> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/model-and-simulation/optimize-the-model/use-parameter-generators/line-parameters/typical-electrical-parameters.md).

# Typical Electrical Parameters

## Description

Overhead transmission lines and underground cables provide typical per-phase electrical parameters for commonly used voltage levels. The data below can serve as reference values for studies and for configuring HYPERSIM line models at 60 Hz.

## Overhead transmission lines

### Typical data

The following table lists typical per-phase parameters for overhead lines from 230 kV to 1100 kV \[1], at 60 Hz. All lines use bundled conductors except the 230 kV line.

| Nominal voltage                         | 230 kV | 345 kV | 500 kV | 765 kV | 1100 kV |
| --------------------------------------- | ------ | ------ | ------ | ------ | ------- |
| **R (ohm/km)**                          | 0.050  | 0.037  | 0.028  | 0.012  | 0.005   |
| **X**<sub>**L**</sub>**&#x20;(ohm/km)** | 0.488  | 0.367  | 0.325  | 0.329  | 0.292   |
| **B**<sub>**C**</sub>**&#x20;(uS/km)**  | 3.371  | 4.518  | 5.200  | 4.978  | 5.544   |
| **L (mH/km)**                           | 1.2945 | 0.9735 | 0.8621 | 0.8727 | 0.7746  |
| **C (uF/km)**                           | 0.0089 | 0.0120 | 0.0138 | 0.0132 | 0.0147  |
| **Zc (ohm)**                            | 380    | 285    | 250    | 257    | 230     |

The parameters above are per-phase values. Use them as positive-sequence inputs in HYPERSIM line models such as [PI Section, 3-ph](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/network-lines-and-cables/pi-section-3-ph.md) and [Constant Param, 3-ph](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/network-lines-and-cables/constant-param-3-ph.md)

{% hint style="info" %}
Estimate zero-sequence values by applying a zero/positive-sequence ratio taken from a known transmission line.
{% endhint %}

### Transmission line data from EMTP examples

**735 kV continuously transposed transmission line** (Data taken from EMTP v4.1 application cases \[2])

| Parameter                               | Zero sequence | Positive sequence | Zero/Positive sequence ratio |
| --------------------------------------- | ------------- | ----------------- | ---------------------------- |
| **R (ohm/km)**                          | 0.2693        | 0.0154            | 17.49                        |
| **X**<sub>**L**</sub>**&#x20;(ohm/km)** | 1.130         | 0.3356            | 3.37                         |
| **B**<sub>**C**</sub>**&#x20;(uS/km)**  | 3.037         | 4.909             | 0.62                         |
| **L (mH/km)**                           | 2.9974        | 0.8902            | 3.37                         |
| **C (uF/km)**                           | 0.008056      | 0.0130            | 0.62                         |

**400 kV transmission line** (Data taken from the BenchmarkT2WindHVDC EMTP benchmark)

| Parameter                               | Zero sequence | Positive sequence | Zero/Positive sequence ratio |
| --------------------------------------- | ------------- | ----------------- | ---------------------------- |
| **R (ohm/km)**                          | 0.3030        | 0.0209            | 14.5                         |
| **X**<sub>**L**</sub>**&#x20;(ohm/km)** | 1.1892        | 0.3192            | 3.73                         |
| **B**<sub>**C**</sub>**&#x20;(uS/km)**  | 3.1743        | 5.1949            | 0.61                         |
| **L (mH/km)**                           | 3.1544        | 0.8467            | 3.73                         |
| **C (uF/km)**                           | 0.0084        | 0.0137            | 0.61                         |

**345 kV transmission line** (Data taken from the IEEE39 EMTP v3 example).

| Parameter                               | Zero sequence | Positive sequence | Zero/Positive sequence ratio |
| --------------------------------------- | ------------- | ----------------- | ---------------------------- |
| **R (ohm/km)**                          | 1.36245       | 0.0981            | 13.89                        |
| **X**<sub>**L**</sub>**&#x20;(ohm/km)** | 0.718996      | 0.36058           | 1.99                         |
| **B**<sub>**C**</sub>**&#x20;(uS/km)**  | 2.74          | 4.49              | 0.61                         |
| **L (mH/km)**                           | 1.9072        | 0.9565            | 1.99                         |
| **C (uF/km)**                           | 0.00727       | 0.0119            | 0.61                         |

