> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/op1400pr/operate-the-test-bench/troubleshoot-the-test-bench.md).

# Troubleshoot the Test Bench

{% hint style="danger" %}
**Before opening the cabinet door for troubleshooting**, make sure that:

* The **mains supply** is **turned off**
* **No external energy source** is **connected** to the **output interface**, the **LP, or HP bus bar** modules.

Failure to do so may put the user at risk of **receiving an electric shock**.

Please **read carfully** the [**Safety & Servicing Guidelines**](https://www.opal-rt.com/docs/op1400pr/op1400pr-overview/safety-and-servicing-guidelines.md) before any interventions.
{% endhint %}

## Troubleshooting <a href="#troubleshooting" id="troubleshooting"></a>

<details>

<summary>Unable to turn on the ITECH DC power supplies.</summary>

* **Verify** that the **power knob** on the **ITECH DC power supply** is set to the **ON (I)** position.

<figure><img src="https://3155739458-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FzVJdfp93TWLISP6nkqTs%2Fuploads%2Fu8WfgA9Ua6wk2izxOPZO%2Fimage.png?alt=media&amp;token=045a2dee-4990-414c-b3b2-a607065ba048" alt="" width="375"><figcaption></figcaption></figure>

* **Verify** that the **3-phase mains input disconnect** switch on the **PDU** is in the **ON** position.

<figure><img src="https://3155739458-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FzVJdfp93TWLISP6nkqTs%2Fuploads%2FS9h4z0BObVaX9uKTQ70M%2Fimage.png?alt=media&amp;token=56c6ce31-3178-48c2-8623-c05eb7773da5" alt="" width="375"><figcaption></figcaption></figure>

* **Verify** that the **building disconnect switch** is **ON**.

<figure><img src="https://3155739458-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FzVJdfp93TWLISP6nkqTs%2Fuploads%2FhB9qZ0quxm1FCwtaXv7s%2Fimage.png?alt=media&amp;token=8be11057-1c64-4bd0-a099-4f78bc8d686d" alt="" width="123"><figcaption></figcaption></figure>

* **Verify** that the “**AC MAINS**” **LED** on the **PDU** front panel is **ON**.

<figure><img src="https://3155739458-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FzVJdfp93TWLISP6nkqTs%2Fuploads%2FqSmY6pNoNzKXp1zP41gi%2Fimage.png?alt=media&amp;token=b7d66b51-1c8f-414f-a340-2699a0850ebb" alt="" width="375"><figcaption></figcaption></figure>

* **Verify** that the **emergency stop** **button** on the **E-stop module** is deactivated (**24 V ON light** must be lit).
  * **Rotate** the **E-stop button clockwise** to **release** it.
  * Press the **START** button to **enable the PDU main power** **contactor**, and ensure that the **Start/Stop button is lit**.

<figure><img src="https://3155739458-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FzVJdfp93TWLISP6nkqTs%2Fuploads%2FPUJsLHDfQ78Cay9fiEbv%2Fimage.png?alt=media&amp;token=ca23b628-7ca7-46ad-8584-e043e09acffe" alt="" width="375"><figcaption></figcaption></figure>

* **Verify** that the **signal harness** on the **rear panels** of the **E-stop module** and **PDU** (**P1 connector**) is correctly plugged in.
  * For **pin assignment**, refer to the **illustration below** or the page entitled “**Terminal Block Pinout (TBP)**” in the “**Connection and Signals Overview**” document delivered with your system.

<figure><img src="https://3155739458-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FzVJdfp93TWLISP6nkqTs%2Fuploads%2Fqo0zv0hmrQmvP3NbFLz4%2Fimage.png?alt=media&amp;token=1a346155-290b-4e30-afac-3dd50f421586" alt="" width="375"><figcaption></figcaption></figure>

* Verify that every power bar is plugged into a powered external outlet and turned on. Check for loose connections, a tripped breaker, and illuminated green indicators.

<figure><img src="https://3155739458-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FzVJdfp93TWLISP6nkqTs%2Fuploads%2FbEA1JrxDmUpixlT4znDQ%2Fimage.png?alt=media&amp;token=7256bdab-5019-4e83-9566-0b3a8e61e9aa" alt="" width="563"><figcaption></figcaption></figure>

* **Verify** that the **power switch** is **turned ON (I)** on the **PDU rear panel**.

<figure><img src="https://3155739458-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FzVJdfp93TWLISP6nkqTs%2Fuploads%2FXkF8xIVmRyeXiH2f6Ulv%2Fimage.png?alt=media&amp;token=a87c3c99-5f40-4a8f-9607-f706f1cacabd" alt="" width="563"><figcaption></figcaption></figure>

</details>

<details>

<summary>Overcurrent protection on the 3-phase mains input keeps tripping when working in the medium to high-power range on the OP1400PR-30 or OP1400PR-60 test benches.</summary>

* To prevent the input protection from tripping on test benches with three DC power supplies, **verify** tha**t the wires follow the interleaved color scheme** shown below (see also [Connect the Test Bench](https://www.opal-rt.com/docs/op1400pr/get-started/connect-the-test-bench.md#pdu-ac-supply-to-the-dc-power-supplies)⁣).

