr></thead><tbody><tr><td valign="top"><strong>Number of conductor types (or Conductor type)</strong></td><td>Specify the number of conductor types (single conductor or bundle of subconductors) to be used. This parameter sets the number of rows for the conductors types table.. The phase conductors and ground wires can be either single conductors or bundles of subconductors.</td></tr><tr><td valign="top"><strong>Transposition options</strong></td><td><p>Select one of the following <strong>three</strong> parameters to specify the transposition:</p><ul><li><strong>Untransposed:</strong> A constant real transformation matrix is determined automatically by the program with the eigen analysis routines.</li><li><strong>Transposed:</strong> The line is modeled as perfectly transposed. The generalized Clarke transformation is used for an m-phase line.</li><li><strong>Transposed by 3 phases (double-circuit only):</strong> Applies only to the double-circuit lines. It is assumed that there is only zero-sequence coupling between the two separate circuits. Each circuit is perfectly balanced.</li></ul></td></tr><tr><td valign="top"><strong>Conductor internal inductance evaluated from</strong></td><td><p>Select one of the following <strong>three</strong> parameters to specify how the conductor internal inductance is computed:</p><ul><li><strong>T/D ratio:</strong> The conductor self-inductance and resistance are computed from the conductor diameter, T/D ratio, DC resistance, and relative permeability of conducting material and specified frequency. If you select T/D ratio, the internal inductance is computed from the T/D value specified in the table of conductors, assuming a hollow or solid conductor, where D is the conductor diameter and T is the thickness of the conducting material.</li><li><strong>Geometric Mean Radius (GMR):</strong> If you select Geometric Mean Radius (GMR), the conductor GMR is used to evaluate the internal inductance. When the conductor inductance is evaluated from the GMR, the specified frequency does not affect the conductor inductance. You have therefore to provide the manufacturer's GMR for the desired frequency (usually 50 Hz or 60 Hz).</li><li><strong>Reactance Xa at 1- meter spacing:</strong> Selecting Reactance Xa at 1-meter spacing uses the positive sequence reactance at the specified frequency of a three-phase line having 1- meter spacing between the three phases to compute the conductor's internal inductance.</li></ul></td></tr><tr><td valign="top"><strong>Include conductor skin effect</strong></td><td><p>Select this check box to account for the effect of frequency on conductor <strong>AC resistance</strong> and <strong>inductance</strong> (skin effect).</p><p>If this option is <strong>cleared</strong>, the conductor resistance remains equal to the value specified by the <strong>Conductor DC resistance</strong> parameter, and the inductance remains equal to its <strong>DC value</strong>, calculated from the <strong>conductor outside diameter</strong> and the <strong>T/D ratio</strong>.</p><p>When this option is <strong>selected</strong>, the conductor AC resistance and inductance are calculated using a frequency-dependent model that assumes either:</p><ul><li>a <strong>hollow conductor</strong> with the specified <strong>T/D ratio</strong>, or</li><li>a <strong>solid conductor</strong> when <strong>T/D = 0.5</strong>.</li></ul><p>The <strong>T/D ratio</strong> is always used to compute the AC resistance when skin effect is enabled, even when the conductor inductance is derived from the <strong>Geometric Mean Radius (GMR)</strong> or from the <strong>reactance at one-foot spacing</strong> (or <strong>one-meter spacing</strong> in metric units).<br>The <strong>ground skin effect</strong> is always included in the calculations and depends on the specified <strong>ground resistivity</strong>.</p></td></tr></tbody></table>

