> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/hypersim/model-and-simulation/phasor-domain-with-ephasorsim/integrate-a-power-system-model-to-ephasorsim/native-library-components/shunt-components.md).

# Shunt Components

## Positive-sequence network <a href="#parameters" id="parameters"></a>

In a **positive-sequence network**, a shunt represents a fixed shunt element connected to a bus. The shunt can model either capacitive or inductive reactive power compensation:

* **Positive Q** → inductive shunt
* **Negative Q** → capacitive shunt

### Fixed shunt

| Excel Column Name | Native Component Parameter | Description                                                                                                           |
| ----------------- | -------------------------- | --------------------------------------------------------------------------------------------------------------------- |
| **ID**            | `name`                     | Shunt identifier.                                                                                                     |
| **Status**        | `status`                   | <p>Initial service status.<br><code>1</code> = connected<br><code>0</code> = disconnected</p>                         |
| **Bus**           | `bus`                      | Bus identifier where the shunt is connected.                                                                          |
| **P (MW)**        | `power.re`                 | Active power injection.                                                                                               |
| **Q (kVAr)**      | `power.im`                 | Reactive power injection. Positive values represent inductive shunts and negative values represent capacitive shunts. |

## Multiphase network <a href="#parameters" id="parameters"></a>

In a **multiphase network**, shunt components can be used to model single-phase, two-phase, and three-phase grounded-wye (Yg) shunt devices.

### Single-phase shunt

| Excel Column Name  | Native Component Parameter | Description                                                               |
| ------------------ | -------------------------- | ------------------------------------------------------------------------- |
| **ID**             | `name`                     | Shunt identifier.                                                         |
| **Status**         | `status`                   | Initial service status for phase 1 (`1` = connected, `0` = disconnected). |
| **kV (ph-gr RMS)** | `vll`                      | Rated phase-to-ground voltage.                                            |
| **Bus1**           | `buses`                    | Connected phase bus identifier.                                           |
| **P1 (kW)**        | `power_re`                 | Active power for phase 1.                                                 |
| **Q1 (kVAr)**      | `power_im`                 | Reactive power for phase 1.                                               |

### Two-phase shunt

| Excel Column Name    | Native Component Parameter | Description                                                                      |
| -------------------- | -------------------------- | -------------------------------------------------------------------------------- |
| **ID**               | `name`                     | Shunt identifier.                                                                |
| **Status1, Status2** | `status`                   | Initial service status for phases 1 and 2 (`1` = connected, `0` = disconnected). |
| **kV (ph-gr RMS)**   | `vll`                      | Rated phase-to-ground voltage.                                                   |
| **Bus1, Bus2**       | `buses`                    | Connected phase bus identifiers.                                                 |
| **P1, P2 (kV)**      | `power_re`                 | Active power for phases 1 and 2.                                                 |
| **Q1, Q2 (kVAr)**    | `power_im`                 | Reactive power for phases 1 and 2.                                               |

### Three-phase shunt

| Excel Column Name             | Native Component Parameter | Description                                                                          |
| ----------------------------- | -------------------------- | ------------------------------------------------------------------------------------ |
| **ID**                        | `name`                     | Shunt identifier.                                                                    |
| **Status1, Status2, Status3** | `status`                   | Initial service status for phases 1, 2, and 3 (`1` = connected, `0` = disconnected). |
| **kV (ph-gr RMS)**            | `vll`                      | Rated phase-to-ground voltage.                                                       |
| **Bus1, Bus2, Bus3**          | `buses`                    | Connected phase bus identifiers.                                                     |
| **P1, P2, P3 (kV)**           | `power_re`                 | Active power for phases 1, 2, and 3.                                                 |
| **Q1, Q2, Q3 (kVAr)**         | `power_im`                 | Reactive power for phases 1, 2, and 3.                                               |

{% hint style="info" %}
For the case of three-phase shunt components, the admittance matrix is defined as:

$$
Y = \frac{1}{1000\*V^2}\begin{bmatrix} P\_a-jQ\_a & 0 & 0 \ 0 & P\_b-jQ\_b & 0 \ 0 & 0 & p\_c-jQ\_c \end{bmatrix}
$$
{% endhint %}


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/hypersim/model-and-simulation/phasor-domain-with-ephasorsim/integrate-a-power-system-model-to-ephasorsim/native-library-components/shunt-components.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.