> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/smart-power-simulation-software-sps/blocks-functions-tools/basics/passives/three-phase-series-rlc-load.md).

# Three-Phase Series RLC Load

## Description

<figure><img src="https://799605156-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FdlNg8IbOdahCpFCyzxSN%2Fuploads%2Fgit-blob-dda0be5eb189e69cebce0e72325a734458b130dd%2F3P_serie_RLC_load_block.png?alt=media" alt=""><figcaption></figcaption></figure>

The **Three-Phase Series RLC Load** block, located in the **OPAL-RT SPS Software/Passives** library, implements a three-phase balanced load as a series combination of RLC elements. At the specified frequency, the load exhibits a constant impedance. The active and reactive powers absorbed by the load are proportional to the square of the applied voltage.

Only elements associated with nonzero powers are displayed in the block icon.

## Ports

### Conserving

<table><thead><tr><th width="202.79998779296875">Port</th><th>Description</th></tr></thead><tbody><tr><td><strong>A</strong> — Phase A (Specialized electrical)</td><td>Specialized electrical conserving port associated with phase A.</td></tr><tr><td><strong>B</strong> — Phase B (Specialized electrical)</td><td>Specialized electrical conserving port associated with phase B.</td></tr><tr><td><strong>C</strong> — Phase C (Specialized electrical)</td><td>Specialized electrical conserving port associated with phase C.</td></tr><tr><td><strong>N</strong> — Neutral (Specialized electrical)</td><td>Specialized electrical conserving port associated with the neutral. <strong>Dependencies:</strong> To enable this port, set <strong>Configuration</strong> to Y (neutral).</td></tr></tbody></table>

## Parameters

To edit block parameters interactively, use the Property Inspector. From the Simulink® Toolstrip, on the **Simulation** tab, in the **Prepare** gallery, select **Property Inspector**.

### Parameters

<table><thead><tr><th width="238.800048828125">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Configuration</strong> — Connection of three phases<br>Y(grounded) (default) | Y(floating) | Y(neutral) | Delta</td><td><p>The connection of the three phases. Select one of the following:</p><ul><li>Y(grounded) — Neutral is grounded.</li><li>Y(floating) — Neutral is not accessible.</li><li>Y(neutral) — Neutral is made accessible through a fourth connector.</li><li>Delta — Three phases connected in delta.</li></ul><p>The block icon is updated according to the load connection.</p></td></tr><tr><td><strong>Nominal phase-to-phase voltage Vn</strong> — Nominal phase-to-phase voltage of load<br>1000 (default)</td><td>Nominal phase-to-phase voltage of the load, in volts RMS (Vrms). <strong>Dependencies:</strong> To enable this parameter, clear the <strong>Specify PQ powers for each phase</strong> parameter.</td></tr><tr><td><strong>Nominal phase-to-neutral voltages [Va Vb Vc] (Vrms)</strong> — Nominal phase-to-neutral voltages of load<br>[1e3 1e3 1e3] (default)</td><td>Nominal phase-to-neutral voltages of the load, in volts RMS (Vrms). <strong>Dependencies:</strong> To enable this parameter, select the <strong>Specify PQ powers for each phase</strong> parameter.</td></tr><tr><td><strong>Nominal frequency fn (Hz)</strong> — Nominal frequency<br>60 (default)</td><td>The nominal frequency, in hertz (Hz). Default is 60.</td></tr><tr><td><strong>Specify PQ powers for each phase</strong> — Option to specify PQ powers for each phase<br>off (default) | on</td><td>Option to specify active powers, inductive reactive powers, and capacitive reactive powers for each phase of the load.</td></tr><tr><td><strong>Active power P (W)</strong> — Three-phase active power of load<br>10e3 (default)</td><td>Three-phase active power of the load, in watts. <strong>Dependencies:</strong> To enable this parameter, clear the <strong>Specify PQ powers for each phase</strong> parameter.</td></tr><tr><td><strong>Inductive reactive power QL (positive var)</strong> — Three-phase inductive reactive power QL<br>100 (default) | nonnegative scalar</td><td>Three-phase inductive reactive power QL, in vars. <strong>Dependencies:</strong> To enable this parameter, clear the <strong>Specify PQ powers for each phase</strong> parameter.</td></tr><tr><td><strong>Capacitive reactive power QC (negative var)</strong> — Three-phase capacitive reactive power QC<br>100 (default) | nonnegative scalar</td><td>Three-phase capacitive reactive power QC, in vars. <strong>Dependencies:</strong> To enable this parameter, clear the <strong>Specify PQ powers for each phase</strong> parameter.</td></tr><tr><td><strong>Active powers [Pa Pb Pc] (W)</strong> — Three-phase active power of load<br>[10e3 9e3 11e3] (default) | vector of three nonnegative elements</td><td>Three-phase active power of the load, in watts. You can specify different powers for each phase, including 0. <strong>Dependencies:</strong> To enable this parameter, select the <strong>Specify PQ powers for each phase</strong> parameter.</td></tr><tr><td><strong>Inductive reactive powers [QLa QLb QLc] (positive var)</strong> — Three-phase inductive reactive power QL<br>[100 90 110] (default) | vector of three nonnegative elements</td><td>Three-phase inductive reactive power QL, in vars. You can specify different powers for each phase, including 0. <strong>Dependencies:</strong> To enable this parameter, select the <strong>Specify PQ powers for each phase</strong> parameter.</td></tr><tr><td><strong>Capacitive reactive powers [QCa QCb QCc] (negative var)</strong> — Three-phase capacitive reactive power QC<br>[100 90 110] (default) | vector of three nonnegative elements</td><td>Three-phase capacitive reactive power QC, in vars. You can specify different powers for each phase, including 0. <strong>Dependencies:</strong> To enable this parameter, select the <strong>Specify PQ powers for each phase</strong> parameter.</td></tr><tr><td><strong>Measurements</strong> — Type of measurements<br>None (default) | Branch voltages | Branch currents | Branch voltages and currents</td><td>Select Branch voltages to measure the three voltages across each phase of the block terminals. For a Y connection, these voltages are the phase-to-ground or phase-to-neutral voltages. For a delta connection, these voltages are the phase-to-phase voltages.<br>Select Branch currents to measure the three total currents (sum of R, L, C currents) flowing through each phase. For a delta connection, these currents are the currents flowing in each branch of the delta.<br>Select Branch voltages and currents to measure the three voltages and the three currents of the block.<br>Place a Multimeter block in your model to display the selected measurements during the simulation. In the <strong>Available Measurements</strong> list box of the Multimeter block, the measurements are identified by a label followed by the block name.</td></tr></tbody></table>