Elements in the table

<table data-search="false"><thead><tr><th width="200" valign="top">Column</th><th>Description</th></tr></thead><tbody><tr><td valign="top"><strong>Type</strong></td><td>Lists the conductor or bundle types in ascending order, starting at <strong>1</strong> and ending at the value specified by the <strong>Number of conductor types or bundle types</strong> parameter.</td></tr><tr><td valign="top"><strong>Outside diameter (cm)</strong></td><td>Specifies the conductor outside diameter, expressed in <strong>centimeters</strong> or <strong>inches</strong>, depending on the selected unit system.</td></tr><tr><td valign="top"><strong>DC resistance (Ohm/km)</strong></td><td></td></tr><tr><td valign="top"><strong>T/D ratio</strong></td><td><p>The <strong>T/D ratio</strong> is used to calculate the conductor <strong>AC resistance</strong> when <strong>Include conductor skin effect</strong> is enabled. It is also used to calculate the conductor <strong>self-inductance</strong> when the <strong>Conductor internal inductance evaluated from</strong> option is set to <strong>T/D ratio</strong>.</p><p>For a hollow conductor:</p><ul><li><strong>T</strong> = thickness of the conducting material</li><li><strong>D</strong> = outside conductor diameter</li></ul><p>A <strong>T/D ratio of 0.5</strong> corresponds to a <strong>solid conductor</strong>, while values between <strong>0</strong> and <strong>0.5</strong> represent hollow conductors.</p><p>For <strong>Aluminum Conductor Steel Reinforced (ACSR)</strong> conductors, the steel core can generally be neglected for skin-effect calculations. In such cases, the conductor may be modeled as a hollow aluminum conductor, with typical <strong>T/D ratios ranging from 0.3 to 0.4</strong>.</p><p>The valid range for this parameter is <strong>0 ≤ T/D ≤ 0.5</strong>.</p></td></tr><tr><td valign="top"><strong>Relative permeability</strong></td><td><p>If Conductor internal inductance evaluated from T/D ratio,</p><p>specify the relative permeability r of the conducting material. r = 1.0 for nonmagnetic conductors (aluminum, copper). This parameter is not accessible when the <strong>Include conductor skin effect</strong> parameter is not checked.</p></td></tr><tr><td valign="top"><strong>Conductors per bundle</strong></td><td>If Conductor internal inductance evaluated from T/D ratio, specify the number of subconductors in the bundle or 1 for single conductors.</td></tr><tr><td valign="top"><strong>Bundle diameter (cm)</strong></td><td><p>If Conductor internal inductance evaluated from T/D ratio, specify the bundle diameter in centimeters or inches. This parameter is not accessible when the Number of conductors per bundle is set to 1.</p><p>When you specify bundled conductors, the subconductors are assumed to be evenly spaced on a circle. If this is not the case, you must enter individual subconductor positions in the Line Geometry tab and lump these subconductors together by giving them the same Phase number parameter.</p></td></tr><tr><td valign="top"><strong>Angle conductor 1 (degre)</strong></td><td>If Conductor internal inductance evaluated from T/D ratio, specify an angle in degrees that determines the position of the first conductor in the bundle with respect to a horizontal line parallel to ground. This angle determines the bundle orientation. This parameter is not accessible when the number of “Conductors per bundle” is set to 1.</td></tr><tr><td valign="top"><strong>GMR (cm)</strong></td><td>If Conductor internal inductance evaluated from GMR, specify the GMR in centimeters or inches. The GMR at 60 Hz or 50 Hz is usually provided by conductor manufacturers. When the parameter box “<strong>Conductor internal inductance evaluated from</strong>” is set to T/D ratio, the value of the corresponding GMR giving the same conductor inductance is displayed.</td></tr><tr><td valign="top"><strong>Xa 1-meter spacing (Ohm/km)</strong></td><td>If Conductor internal inductance evaluated from Reactance Xa</td></tr></tbody></table>
{% endstep %}

{% step %}

### Compute

* Click the **Compute Parameters** icon. The report appears in the Log tab.
* Click on **Load parameters** at the right bottom of the machine mask.
* Click the **Apply** button.
  {% endstep %}

{% step %}

### View the log report

The **Log** tab displays a report of the electrical parameters calculated by the Line Generator. Once the parameter calculation is complete, the computed data can be reviewed in this tab and, if desired, loaded directly into the transmission line model.

The report includes the following electrical parameters:

* **Resistance (R), inductance (L), and capacitance (C) matrices**.
* The **Ti transformation matrix**.
* **Modal R, L, and C parameter vectors**.
* **Zero- and positive-sequence self-impedance parameters**, presented as R, L, and C vectors.
* **Mutual zero-sequence impedance parameters** between lines, presented as R, L, and C vectors.

This information can be used to verify the calculated line parameters before applying them to the model.