<figure><img src="https://3155739458-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FzVJdfp93TWLISP6nkqTs%2Fuploads%2FZnSd3VnX8sJQxThjS67A%2Fimage.png?alt=media&amp;token=f3f250df-b539-490f-b821-eacb18dca01c" alt="" width="563"><figcaption></figcaption></figure>

</details>

<details>

<summary>The OP8110 amplifier ends up in an undervoltage or overvoltage fault when power starts being consumed or produced.</summary>

* **Verify** that the **maximum positive and negative current limits** of the **DC power supplies** are **properly set** within the **recommended range**. See the [**Functional overview**](https://www.opal-rt.com/docs/op1400pr/op1400pr-overview/description-and-components/dc-power-supply.md#functional-overview) section in the [DC power supply page](https://www.opal-rt.com/docs/op1400pr/op1400pr-overview/description-and-components/dc-power-supply.md).

</details>

<details>

<summary>The OP8110 amplifier seems to produce an output voltage but it does not appear on the DUT<br>output.</summary>

* **Verify** that the **DUT channel** is **locally enabled** and **remotely activated**. If **bus bars** are present, check if the white **light** of the the **START/STOP button is lit**.
* **Verify** that the **wiring from the amplifier to the DUT interface is correct.**

</details>

<details>

<summary>The OP8110 amplifier does not produce an output voltage.</summary>

* **Verify** that the **SFP cables** are **correctly connected** between the **amplifier** (right SFP port identified as **GTP A**) and the **simulator**. Refer to [Connect the Test Bench](https://www.opal-rt.com/docs/op1400pr/get-started/connect-the-test-bench.md#cable-routing).
* **Verify** that the **SFP communication link** has been **correctly configured in RT-LAB** and that **the model is running** (measurements coming from the amplifier should show slight noise).
* **Verify** that the [**OP8110 amplifier** unit is **turned on**](https://www.opal-rt.com/docs/op1400pr/operate-the-test-bench/operate-the-test-bench.md#turn-on-the-op8110-amplifiers) (the light inside the power-on button on the front panel is green), refer to the issue [**OP8110 amplifier does not turn on**](#the-op8110-amplifier-does-not-turn-on) if necessary.

</details>

<details>

<summary>Cannot enable the DC link to an OP8110 amplifier through RT-LAB (DC precharge never starts).</summary>

* **Verify** that the [**SFP cable** is **correctly connected**](https://www.opal-rt.com/docs/op1400pr/get-started/connect-the-test-bench.md#cable-routing) between the **OP8110 amplifier** (right SFP port) and **the simulator**.
* **Verify** that the **SFP communication link** has been **correctly configured in RT-LAB** and that **the model is running** (measurements coming from the amplifier should have a little noise).
* **Verify** that the [**OP8110 amplifier unit is turned on**](https://www.opal-rt.com/docs/op1400pr/operate-the-test-bench/operate-the-test-bench.md#turn-on-the-op8110-amplifiers) (the light inside the power-on button on the front panel is green), refer to the issue [**OP8110 amplifier does not turn on**](#the-op8110-amplifier-does-not-turn-on) if necessary.
* **Power down** the DC [**DC power supply**](https://www.opal-rt.com/docs/op1400pr/op1400pr-overview/description-and-components/dc-power-supply.md) and wait five minutes. Then **re-enable the precharge sequence**. See the OP8110 [**DC Precharge section**](https://www.opal-rt.com/docs/op1400pr/op1400pr-overview/description-and-components/op8110-4q-power-amplifier.md#dc-precharge).

</details>

<details>

<summary>The OP8110 amplifier does not turn on.</summary>

* **Verify** that the **auxiliary supply cables** (one for OP8110-3, two for OP8110-6) are **correctly plugged** into the **OP8110's** **12 V AUX** **connectors** on the **rear panel**.

<figure><img src="https://3155739458-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FzVJdfp93TWLISP6nkqTs%2Fuploads%2FOJL3J78mc3zf1fLEtUC5%2Fimage.png?alt=media&amp;token=080f7f23-59e0-4803-b0da-bfe12f99fdc8" alt="" width="563"><figcaption><p><strong>OP8110-3</strong> AUX connector</p></figcaption></figure>

<figure><img src="https://3155739458-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FzVJdfp93TWLISP6nkqTs%2Fuploads%2F6gMhqpHyAdZHM804HQbv%2Fimage.png?alt=media&amp;token=65718e9d-b1cb-4aa0-adb4-6875928f3602" alt="" width="563"><figcaption><p><strong>OP8110-6</strong> AUX connectors</p></figcaption></figure>

* **Verify** that the **auxiliary cables** on the **PDU rear** panel are **correctly plugged in**.

