> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/smart-power-simulation-software-sps/blocks-functions-tools/machines/blocks/machines-control/synchronous-machines-control/multiband-power-system-stabilizer.md).

# Multiband Power System Stabilizer

## Description

<figure><img src="https://799605156-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FdlNg8IbOdahCpFCyzxSN%2Fuploads%2Fgit-blob-9ffc7fe8888a89dda44b6d0fbb090b0b67a35a8b%2Fmultiband_powe_sys_stab_block.png?alt=media" alt=""><figcaption></figcaption></figure>

The **Multiband Power System Stabilizer** block, located in the **OPAL-RT SPS Software/Electrical Machines** library, outputs a signal with reducing disturbances occurring in a power system induce electromechanical oscillations of the electrical generators. These oscillations, also called power swings, must be effectively damped to maintain the system’s stability. Electromechanical oscillations can be classified in four main categories:

* Local oscillations: between a unit and the rest of the generating station and between the latter and the rest of the power system. Their frequencies typically range from 0.8 Hz to 4.0 Hz.
* Interplant oscillations: between two electrically close generation plants. Frequencies can vary from 1 Hz to 2 Hz.
* Interarea oscillations: between two major groups of generation plants. Frequencies are typically in a range of 0.2 Hz to 0.8 Hz.
* Global oscillation: characterized by a common in-phase oscillation of all generators as found on an isolated system. The frequency of such a global mode is typically under 0.2 Hz. The need for effective damping of such a wide range, almost two decades, of electromechanical oscillations motivated the concept of the multiband power system stabilizer (MB-PSS).

{% hint style="info" %}
This block requires that you have a Control System Toolbox™ license. Otherwise, trying to simulate a model containing this block produces an error..
{% endhint %}

As its name reveals, the MB-PSS structure is based on multiple working bands. Three separate bands are used, respectively dedicated to the low-, intermediate-, and high-frequency modes of oscillations: the low band is typically associated with the power system global mode, the intermediate with the interarea modes, and the high with the local modes.

Each of the three bands is made of a differential bandpass filter, a gain, and a limiter (see the figure called [Conceptual Representation](https://opal-rt.atlassian.net/wiki/spaces/PSPS/pages/1551697520/Multiband+Power+System+Stabilizer#Conceptual-Representation)). The outputs of the three bands are summed and passed through a final limiter producing the stabilizer output Vstab. This signal then modulates the set point of the generator voltage regulator so as to improve the damping of the electromechanical oscillations.

To ensure robust damping, the MB-PSS should include a moderate phase advance at all frequencies of interest to compensate for the inherent lag between the field excitation and the electrical torque induced by the MB-PSS action.

#### **Conceptual Representation**

<figure><img src="https://799605156-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FdlNg8IbOdahCpFCyzxSN%2Fuploads%2Fgit-blob-6d99ddfaf064cf626ac64a0acc5e09b20c0b6b5c%2Fmultiband_powe_sys_stab_model1png?alt=media" alt=""><figcaption></figcaption></figure>

#### **Internal Specifications**

<figure><img src="https://799605156-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FdlNg8IbOdahCpFCyzxSN%2Fuploads%2Fgit-blob-70ee73337bb9de3c239b1a22df540472b220ee03%2Fmultiband_powe_sys_stab_model2.png?alt=media" alt=""><figcaption></figcaption></figure>

The MB-PSS is represented by the IEEE® St. 421.5 PSS 4B type model \[2], illustrated in the figure called Internal Specifications, with built-in speed transducers whose parameters are fixed according to manufacturer’s specifications.

Generally, only a few of the lead-lag blocks in this figure should be used in a given PSS application. Two different approaches are available to configure the settings in order to facilitate the tuning process:

1. Simplified settings: Only the first lead-lag block of each frequency band is used to tune the Multiband Power System Stabilizer block. The differential filters are assumed to be symmetrical bandpass filters respectively tuned at the center frequency FL, FI, and FH. The peak magnitude of the frequency responses (see the figure called Conceptual Representation) can be adjusted independently through the three gains KL, KI, and KH. Only six parameters are therefore required for a simplified tuning of the MB-PSS.
2. Detailed settings: The designer is free to use all the flexibility built into the MB-PSS structure to achieve nontrivial controller schemes and to tackle even the most constrained problem (for example, multi-unit plant including an intermachine mode, in addition to a local mode and multiple interarea modes). In this case, all the time constants and gains appearing in the figure called Internal Specifications have to be specified in the dialog box.