**345 kV transmission line** (Data taken from the IEEE39 EMTP v4 example)

| Parameter                               | Zero sequence | Positive sequence | Zero/Positive sequence ratio |
| --------------------------------------- | ------------- | ----------------- | ---------------------------- |
| **R (ohm/km)**                          | 0.1268        | 0.0315            | 4.03                         |
| **X**<sub>**L**</sub>**&#x20;(ohm/km)** | 0.7917        | 0.3757            | 2.11                         |
| **B**<sub>**C**</sub>**&#x20;(uS/km)**  | 2.8045        | 4.3030            | 0.65                         |
| **L (mH/km)**                           | 2.1000000     | 0.996640          | 2.11                         |
| **C (uF/km)**                           | 0.0074393     | 0.011414          | 0.65                         |

**230 kV continuously transposed transmission line** (Data taken from the TRV EMTP example)

| Parameter                               | Zero sequence | Positive sequence | Zero/Positive sequence ratio |
| --------------------------------------- | ------------- | ----------------- | ---------------------------- |
| **R (ohm/km)**                          | 0.3167        | 0.0243            | 13.03                        |
| **X**<sub>**L**</sub>**&#x20;(ohm/km)** | 1.2147        | 0.3477            | 3.49                         |
| **B**<sub>**C**</sub>**&#x20;(uS/km)**  | 2.9669        | 4.7500            | 0.62                         |
| **L (mH/km)**                           | 3.222         | 0.9238            | 3.49                         |
| **C (uF/km)**                           | 0.00787       | 0.0126            | 0.62                         |

{% hint style="info" %}
According to the IEEE PSRC working group report \[3], the zero-sequence inductance is typically between 2 and 3.5 times the positive-sequence inductance. The data above follow this guidance.
{% endhint %}

## Underground cables

### Typical data

Underground cables have much lower series inductance and much higher shunt capacitance than overhead lines. The lower series inductance results from closer conductor spacing. The higher shunt capacitance is due to the proximity of the conductor (surrounded by the grounded sheath) to ground potential and the insulation’s dielectric constant, which is several times that of air \[3].

The following table shows typical data for two cable types (from \[1])—direct-buried paper-insulated lead-covered (PILC) and high-pressure pipe type (PIPE)—at nominal voltages of 115, 230, and 500 kV. The characteristic impedance Zc of a cable is about one-tenth to one-fifth that of an overhead line with the same voltage rating.

| Nominal voltage                         | 115 kV | 115 kV | 230 kV | 230 kV | 500 kV |
| --------------------------------------- | ------ | ------ | ------ | ------ | ------ |
| **Cable type**                          | PILC   | PIPE   | PILC   | PIPE   | PILC   |
| **R (ohm/km)**                          | 0.0590 | 0.0379 | 0.0277 | 0.0434 | 0.0128 |
| **X**<sub>**L**</sub>**&#x20;(ohm/km)** | 0.3026 | 0.1312 | 0.3388 | 0.2052 | 0.2454 |
| **B**<sub>**C**</sub>**&#x20;(uS/km)**  | 230.4  | 160.8  | 245.6  | 298.8  | 96.5   |
| **L (mH/km)**                           | 0.8027 | 0.3480 | 0.8987 | 0.5443 | 0.6510 |
| **C (uF/km)**                           | 0.6112 | 0.4265 | 0.6515 | 0.7926 | 0.2560 |
| **Zc (ohm)**                            | 36.2   | 24.5   | 37.1   | 26.2   | 50.4   |

Use this table as a reference only. For cable modeling, use the [Cable Data](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/network-lines-and-cables/cable-data.md) module to calculate electrical parameters from cable geometry.

The generated data are then used by the [Wideband Line/Cable Fitter](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/network-lines-and-cables/wideband-line-cable-fitter.md), which creates the cable case for the [Wideband Line/Cable](https://www.opal-rt.com/docs/hypersim/library-blocks-reference/network-lines-and-cables/wideband-line-cable.md) model.

## References

Data shown in this page is taken from the following references:

1. Kundur, P., Neal J. Balu, and Mark G. Lauby. Power System Stability and Control. New York: McGraw-Hill, 1994.
2. EMTPWorks 4.1 ApplicationCases examples.
3. PES Power System Relaying and Control Committee, “AC Transmission Line Model Parameter Validation”. PES technical report, 2014.


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/model-and-simulation/optimize-the-model/use-parameter-generators/line-parameters/typical-electrical-parameters.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.