<figure><img src="https://3155739458-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FzVJdfp93TWLISP6nkqTs%2Fuploads%2FkNUMmsuK0Tgvaq7ohyoX%2Fimage.png?alt=media&amp;token=58c175cb-6d4d-4460-be3d-549609312f04" alt="" width="563"><figcaption><p><strong>PDU</strong> AUX connectors</p></figcaption></figure>

</details>

<details>

<summary>LP or HP bus bar is not powered (the 24 V ON light is not lit).</summary>

* **Verify** that the **emergency stop** **button** on the **E-stop module** is deactivated (**24 V ON light** must be lit).

  * **Rotate** the **E-stop button clockwise** to **release** it.
  * Press the **START** button to **enable the PDU main power** **contactor**, and ensure that the **START/STOP button is lit**.

  <figure><img src="https://3155739458-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FzVJdfp93TWLISP6nkqTs%2Fuploads%2FPUJsLHDfQ78Cay9fiEbv%2Fimage.png?alt=media&amp;token=ca23b628-7ca7-46ad-8584-e043e09acffe" alt="" width="375"><figcaption></figcaption></figure>
* **Verify** that the **signal harness** on the **rear panels** of the **E-stop module** and **PDU** (**P1 connector**) is correctly plugged in.

  * For **pin assignment**, refer to the **illustration below** or the page entitled “**Terminal Block Pinout (TBP)**” in the “**Connection and Signals Overview**” document delivered with your system.

  <figure><img src="https://3155739458-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FzVJdfp93TWLISP6nkqTs%2Fuploads%2Fqo0zv0hmrQmvP3NbFLz4%2Fimage.png?alt=media&amp;token=1a346155-290b-4e30-afac-3dd50f421586" alt="" width="375"><figcaption></figcaption></figure>
* **Verify** that the **24 V ON light** on the **PDU** front panel is **lit**.

<figure><img src="https://3155739458-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FzVJdfp93TWLISP6nkqTs%2Fuploads%2FGJepzNObbwXpMXxza787%2Fimage.png?alt=media&amp;token=ef3bbfff-c549-42c0-944d-ea88f5cee78b" alt="" width="262"><figcaption></figcaption></figure>

</details>

<details>

<summary>LP or HP bus bar outputs cannot be turned on (the light between the START and STOP buttons does not turn on).</summary>

* **Verify** that the front panel **24 V ON light** **is lit**, refer to [**LP or HP bus bar is not powered**](#lp-or-hp-bus-bar-is-not-supplied-24-v-on-light-is-not-lit) if necessary.
* Enable the **DUT** by **pressing** the **START button**. The **button light** should start **blinking**.
* **Activate** the **DUT** remotely. The **button light** should be **lit continuously**.
* **Verify** that a **DB37 harness** is **connected** between the **bus bar DI connector** (rear panel) and the appropriate **digital output connector** of the **simulator**.
* **Verify** that the **digital output module** of the **simulator** is **correctly configured** (a loopback test can be done with the DB37 harness looping back to a digital input module).

</details>

<details>

<summary>The START/STOP button on the E-stop module is not working; light does not turn on or does not remain on after you press START.</summary>

* **Verify** that the **signal harness** on the **rear panel** of the **E-stop module** and on the **rear panel** of the **PDU** (P1 connectors) is correctly plugged in.

<figure><img src="https://3155739458-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FzVJdfp93TWLISP6nkqTs%2Fuploads%2Fqo0zv0hmrQmvP3NbFLz4%2Fimage.png?alt=media&amp;token=1a346155-290b-4e30-afac-3dd50f421586" alt="" width="375"><figcaption></figcaption></figure>

* Verify that **every power bar** is plugged into a **powered external outlet** and **turned on** (green light on). Check for **loose connections** and **tripped breakers**.

<figure><img src="https://3155739458-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FzVJdfp93TWLISP6nkqTs%2Fuploads%2FbEA1JrxDmUpixlT4znDQ%2Fimage.png?alt=media&amp;token=7256bdab-5019-4e83-9566-0b3a8e61e9aa" alt="" width="563"><figcaption></figcaption></figure>

* **Verify** that the **power switch** is **turned ON (I)** on the **PDU** rear panel.

<figure><img src="https://3155739458-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FzVJdfp93TWLISP6nkqTs%2Fuploads%2FXkF8xIVmRyeXiH2f6Ulv%2Fimage.png?alt=media&amp;token=a87c3c99-5f40-4a8f-9607-f706f1cacabd" alt="" width="563"><figcaption></figcaption></figure>

* Verify that the **24 V ON light** on the PDU front panel is **lit**.

<figure><img src="https://3155739458-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FzVJdfp93TWLISP6nkqTs%2Fuploads%2FGJepzNObbwXpMXxza787%2Fimage.png?alt=media&amp;token=ef3bbfff-c549-42c0-944d-ea88f5cee78b" alt="" width="262"><figcaption></figcaption></figure>

</details>

## Need additional support? <a href="#need-additional-support" id="need-additional-support"></a>

For issues or technical support requests not covered here, visit the [OPAL-RT knowledge base](http://www.opal-rt.com/support-knowledge-base/) (free login required).

If an issue persists, contact [OPAL-RT technical support](https://www.opal-rt.com/contact-technical-support/).


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/op1400pr/operate-the-test-bench/troubleshoot-the-test-bench.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.