## Ports

### Input

<table data-header-hidden><thead><tr><th width="338.800048828125"></th><th></th></tr></thead><tbody><tr><td><strong>dw</strong> — Synchronous machine speed deviation or acceleration power<br>Scalar</td><td>Synchronous machine speed deviation <em>dw</em> signal (in pu).</td></tr></tbody></table>

### Output

<table data-header-hidden><thead><tr><th width="119.60003662109375"></th><th></th></tr></thead><tbody><tr><td><strong>Vstab</strong> — Stabilization voltage<br>Scalar</td><td>Stabilization voltage, in per unit. Connect this output port to the <strong>Vstab</strong> input port of the <a href="https://www.opal-rt.com/docs/smart-power-simulation-software-sps/blocks-functions-tools/machines/blocks/machines-control/synchronous-machines-control/excitation-systems.md">Excitation System block</a> that you use to control the terminal voltage of the synchronous machine.</td></tr></tbody></table>

## Parameters

<table data-header-hidden><thead><tr><th width="302"></th><th></th></tr></thead><tbody><tr><td><strong>Mode of operation</strong> — Mode of operation<br>Simplified settings (default) | Detailed settings</td><td>Specify the mode of operation of the stabilizer.</td></tr><tr><td><strong>Global gain</strong> — Gain of multiband power system stabilizer<br>1.0 (default)</td><td><p>Overall gain K of the multiband power system stabilizer.</p><p><strong>Dependencies</strong> To enable this parameter, set <strong>Mode of operation</strong> to Simplified settings.</p></td></tr><tr><td><strong>Low frequency band: [FL KL]</strong> — Center frequency and peak gain of low-frequency bandpass filter<br>[0.2 20] (default) | vector of two scalars</td><td><p>Center frequency, in hertz, and peak gain of the low-frequency bandpass filter.</p><p><strong>Dependencies</strong> To enable this parameter, set <strong>Mode of operation</strong> to Simplified settings.</p></td></tr><tr><td><strong>Intermediate frequency band: [FI KI]</strong> — Center frequency and peak gain of intermediate-frequency bandpass filter<br>[0.9 25] (default) | vector of two scalars</td><td><p>Center frequency, in hertz, and peak gain of the intermediate- frequency bandpass filter.</p><p><strong>Dependencies</strong> To enable this parameter, set <strong>Mode of operation</strong> to Simplified settings.</p></td></tr><tr><td><strong>High frequency band: [FH KH]</strong> — Center frequency and peak gain of high-frequency bandpass filter<br>[12.0 145] (default) | vector of two scalars</td><td><p>Center frequency, in hertz, and peak gain of the high-frequency bandpass filter.</p><p><strong>Dependencies</strong> To enable this parameter, set <strong>Mode of operation</strong> to Simplified settings.</p></td></tr><tr><td><strong>Low frequency gains: [KL1 KL2 KL]</strong> — Low frequency gains<br>[66 66 9.4] (default) | vector of three scalars</td><td><p>Gains of the positive and negative branches of the differential filter in the low-frequency band and the overall gain K<sub>L</sub> of the low-frequency band, in pu.</p><p><strong>Dependencies</strong> To enable this parameter, set <strong>Mode of operation</strong> to Detailed settings.</p></td></tr><tr><td><strong>Low frequency time constants</strong> — Low frequency time constants<br>[1.667 2 0 0 0 0 2 2.4 0 0 0 0 1 1] (default) | vector of 14 nonnegative scalars</td><td><p>Time constants, in seconds, of the lead-lag blocks in the positive and negative branches of the low-frequency filter. You must specify these twelve time constants and two gains: [T<sub>B1</sub> T<sub>B2</sub> T<sub>B3</sub> T<sub>B4</sub> T<sub>B5</sub> T<sub>B6</sub> T<sub>B7</sub> T<sub>B8</sub> T<sub>B9</sub> T<sub>B10</sub> T<sub>B11</sub> T<sub>B12</sub> K<sub>B11</sub> K<sub>B17</sub>] Set K<sub>B11</sub> to 0 in order to make the first block of the positive filter branch a washout block. Set K<sub>B11</sub> to 1 in order to make the block a lead-lag block. Set K<sub>B17</sub> to 0 in order to make the first block of the negative filter branch a washout block. Set K<sub>B17</sub> to 1 in order to make the block a lead-lag block.</p><p><strong>Dependencies</strong> To enable this parameter, set <strong>Mode of operation</strong> to Detailed settings.</p></td></tr><tr><td><strong>Intermediate frequency gains: [KI1 KI2 KI]</strong> — Intermediate frequency gains<br>[66 66 47.6] (default) | vector of three scalars</td><td><p>Gains of the positive and negative branches of the differential filter in the intermediate-frequency band and the overall gain K<sub>I</sub> of the intermediate-frequency band, in pu.