{% hint style="info" %}
The R, L, C parameters are always displayed respectively in ohms/km, henries/km, and farads/km
{% endhint %}

<details>

<summary>Example of a 735-kV three-phase line transposed</summary>

{% code overflow="wrap" lineNumbers="true" %}

```
----------------------------------------------------------------------------------
Hyperline Report                                   Thu Jun 29 16:42:57 EDT 2023
----------------------------------------------------------------------------------

COMMENTS: 

Example of a 735-kV three-phase line
Three bundles of 4 Bersfort ACSR 1355 MCM conductors
Two 1/2 inch-diameter steel ground wires
Ytower and Ymin are the average heights of conductors
LINE GEOMETRY:

Frequency (Hz): 60.0
Ground resistivity (Ω·m): 100.0
Number of phase conductors (bundles): 3
Number of ground wires (bundles): 2

------------------------------------------------------------------------
 Conductor     Phase         X        Y Tower      Y Min     Conductor  
  (bundle)     Number     (meters)    (meters)    (meters)      Type    
------------------------------------------------------------------------
     p1          1         -12.80160    20.72640    20.72640     1      
     p2          2           0.00000    20.72640    20.72640     1      
     p3          3          12.80160    20.72640    20.72640     1      
     g1          0          -8.99160    32.91840    32.91840     2      
     g2          0           8.99160    32.91840    32.91840     2      
------------------------------------------------------------------------

CONDUCTOR AND BUNDLE CHARACTERISTICS:

Number of conductor types or bundle types: 2
Transposition Options: Untransposed
Conductor internal inductance evaluated from: T/D Ratio
Include conductor skin effect: true

------------------------------------------------------------------------------------------------------------
 Conductor    Outside                                DC       Relative   Conductors    Bundle      Angle    
    Type      Diameter   T/D Ratio      GMR      Resistance Permeability Per Bundle   Diameter  Conductor 1 
                (cm)                    (cm)       (Ω/km)                               (cm)     (degrees)  
------------------------------------------------------------------------------------------------------------
     1           3.55600     0.37500  0.00000000  0.04304860     1.00000     4          64.65824       45.00
     2           1.27000     0.50000  0.00000000  3.10685596     1.00000     1           0.00000        0.00
------------------------------------------------------------------------------------------------------------

LINE PARAMETERS:

Resistance matrix (ohm/km):
 107.0972e-03  97.288142e-03  94.985601e-03 
 97.288142e-03  110.49444e-03  97.288142e-03 
 94.985601e-03  97.288142e-03  107.0972e-03 

Inductance matrix (H/km):
 1.5767213e-03  751.60911e-06  616.27982e-06 
 751.60911e-06  1.5708151e-03  751.60911e-06 
 616.27982e-06  751.60911e-06  1.5767213e-03 

Capacitance matrix (F/km):
 11.661265e-09  -2.1268277e-09  -583.62337e-12 
 -2.1268277e-09  12.117397e-09  -2.1268277e-09 
 -583.62337e-12  -2.1268277e-09  11.661265e-09 


Modal parameters for: Untransposed

Transformation matrix:
 595.18362e-03  -707.10678e-03  -413.16241e-03 
 539.91787e-03  -4.2940592e-15  811.53746e-03 
 595.18362e-03  707.10678e-03  -413.16241e-03 

Modal resistances [0 1 2 3 ... N] (ohm/km)
300.43789e-03 12.111597e-03 11.281739e-03 

Modal inductances [0 1 2 3 ... N] (H/km)
2.977745e-03 960.44144e-06 775.18526e-06 

Modal capacitances [0 1 2 3 ... N] (F/km)
8.5801475e-09 12.244888e-09 14.548121e-09 

Self impedance (Zero-sequence & Positive-sequence):

Line 1
[R0 R1] =   301.27087e-03   11.708982e-03 (ohm/km)
[L0 L1] =   2.9877512e-03   868.25318e-06 (H/km)
[C0 C1] =   8.5884565e-09   13.425735e-09 (F/km)

----------------------------------------------------------------------------------

```

{% endcode %}

</details>
{% endstep %}
{% endstepper %}

## Exercice

Compute the **per-kilometer resistance, inductance, and capacitance parameters** of a **three-phase, single-circuit, transposed transmission line** operating at **60 Hz**. The conductor arrangement and geometric data are provided in the figure below.