**Measurement labels by connection:**

| Measurement     | Y(grounded) | Y(floating) | Y(neutral) | Delta |
| --------------- | ----------: | ----------: | ---------: | ----: |
| Branch voltages |        Uag: |        Uan: |     Uan`:` |  Uab: |
| Branch currents |        Iag: |        Ian: |       Ian: |  Iab: |

### Load Flow

<table><thead><tr><th width="123.5999755859375">Parameter</th><th>Description</th></tr></thead><tbody><tr><td><strong>Load type</strong> — Option to specify load type<br>constant Z (default) | constant PQ | constant I</td><td>Specify the load type.<br>If you select <strong>constant Z</strong>, the load impedance is determined from the nominal phase-to-phase voltage Vn, active power P, and reactive power (QL-QC) specified on the <strong>Parameters</strong> tab of the block dialog box. During the load flow solution, the impedance is kept constant. The effective P and Q therefore vary proportionally to the square of the bus voltage computed by the Load Flow tool.<br>If you select <strong>constant PQ</strong>, the active power P and reactive power Q are kept constant and equal to the values specified on the <strong>Parameters</strong> tab of the block dialog box. When you apply the load flow solution to the model (by clicking the <strong>Apply</strong> button of the Load Flow tool), the <strong>Nominal phase-to-phase voltage Vn</strong> parameter on the <strong>Parameters</strong> tab is automatically adjusted to the phase-to-phase bus voltage computed by the Load Flow tool.<br>If you select <strong>constant I</strong>, the load current is kept constant at its nominal value determined from base voltage specified in the dialog box of the associated Load Flow Bus block and from active power P and reactive power QL and QC specified on the <strong>Parameters</strong> tab of the block dialog box. The effective P and Q therefore vary proportionally to the bus voltage computed by the Load Flow tool. When you apply the load flow solution to the model (by clicking the <strong>Apply</strong> button of the Load Flow tool), the p.u. value of the nominal voltage Vn on the <strong>Parameters</strong> tab is automatically adjusted to the square root of the load voltage (in pu) computed by the Load Flow tool.</td></tr></tbody></table>


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/smart-power-simulation-software-sps/blocks-functions-tools/basics/passives/three-phase-series-rlc-load.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.