> For the complete documentation index, see [llms.txt](https://www.opal-rt.com/docs/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://www.opal-rt.com/docs/smart-power-simulation-software-sps/example-models/get-started-with-sps/use-of-surge-arresters-in-transmission-system.md).

# Use of Surge Arresters in Transmission System

This example shows the use of surge arresters in a series- and shunt-compensated 735 kV AC transmission system.

<figure><img src="https://799605156-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FdlNg8IbOdahCpFCyzxSN%2Fuploads%2Fgit-blob-2be5def3db3ca793d306af3c85e29becba903293%2Fuse_surge_arresters_transmission_system.png?alt=media" alt=""><figcaption></figcaption></figure>

## Description

A 735 kV equivalent transmission system feeds a load through a 200 km transmission line. The line is series compensated at the midpoint and shunt compensated at its receiving end. A fault is applied at the load terminals. The fault is cleared by load breaker opening. For simplification purposes, only one phase of the transmission system is modeled. All parameters correspond to positive-sequence.

The three-phase short-circuit level of the transmission system is 15000 MVA. The line is 40% series compensated by a capacitor (26.2 ohms at 60 Hz) and shunt compensated by a 330 Mvar (110 Mvar/phase) inductor at the load end.

The series capacitor and shunt inductor are both protected by metal oxide varistors (MOV).

* The series capacitor varistor (MOV1) consists of 30 columns protecting the capacitor at 2.5 times its rated voltage (rated voltage is obtained for a 2000 kA line rated current).\
  The corresponding protection voltage (defined at 15 kA = 500 A per column) is: 2.5 \* 26.2 \* 2 kA \* sqrt(2) = 185 kV.
* The shunt inductor is protected by a 2-column arrester (MOV2) at 1.8 p.u. of nominal phase-to-ground voltage (424.4 kVrms).\
  The corresponding protection voltage (defined at 1 kA or 500 A/column) is: 1.8 \* 424.4 \* sqrt(2) = 1080 kV.

## Simulation

Start the simulation and observe the MOV voltages and currents on Scope1 and Scope2.

* **At fault application**, the capacitor voltage increases and MOV1 conducts. Peak current reaches 8.4 kA on the 2nd pulse 2 cycles after fault application; the MOV current is symmetric (4.5 kA current pulses at every half cycle).
* **At fault clearing**, the overvoltage produced at bus B2 is limited by the shunt MOV2. The fast transient produces an 850 A current pulse in the MOV.

## Command

Example model name: power\_surgnetwork

{% code lineNumbers="true" %}

```matlab
open('power_surgnetwork')
```

{% endcode %}


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://www.opal-rt.com/docs/smart-power-simulation-software-sps/example-models/get-started-with-sps/use-of-surge-arresters-in-transmission-system.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.