Using the same line configuration, investigate the impact of removing the transposition. Compare the resulting impedance parameters and discuss the effects of an **untransposed transmission line** on system performance.

For this exercise, use the following conductor data:

* The conductor internal inductance is determined from the **T/D ratio**. Use a value of **0.375** for the phase conductors and **0.5** for the ground wires.
* The **DC resistance** of the phase conductors is **0.04304 Ω/km**.
* The **DC resistance** of the ground wires is **3.107 Ω/km**.
* The **outside diameter** of each ground wire is **1.27 cm**.
* Assume the conductors have **no sag**.

Determine the line's **R**, **L**, and **C** parameters and evaluate how the absence of transposition affects the line impedance matrices and sequence parameters.

{% columns %}
{% column %}

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-b32de85813cc0804affbb01b3b38e806792a2b0d%2Fimage%20(1657).png?alt=media" alt=""><figcaption></figcaption></figure>
{% endcolumn %}

{% column %}

<figure><img src="https://3623212549-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FLxgTpoh7kyPmQ5vuyqD7%2Fuploads%2Fgit-blob-cfb633af842ff034e2c19b0f3c47d2dfbc9bffff%2Fimage%20(1658).png?alt=media" alt=""><figcaption><p><br>Conductor Geometry Diagram</p></figcaption></figure>
{% endcolumn %}
{% endcolumns %}

<details>

<summary><strong>List of values needed for this exercise (with answers)</strong></summary>

|                                                                                   |                                                                           |
| --------------------------------------------------------------------------------- | ------------------------------------------------------------------------- |
| Frequency of voltage transmitted by the line (Hz)                                 | 60                                                                        |
| Ground resistivity (omega m)                                                      | 100                                                                       |
| Number of phases conductor bundles                                                | 3                                                                         |
| Number of ground wires                                                            | 2                                                                         |
| Horizontal distance between each phase bundle (m)                                 | -12.80 for phase A, 0 for phase B and 12.80 for phase C                   |
| Vertical distance between each phase bundle (m)                                   | 20.73 for all phases                                                      |
| Vertical distance of conductor bundle at the tower (m)                            | 20.73 as there is no sag                                                  |
| Horizontal distance between ground wires                                          | -8.99 and +8.99                                                           |
| Vertical distance of ground wire at the tower                                     | 32.92 for both wires                                                      |
| Vertical distance of ground wire at mid-point of line (m)                         | 32.92 as there is no sag                                                  |
| Transposition information                                                         | Transposed                                                                |
| Method to compute internal inductance                                             | T/D 0.375 for phases, 0.5 for ground                                      |
| Outside diameter of individual conductor in bundle (cm)                           | 3.556 for phases, 1.27 for ground                                         |
| DC resistance of individual conductor (omega per km)                              | 0.04304 omega/km for phase conductors and 3.107 omega/km for ground wires |
| Number of conductors per bundle                                                   | 4 for phase and 1 for ground                                              |
| Bundle diameter (cm)                                                              | 45.72 \* sqrt(2) = 64.65 for phase and ground                             |
| Position of first conductor in the bundle counter-clockwise from x-axis (degrees) | **Answer**: 45 degrees                                                    |

</details>

### Results

* Open the mask of the line and go to Line Generator tab.
* Verify if the values in your table match below.
* After verifying these values, enter them in the Line Generator tab.
* Click the **Compute** icon.
* In the log tab, you should have the required results.
* Change the transposition option and re-compute to notify the impact.

## **REFERENCES**

\[1] HYPERSIM Reference guide manual for software version 9.1.\
\[2] Dommel, H., et al., Electromagnetic Transients Program Reference Manual (EMTP Theory Book), 1986.\
\[3] Carson, J. R., "Wave Propagation in Overhead Wires with Ground Return," Bell Systems Technical Journal, Vol. 5, pp 539-554, 1926.


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/model-and-simulation/optimize-the-model/use-parameter-generators/line-parameters.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.