</p><p><strong>Dependencies</strong> To enable this parameter, set <strong>Mode of operation</strong> to Detailed settings.</p></td></tr><tr><td><strong>Intermediate frequency time constants</strong> — Intermediate frequency time constants<br>[1 1 0.25 0.3 0 0 1 1 0.3 0.36 0 0 0 0] (default) | vector of 14 nonnegative scalars</td><td><p>Time constants, in seconds, of the lead-lag blocks in the positive and negative branches of the intermediate-frequency filter. You must specify these twelve time constants and two gains: [T<sub>I1</sub> T<sub>I2</sub> T<sub>I3</sub> T<sub>I4</sub> T<sub>I5</sub> T<sub>I6</sub> T<sub>I7</sub> T<sub>I8</sub> T<sub>I9</sub> T<sub>I10</sub> T<sub>I11</sub> T<sub>I12</sub> K<sub>I11</sub> K<sub>I17</sub>] Set K<sub>I11</sub> to 0 in order to make the first block of the positive filter branch a washout block. Set K<sub>I11</sub> to 1 in order to make the block a lead-lag block. Set K<sub>I17</sub> to 0 in order to make the first block of the negative filter branch a washout block. Set K<sub>I17</sub> to 1 in order to make the block a lead-lag block.</p><p><strong>Dependencies</strong> To enable this parameter, set <strong>Mode of operation</strong> to Detailed settings.</p></td></tr><tr><td><strong>High frequency gains: [KH1 KH2 KH]</strong> — High frequency gains<br>[66 66 233] (default) | vector of three scalars</td><td><p>Gains of the positive and negative branches of the differential filter in the high-frequency band and the overall gain K<sub>I</sub> of the high-frequency band, in pu.</p><p><strong>Dependencies</strong> To enable this parameter, set <strong>Mode of operation</strong> to Detailed settings.</p></td></tr><tr><td><strong>High frequency time constants</strong> — High frequency time constants<br>[0.01 0.012 0 0 0 0 0.012 0.0144 0 0 0 0 1 1] (default) | vector of 14 nonnegative scalars</td><td><p>Time constants, in seconds, of the lead-lag blocks in the positive and negative branches of the high-frequency filter. You must specify these twelve time constants and two gains: [T<sub>H1</sub> T<sub>H2</sub> T<sub>H3</sub> T<sub>H4</sub> T<sub>H5</sub> T<sub>H6</sub> T<sub>H7</sub> T<sub>H8</sub> T<sub>H9</sub> T<sub>H10</sub> T<sub>H11</sub> T<sub>H12</sub> K<sub>H11</sub> K<sub>H17</sub>] Set K<sub>H11</sub> to 0 in order to make the first block of the positive filter branch a washout block. Set K<sub>H11</sub> to 1 in order to make the block a lead-lag block. Set K<sub>H17</sub> to 0 in order to make the first block of the negative filter branch a washout block. Set K<sub>H17</sub> to 1 in order to make the block a lead-lag block.</p><p><strong>Dependencies</strong> To enable this parameter, set <strong>Mode of operation</strong> to Detailed settings.</p></td></tr><tr><td><strong>Signal limits [VLmax VImax VHmax VSmax]</strong> — Signal limits<br>[.075 .15 .15 .15] (default) | vector of four scalars</td><td>Limits imposed on the output of the low-, intermediate-, and high-frequency bands and the limit VSmax imposed on the output of the stabilizer, all in pu.</td></tr><tr><td><strong>Plot frequency response</strong> — Plot frequency response<br>off (default) | on</td><td>Select this option to display a plot of the frequency response of the stabilizer when you click the <strong>Apply</strong> button.</td></tr><tr><td><strong>Magnitude in dB</strong> — Plot magnitude of frequency response<br>on (default) | off</td><td><p>Select this option to plot the magnitude of the frequency response to plot, in dB.</p><p><strong>Dependencies</strong> To enable this parameter, select the <strong>Plot frequency response</strong> parameter.</p></td></tr><tr><td><strong>Frequency range</strong> — Frequency range<br>logspace(-2,2,500) (default)</td><td><p>Frequency range used to plot the frequency response of the stabilizer.</p><p><strong>Dependencies</strong> To enable this parameter, select the <strong>Plot frequency response</strong> parameter.</p></td></tr></tbody></table>


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/smart-power-simulation-software-sps/blocks-functions-tools/machines/blocks/machines-control/synchronous-machines-control/multiband-power-system-stabilizer.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.